Festo 1971599 CPX-FVDA-P2 PROFIsafe Shut-Off Output Module

Festo 1971599 CPX-FVDA-P2 PROFIsafe Shut-Off Output Module

24 V DC P-M switching module with one internal valve-supply shut-off channel, two external outputs, channel diagnostics, SIL 3/PL e capability and 50 g mass.

Festo Remote I/O and Network Interface Components

Festo CPX-FVDA-P2 PROFIsafe Shut-Off Output Module

BrandFesto
Model IdentifierCPX-FVDA-P2
Official Part Number1971599

Technical Overview

The Festo CPX-FVDA-P2 is a PROFIsafe output module for switching off the 24 V DC valve supply within a compatible CPX terminal and supplying two external output circuits. Its P-M switching logic provides one internal valve-voltage channel and two external outputs, with 1.5 A maximum per channel and 5 A maximum module current. Wire-break, short-circuit/overload, cross-circuit and valve-undervoltage diagnostics support channel monitoring. Festo specifies safe switch-off capability up to SIL 3 and category 3, PL e within the prescribed system architecture. The 50 g electronics module uses a dedicated interlinking block; protection depends on the selected connection block.

PROFIsafe 24 V DC output module with internal valve-supply shut-off, two external outputs, P-M switching and per-channel diagnostics.

Key Features

  • One internal valve-supply shut-off channel and two external outputs
  • 24 V DC nominal supply with −15%/+20% permissible variation
  • P-M output switching logic
  • 1.5 A maximum supply per channel and 5 A maximum total module current
  • Maximum reaction time to switch-off command: F_WD_TIME + 23 ms
  • Safe switch-off capability: SIL 3 and category 3, Performance Level e, within the prescribed architecture
  • Wire-break, short-circuit/overload, cross-circuit and valve-undervoltage diagnostics
  • Internal electronic fuse per channel; configurable diagnostic and wire-break monitoring behavior
  • Six-byte maximum input and output address volumes; module and channel LEDs
  • 50 g electronics-module weight; protection depends on connection block

Combine internal valve-supply shut-off and two external output circuits with PROFIsafe commands and channel-level diagnostics in a CPX terminal.

Technical Specification Matrix

ParameterValue
Physical Weight (kg)0.05
Ambient temperature-5 °C...50 °C
Note on ambient temperatureObserve derating curve for pneumatic interface
Storage temperature-20 °C...70 °C
Degree of protectionDepending on the connection block
Corrosion resistance class CRC1 - Low corrosion stress; (installed)
Max. cable length200 M
LABS (PWIS) conformityVDMA24364-B2-L
CE mark (see declaration of conformity)To EU EMC Directive; To EC Machinery Directive; In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity)To UK instructions for EMC; To UK regulations for machines; To UK RoHS instructions
Approvalc UL us - Recognised (Oil)
Certificate issuing authorityGerman Technical Control Board (TÜV) Rhld 01/205/5294.02/23; German Technical Control Board (TÜV) Rhld 01/205U/5294.01/23
Note on materialsRoHS compliant
Material housingReinforced PA; Makrolon®
Probability of Failure per Hour (PFH)1E-09
LED display1 fail-safe mode protocol active; 1 Group diagnostics; 3 Channel diagnostics; 3 Channel status
DiagnosisWire break per channel; Short circuit/overload per channel; Cross circuit; Undervoltage of valves
Max. address volume, inputs6 Byte
Max. address volume, outputs6 Byte
Number of outputs2
Note on outputs1 internal channel to switch off the valve voltage; 2 external outputs
ParameterisationDiagnostic behaviour; Wire break monitoring per channel
Nominal operating voltage DC24 V
Permissible voltage fluctuations-15% / +20%
Residual ripple2 Vpp within voltage range
Intern power consumption nominal operating voltageTypically 25 mA (power supply for electronics); Typ. 65 mA (load voltage supply for valve)
Load capacity against FE400 nF
Switching logic for outputsP-M switching
Max. reaction time to switch-off commandF_WD_TIME + 23 ms
Safety functionSafely switching off supply voltage for the valves
Safety Integrity Level (SIL)Safe switch-off/SIL 3
Performance Level (PL)Safe switch-off/category 3, Performance Level e
Max. power supply per channel1.5 A
Max. total current per module5 A
Voltage drop per channel0.6 V
Isolation channel - channelNo
Isolation channel - internal busYes, with intermediate air supply
Fuse protection (short circuit)Internal electronic fuse per channel
Supported CPX fieldbus familiesPROFINET or PROFIBUS with the manufacturer-specified compatible node/software release
Interlinking block for this CPX electronics-module assemblyCPX-M-GE-EV-FVO, as listed in the manufacturer ordering table

Industrial Applications

1. Valve-Supply Shut-Off in a CPX Pneumatic Station

A machine safety architecture needs to remove the electrical supply to valves connected through a compatible CPX terminal. The module provides an internal channel specifically for switching off valve supply voltage and receives commands through the prescribed PROFIsafe system. Its maximum reaction time is F_WD_TIME plus 23 ms; resulting valve and actuator behavior remains part of the complete pneumatic design.

Problem Solved

The internal channel provides a documented electrical shut-off point for the valve supply, allowing that supply circuit to be included in the machine’s PROFIsafe control architecture.

Internal valve-supply channel PROFIsafe F_WD_TIME + 23 ms

2. Shut-Off Commands to External Consuming Devices

An automation station needs monitored supply switching for two external consuming devices as well as its internal valve circuit. This module provides two external outputs through a compatible connection block, with P-M switching and 1.5 A maximum current per channel. The 5 A module total is a separate limit, and the required interlinking and connection blocks define the physical station assembly.

Problem Solved

Two external output circuits extend the module’s supply-switching function beyond the internal valve channel, providing defined electrical interfaces for compatible external consumers within the documented current limits.

Two external outputs P-M switching 1.5 A per channel

3. Channel Fault Monitoring During Machine Operation

A station needs to identify electrical faults associated with its shut-off output circuits. The module provides wire-break and short-circuit/overload diagnostics per channel, together with cross-circuit and valve-undervoltage diagnostics. Configurable wire-break monitoring and diagnostic behavior complement group and channel LEDs, giving the control system and maintenance personnel documented information about the affected output path.

Problem Solved

Channel diagnostics and local indication make specified electrical fault conditions observable, helping relate a reported problem to the output circuit during commissioning and machine fault investigation.

Per-channel diagnostics Wire-break monitoring Group/channel LEDs