IM 155-6PN High Feature PROFINET interface module
The IM 155-6PN High Feature is designed mainly for PROFINET applications with a high, flexible demand for functions, as well as a large station expansion of up to 64 modules (max. 1024 IO signals). All I/O modules, including PROFIsafe, can be used. In addition, the station can be expanded with as many as 16 IP67 modules of the SIMATIC ET 200AL series using BA-Send/BU-Send.
Unlike the other interface modules, the IM 155-6PN/2 HF supports the following additional functions:
With its third port, the 3-port IM155-6PN/3 HF interface module allows the expansion of the PROFINET topology by a spur line. Typical applications are:
The local IO data coupling allows data to be exchanged between up to 4 controllers quickly, deterministically, and without elaborate configuring.
IM 155-6PN High Speed PROFINET interface module
The IM 155-6PN High Speed is designed mainly for PROFINET applications with very short response times. All I/O modules, including PROFIsafe, can be used.
Compared to the IM 155-6PN HF, the IM 155-6PN HS has the following functional differences:
IM 155-6DP High Feature PROFIBUS interface module
The IM 155-DP High Feature is designed mainly for PROFIBUS applications with average station expansion of up to 32 modules (max. 512 IO signals). All I/O modules, including PROFIsafe, can be used. In addition, the station can be expanded with as many as 16 IP67 modules of the SIMATIC ET 200AL series using BA-Send/BU-Send.
| Article number | 6ES7155-6AU01-0CN0 | 6ES7155-6AU30-0CN0 | 6ES7155-6AU00-0DN0 | 6ES7155-6BA01-0CN0 |
| ET 200SP, IM155-6PN/2 HF | ET 200SP, IM155-6PN/3 HF | ET 200SP, IM155-6PN HS | ET 200SP, IM155-6DP HF incl. DP-Connect. | |
| General information | ||||
| Product type designation | IM 155-6 PN/2 HF | IM 155-6 PN/3 HF | IM 155-6 PN HS | IM 155-6 DP HF |
| HW functional status | From FS02 | From FS02 | From FS02 | From FS02 |
| Firmware version | V4.2 | V4.2 | V4.0 | V4.2 |
| ● FW update possible | Yes | Yes | Yes | |
| Product function | ||||
| ● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
| ● Module swapping during operation (hot swapping) | Yes; Multi-hot swapping | Yes; Multi-hot swapping | Yes; Multi-hot swapping | Yes; Multi-hot swapping |
| ● Isochronous mode | Yes | Yes | Yes | No |
| ● Tool changer | Yes; Docking station and docking unit | Yes; Docking station and docking unit | ||
| ● Local coupling, IO data | No | Yes | ||
| — Number of coupling modules | 16 | |||
| — Number of coupling submodules per module | 4 | |||
| ● Local coupling, data records | No | No | ||
| Engineering with | ||||
| ● STEP 7 TIA Portal configurable/integrated from version | STEP 7 V15.1 or higher | V15.1 | STEP 7 V14 or higher | V15 SP1 |
| ● STEP 7 configurable/integrated from version | Configurable via GSD file | Configurable via GSD file | V5.5 SP4 and higher | As of V5.5 SP4, only up to FW V3.1 |
| ● PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher | |||
| ● PROFINET from GSD version/GSD revision | GSDML V2.3 | GSDML V2.3 | – / V2.3 | |
| Configuration control | ||||
| via dataset | Yes | Yes | Yes | Yes |
| Supply voltage | ||||
| Rated value (DC) | 24 V | 24 V | 24 V | 24 V |
| permissible range, lower limit (DC) | 19.2 V | 19.2 V | 19.2 V | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | 28.8 V |
| Reverse polarity protection | Yes | Yes | Yes | Yes |
| Mains buffering | ||||
| ● Mains/voltage failure stored energy time | 10 ms | 10 ms | 5 ms | 10 ms |
| Input current | ||||
| Current consumption (rated value) | 175 mA; At 24 V, 2 slots 2x RJ45 BusAdapter, no I/O modules | |||
| Current consumption, max. | 700 mA | 950 mA | 500 mA | 335 mA |
| Inrush current, max. | 4.5 A | 9 A | 4.5 A | 1.6 A |
| I²t | 0.25 A²·s | 0.34 A²·s | 0.09 A²·s | 0.038 A²·s |
| Power loss | ||||
| Power loss, typ. | 2.4 W | 4.9 W | 1.7 W | 1.5 W |
| Address area | ||||
| Address space per module | ||||
| ● Address space per module, max. | 288 byte; For input and output data respectively | 288 byte; For input and output data respectively | 32 byte; For input and output data respectively | 32 byte; per input / output |
| Address space per station | ||||
| ● Address space per station, max. | 1 440 byte; Dependent on configuration | 1 440 byte; Dependent on configuration | 968 byte; For input and output data respectively | 244 byte; per input / output |
| Hardware configuration | ||||
| Rack | ||||
| ● Quantity of operable ET 200SP modules, max. | 64 | 64 | 30 | 32 |
| ● Quantity of operable ET 200AL modules, max. | 16 | 16 | 0 | 16 |
| Submodules | ||||
| ● Number of submodules per station, max. | 256 | 256 | 125 | |
| Time stamping | ||||
| Accuracy | 10 ms | |||
| Interfaces | ||||
| Number of PROFINET interfaces | 1; 2 ports (switch) | 1; 3 ports (switch) | 1; 2 ports (switch) | |
| Number of PROFIBUS interfaces | 1 | |||
| 1. Interface | ||||
| Interface types | ||||
| ● RS 485 | Yes | |||
| ● Number of ports | 2; via BusAdapter | 3; Via 2 BusAdapter slots | 2 | |
| ● integrated switch | Yes | Yes | Yes | |
| ● BusAdapter (PROFINET) | Yes; compatible BusAdapters: BA 2x RJ45, BA 2x M12, BA 2x FC, BA 2x LC, BA LC/RJ45, BA LC/FC, BA 2x SCRJ, BA SCRJ/RJ45, BA SCRJ/FC, | Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC | Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC | |
| ● Output current of the interface, max. | 90 mA | |||
| Protocols | ||||
| ● PROFINET IO Device | Yes | Yes | Yes | |
| ● PROFIBUS DP slave | Yes | |||
| ● Open IE communication | Yes | Yes | Yes | |
| ● Media redundancy | Yes; PROFINET MRP | Yes; PROFINET MRP | Yes; As MRP or MRPD client; max. 50 or 30 devices in the ring | |
| Interface types | ||||
| RJ 45 (Ethernet) | ||||
| ● Transmission procedure | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | |
| ● 10 Mbps | No | No | No | |
| ● 100 Mbps | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | |
| ● Autonegotiation | Yes | Yes | Yes | |
| ● Autocrossing | Yes | Yes | Yes | |
| RS 485 | ||||
| ● Transmission rate, max. | 12 Mbit/s | |||
| Protocols | ||||
| Number of connections | ||||
| ● Number of MtM communication relationships/connections, max. | 16 | 16 | ||
| PROFINET IO Device | ||||
| Services | ||||
| — IRT | Yes; 250 μs, 500 μs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 µs to 4 ms in 125 µs frame | Yes; 250 μs, 500 μs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 µs to 4 ms in 125 µs frame | Yes; 125 µs, 250 µs, 500 µs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 µs to 4 ms in 125 µs frame | |
| — PROFIenergy | Yes | Yes | Yes | |
| — Prioritized startup | Yes | Yes | Yes | |
| — Shared device | Yes | Yes | Yes | |
| — Number of IO Controllers with shared device, max. | 4 | 4 | 4 | |
| Redundancy mode | ||||
| ● PROFINET system redundancy (S2) | Yes; NAP S2 | Yes; NAP S2 | No | |
| ● Redundant PROFINET configuration (R1) | No | |||
| ● H-Sync forwarding | Yes | Yes | ||
| Media redundancy | ||||
| — MRP | Yes | Yes | Yes | |
| — MRPD | No | No | Yes | |
| Open IE communication | ||||
| ● TCP/IP | Yes | Yes | Yes | No |
| ● SNMP | Yes | Yes | Yes | |
| ● LLDP | Yes | Yes | Yes | |
| PROFIBUS DP | ||||
| Services | ||||
| — SYNC capability | Yes | |||
| — FREEZE capability | Yes | |||
| — DPV0 | Yes | |||
| — DPV1 | Yes | |||
| Isochronous mode | ||||
| Equidistance | Yes | Yes | Yes | |
| shortest clock pulse | 250 µs | 250 µs | 125 µs | |
| max. cycle | 4 ms | 4 ms | 4 ms | |
| Bus cycle time (TDP), min. | 250 µs | 250 µs | 125 µs | |
| Jitter, max. | 1 µs | 1 µs | 0.25 µs | |
| Interrupts/diagnostics/status information | ||||
| Status indicator | Yes | Yes | Yes | Yes |
| Alarms | Yes | Yes | Yes | Yes |
| Diagnostics function | Yes | Yes | Yes | Yes |
| Diagnostics indication LED | ||||
| ● RUN LED | Yes; green LED | Yes; green LED | Yes; green LED | Yes; green LED |
| ● ERROR LED | Yes; red LED | Yes; red LED | Yes; red LED | Yes; red LED |
| ● MAINT LED | Yes; Yellow LED | Yes; Yellow LED | Yes; Yellow LED | Yes; Yellow LED |
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED |
| ● Connection display LINK TX/RX | Yes; 2x green link LEDs on BusAdapter | Yes; 2x green link LEDs on BusAdapter | Yes; 2x green link LEDs on BusAdapter | |
| ● Connection display DP | Yes; green DP LED | |||
| Potential separation | ||||
| between backplane bus and electronics | No | No | No | No |
| between PROFIBUS DP and all other circuit components | Yes | |||
| between PROFINET and all other circuits | Yes | Yes | Yes | |
| between supply and all other circuits | No | No | No | No |
| Permissible potential difference | ||||
| between different circuits | Safety extra low voltage SELV | |||
| Isolation | ||||
| Isolation tested with | 707 V DC (type test) | 707 V DC (type test) | 707 V DC between supply voltage and electronics (type test); 1 500 V AC between Ethernet and electronics (type test) | 707 V DC (type test) |
| Standards, approvals, certificates | ||||
| Network loading class | 3 | 3 | 3 | |
| Security level | According to Security Level 1 Test Cases V1.1.1 | According to Security Level 1 Test Cases V1.1.1 | According to Security Level 1 Test Cases V1.1.1 | |
| Ambient conditions | ||||
| Ambient temperature during operation | ||||
| ● horizontal installation, min. | -30 °C; No condensation | -30 °C | -25 °C; No condensation | -25 °C |
| ● horizontal installation, max. | 60 °C | 60 °C | 60 °C | 60 °C |
| ● vertical installation, min. | -30 °C; No condensation | -30 °C | -25 °C; No condensation | -25 °C |
| ● vertical installation, max. | 50 °C | 50 °C | 50 °C | 50 °C |
| Altitude during operation relating to sea level | ||||
| ● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| connection method / header | ||||
| ET-Connection | ||||
| ● via BU/BA Send | Yes; + 16 ET 200AL modules | Yes; + 16 ET 200AL modules | No | Yes; + 16 ET 200AL modules |
| Mechanics/material | ||||
| Strain relief | Yes; Optional | Yes; Optional | ||
| Dimensions | ||||
| Width | 50 mm | 100 mm | 50 mm | 50 mm |
| Height | 117 mm | 117 mm | 117 mm | 117 mm |
| Depth | 74 mm | 74 mm | 74 mm | 74 mm |
| Weights | ||||
| Weight, approx. | 120 g; without BusAdapter | 220 g; without BusAdapter | 147 g; without BusAdapter | 150 g |
| Weight | N/A |
|---|---|
| Dimensions | N/A |