| Input |
|
| Article number |
6EP3333-6SB00-0AY0 |
| type of the power supply network |
1-phase AC or DC |
| supply voltage at AC |
|
| ● minimum rated value |
100 V |
| ● maximum rated value |
240 V |
| ● initial value |
85 V |
| ● full-scale value |
264 V |
| input voltage |
|
| ● at DC |
110 … 300 V |
| design of input wide range input |
Yes |
| overvoltage overload capability |
300 V AC for 1 s |
| operating condition of the mains buffering |
at Vin = 187 V |
| buffering time for rated value of the output current in the |
40 ms |
| event of power failure minimum |
|
| operating condition of the mains buffering |
at Vin = 187 V |
| line frequency |
|
| ● 1 rated value |
50 Hz |
| ● 2 rated value |
60 Hz |
| line frequency |
47 … 63 Hz |
| input current |
|
| ● at rated input voltage 120 V |
1.95 A |
| ● at rated input voltage 230 V |
0.97 A |
| current limitation of inrush current at 25 °C maximum |
31 A |
| I2t value maximum |
2.5 A²·s |
| fuse protection type |
internal |
| ● in the feeder |
Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C |
| Output |
|
| voltage curve at output |
Controlled, isolated DC voltage |
| output voltage at DC rated value |
24 V |
| output voltage |
|
| ● at output 1 at DC rated value |
24 V |
| relative overall tolerance of the voltage |
3% |
| relative control precision of the output voltage |
|
| ● on slow fluctuation of input voltage |
0.1% |
| ● on slow fluctuation of ohm loading |
0.1% |
| residual ripple |
|
| ● maximum |
200 mV |
| ● typical |
30 mV |
| voltage peak |
|
| ● maximum |
300 mV |
| ● typical |
50 mV |
| adjustable output voltage |
22.2 … 26.4 V |
| product function output voltage adjustable |
Yes |
| type of output voltage setting |
via potentiometer |
| display version for normal operation |
Green LED for output voltage OK |
| behavior of the output voltage when switching on |
No overshoot of Vout (soft start) |
| response delay maximum |
0.5 s |
| voltage increase time of the output voltage |
|
| ● typical |
100 ms |
| output current |
|
| ● rated value |
4 A |
| ● rated range |
0 … 4 A; +55 … +70 °C: Derating 2%/K |
| supplied active power typical |
96 W |
| product feature |
|
| ● bridging of equipment |
Yes |
| number of parallel-switched equipment resources for |
2 |
| increasing the power |
|
| Efficiency |
89% |
| efficiency in percent |
|
| power loss [W] |
12 W |
| ● at rated output voltage for rated value of the output |
|
| current typical |
0.3 W |
| ● during no-load operation maximum |
|
| Closed-loop control |
0.2% |
| relative control precision of the output voltage with rapid |
|
| fluctuation of the input voltage by +/- 15% typical |
|
| relative control precision of the output voltage at load step |
2% |
| of resistive load 10/90/10 % typical |
|
| setting time |
|
| ● load step 10 to 90% typical |
1 ms |
| ● load step 90 to 10% typical |
1 ms |
| Protection and monitoring |
|
| design of the overvoltage protection |
Yes, according to EN 60950-1 |
| response value current limitation typical |
5 A |
| property of the output short-circuit proof |
Yes |
| design of short-circuit protection |
Constant current characteristic |
| enduring short circuit current RMS value |
|
| ● maximum |
5 A |
| overcurrent overload capability in normal operation |
overload capability 150% lout rated typ. 200 ms |
| display version for overload and short circuit |
– |
| measuring point for output current |
50 mV =^ 4 A |
| overcurrent overload capability when switching on |
150% Iout rated typ. 200 ms |
| Safety |
|
| galvanic isolation between input and output |
Yes |
| galvanic isolation |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
| operating resource protection class |
Class II (without protective conductor) |
| protection class IP |
IP20 |
| Approvals |
|
| certificate of suitability |
|
| ● CE marking |
Yes |
| ● UL approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 |
| ● CSA approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 |
| ● cCSAus, Class 1, Division 2 |
No |
| ● ATEX |
No |
| certificate of suitability |
|
| ● IECEx |
No |
| ● NEC Class 2 |
No |
| ● ULhazloc approval |
No |
| ● FM registration |
No |
| type of certification CB-certificate Y |
Yes |
| certificate of suitability |
|
| ● EAC approval |
Yes |
| certificate of suitability shipbuilding approval |
Yes |
| shipbuilding approval |
ABS, BV, DNV GL, LRS |
| Marine classification association |
|
| ● American Bureau of Shipping Europe Ltd. (ABS) |
Yes |
| ● French marine classification society (BV) |
Yes |
| ● DNV GL |
Yes |
| ● Lloyds Register of Shipping (LRS) |
Yes |
| ● Nippon Kaiji Kyokai (NK) |
No |
| EMC |
|
| standard |
|
| ● for emitted interference |
EN 55022 Class B |
| ● for mains harmonics limitation |
EN 61000-3-2 |
| ● for interference immunity |
EN 61000-6-2 |
| environmental conditions |
|
| ambient temperature |
|
| ● during operation |
-25 … +70 °C; with natural convection |
| ● during transport |
-40 … +85 °C |
| ● during storage |
-40 … +85 °C |
| environmental category according to IEC 60721 |
Climate class 3K3, 5 … 95% no condensation |
| Mechanics |
|
| type of electrical connection |
screw-type terminals |
| ● at input |
L, N: 1 screw terminal each for 0.5 … 2.5 mm2 single-core/finely stranded |
| ● at output |
+, -: 1 screw terminal each for 0.5 … 2.5 mm² |
| ● for auxiliary contacts |
– |
| width of the enclosure |
72 mm |
| height of the enclosure |
90 mm |
| depth of the enclosure |
53 mm |
| required spacing |
|
| ● top |
20 mm |
| ● bottom |
20 mm |
| ● left |
0 mm |
| ● right |
0 mm |
| net weight |
0.29 kg |
| product feature of the enclosure housing can be lined up |
Yes |
| fastening method |
Snaps onto DIN rail EN 60715 35×7.5/15, direct mounting in different mounting positions |
| MTBF at 40 °C |
2 391 480 h |
| other information |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|
|