Main |
Part Number |
XPSAC3721 |
Product Series |
Preventa Security Automation |
product type |
Preventa Security Module |
Security module name |
XPSAC |
Security Module Application |
Monitoring of emergency stops and switches |
module function |
Emergency stop |
switch monitoring |
Security Level |
Can reach PL e/category 4 conforms to EN/ISO 13849-1 |
Can achieve SILCL 3 conforms to EN/IEC 62061 |
Safe and reliable data |
MTTFd = 210.4 years according to EN/ISO 13849-1 |
DC > 99 % according to EN/ISO 13849-1 |
PFHd = 3.56E-9 1/h according to EN/IEC 62061 |
startup type |
No monitoring |
Wiring capacity |
Captive screw clamp terminal, 1 x 0.14…1 x 2.5 mm² flexible cable end with double frame |
captive screw clamp terminal, 1 x 0.14…1 x 2.5 mm² rigid cable end with double frame captive |
screw terminal Clamp terminal, 1 x 0.25…1 x 1.5 mm² flexible cable end with double frame |
captive screw clamp terminal, 1 x 0.25…1 x 2.5 mm² flexible cable end with double frame |
captive screw clamp terminal , 2 x 0.14…2 x0.75 mm² flexible with cable ends, with double frame |
captive screw clamp terminals, 2 x 0.14…2 x0.75 mm² rigid with cable ends, with double frame |
captive screw clamp terminals , 2 x 0.25…2 x 1 mm² flexible cord with cable end with double frame |
captive screw clamp terminal, 2 x 0.5…2 x 1.5 mm² flexible cord with cable end with double frame |
output type |
Relay Momentary Opening, 3 NO Circuits, Volt-free |
Number of other loops |
1 solid state output |
Rated supply voltage [Us] |
230V AC – 15…10 % |
Additional information |
power supply frequency |
50/60Hz |
Maximum power consumption in VA |
6 VA AC |
Control circuit voltage |
230V |
Breaking capacity |
180 VA holding AC-15 C300 relay output |
1800 VA surge AC-15 C300 relay output |
Breaking capacity |
1.5 A at 24 V (DC-13) Time constant: 50 ms for relay output |
output thermal current |
6 A per relay for relay outputs |
Conventional thermal current [Ith] |
10.5A |
Fuses for use with relays |
4 A gG or gL for relay output acc. to EN/IEC 60947-5-1, DIN VDE 0660 part 2006 |
A fast fuse for relay output acc. to EN/IEC 60947-5-1, DIN VDE 0660 part 200 |
Minimum output current |
10 mA for relay output |
Minimum output voltage |
16 V for relay outputs |
Maximum response time on input open |
100ms |
Rated insulation voltage [Ui] |
300 V (pollution degree 2) conforming to IEC 60947-5-1 |
300 V (pollution degree 2) conforming to DIN VDE 0110 part 1 |
Rated impulse withstand voltage [Uimp] |
4 kV overvoltage category III conforming to IEC 60947-5-1 |
4 kV overvoltage category III conforming to DIN VDE 0110 part 1 |
local signal indication |
2 leds |
current consumption |
25 mA on 230V AC mains |
installation method |
35 mm DIN rail |
Product Weight |
0.21kg |
environment |
Standards compliant |
EN/IEC 60947-5-1 |
EN/ISO 13850 |
EN 1088/ISO 14119 |
EN 60204-1 |
certified product |
TÜV |
UL |
CSA |
IP protection class |
IP20 (screw terminals) conforming to EN/IEC 60529 |
IP40 (cabinet) conforming to EN/IEC 60529 |
operating temperature |
-10…55 °C |
storage environment temperature |
-25…85°C |
packaging unit |
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
12.1 cm |
Package 1 Width |
2.8cm |
Package 1 Length |
10.5cm |
Package 1 Weight |
242.0g |
Unit Type of Package 2 |
S01 |
Number of Units in Package 2 |
16 |
Package 2 Height |
15.0cm |
Package 2 Width |
15.0cm |
Package 2 Length |
40.0cm |
Package 2 Weight |
4.204 kg |
contract warranty |
Warranty |
18 months |