| Main |
| Part Number |
LC1D115004M7 |
| Product Series |
TeSys |
| Product Series |
TeSys Deca |
| product type |
Contactor |
| product short name |
LC1D |
| Application field of contactor |
Applied to non-inductive or micro-inductive load, resistance furnace |
| use category |
AC-1 |
| number of poles |
4P |
| Rated working voltage [Ue] |
Power circuit: <= 1000 V AC 25…400 Hz |
| Power circuit: <= 460 V DC |
| Rated operating current [Ie] |
200 A 60 °C) at <= 440 V AC AC-1 for power circuits |
| [Uc] control circuit voltage |
230V AC 50/60Hz |
| Additional information |
| model |
LC1D |
| Loop contact type |
4 NO |
| Contactor Compatibility Features |
M14 |
| protection cap |
Bring |
| Conventional thermal current [Ith] |
200 A at <60 °C for power circuits |
| Rated making capacity [Irms] |
1260 A at 440 V for power circuits conforming to IEC 60947 |
| Rated breaking capacity |
1100 A at 440 V for power circuits conforming to IEC 60947 |
| Rated short-time withstand current [Icw] |
250 A at <40 °C – 10 min for power circuit |
| 550 A at <40 °C – 1 min for power circuit |
| 950 A at <40 °C – 10 s for power circuit |
| 1100 A at <40 °C – 1 s for power circuits |
| Fuses for use with relays |
250 A gG at <= 690 V with type 1 suitable power circuit |
| 200 A gG at <= 690 V with type 2 suitable power circuit |
| average impedance |
0.6 mΩ – Ith 200 A 50 Hz for power circuits |
| power consumption per pole |
24W AC-1 |
| Rated insulation voltage [Ui] |
Power circuit: 600 V CSA certified |
| Power circuit: 600 V UL certified |
| Power circuit: 1000 V conforming to IEC 60947-4-1 |
| Overvoltage category |
III |
| pollution level |
3 |
| Rated impulse withstand voltage [Uimp] |
8 kV according to IEC 60947 |
| Safety and reliability level |
B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 |
| B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 |
| Mechanical life |
8 Mcycles |
| Electrical life |
0.8 Mcycles <= 440 V at 200 A AC-1 Ue |
| Control loop characteristics |
AC at 50/60 Hz |
| Surge Suppression Module |
Built-in bidirectional peak current limiting diode |
| Control voltage limit |
0.3…0.5 Uc -40…70 °C Release AC 50/60 Hz |
| 0.8…1.15 Uc -40…55 °C Run AC 50/60 Hz |
| 1…1.15 Uc 55…70 °C Run AC 50 /60Hz |
| (~50Hz pickup) power consumption (VA) |
280…350 VA 60 Hz 0.8 20 °C) |
| 280…350 VA 50 Hz 0.8 20 °C) |
| (~50Hz hold) power consumption (VA) |
2…18 VA 60 Hz 0.3 20 °C) |
| 2…18 VA 50 Hz 0.3 20 °C) |
| heat dissipation |
3…8 W at 50/60 Hz |
| action time |
6…20 ms open |
| 20…50 ms close |
| operating frequency |
2400 cycles/h at <60 °C |
| Wiring capacity |
Control circuit: Bolt fastening2 1…2.5 mm² Cable selection: Flexible wire with wire terminal |
| Control circuit: Bolt fastening1 1…2.5 mm² Cable selection: Flexible wire with wire terminal |
| Control circuit: Bolt fastening1 1 …2.5 mm² Cable option: flexible without wire terminals |
| Control circuit: screw tight2 1…2.5 mm² Cable option: flexible without cable terminals |
| Control circuit: screw tight1 1…2.5 mm² Cable option : Solid without wire terminals |
| Control circuit: Bolt fastening2 1…2.5 mm² Cable selection: Hard wire without wire terminals |
| Power circuit: Terminal 1 10…120 mm² Cable selection: Flexible wire without wire Terminals |
| Power circuit: Terminal 2 10…50 mm² Cable option: Flexible cord without wire terminal |
| Power circuit: Terminal 1 10…120 mm² Cable option: Flexible cord with cable terminal |
| Power circuit: Terminal 2 10… 50 mm² Cable option: Flexible with wire terminals Power |
| circuit: Terminal 1 10…120 mm² Cable option: Solid without wire terminals |
| Power circuit: Terminal 2 10…50 mm² Cable option: Solid No With wire terminal |
| Tightening torque |
Control circuit: 1.2 Nm via screwdriver Ø 6 flat |
| Control circuit: 1.2 Nm via screwdriver No. 2 Phillips screw |
| power supply circuit: 12 Nm via terminal hex 4 mm |
| control circuit: 1.2 Nm via screwdriver With a screwdriver pozidriv No 2 |
| installation method |
DIN rail installation |
| base plate installation |
| environment |
| standard |
CSA C22.2 No 14 |
| EN 60947-4-1 |
| EN 60947-5-1 |
| IEC 60947-4-1 |
| IEC 60947-5-1 |
| UL 508 |
| certified product |
CCC |
| RINA |
| GOST |
| UL |
| CSA |
| LROS (Lloyds register of shipping) |
| BV |
| GL |
| DNV |
| UKCA |
| IP protection class |
IP20 front panel complies with screwed |
| Protective measures |
TH conforms to IEC 60068-2-30 |
| climate tolerance |
Complies with IACS E10 for exposure to hot flashes |
| Complies with IEC 60947-1 Annex Q category D for exposure to hot flashes |
| ambient air temperature |
-40…60 °C |
| 60…70 °C with derating |
| working altitude |
0…3000 m |
| Fire resistance and abnormal high temperature resistance |
850 °C conforming to IEC 60695-2-1 |
| flame retardant |
V1 complies with UL 94 |
| Shock and vibration resistance |
Shock resistance with contacts open (2 gn (5…300 Hz)) |
| shock resistance with contacts closed (4 gn (5…300 Hz)) shock resistance |
| with contacts closed (15 gn (11ms)) |
| Shock performance Contact opening (6 gn (11ms)) |
| high |
158 mm |
| width |
150 mm |
| depth |
132 mm |
| Product Weight |
2.86kg |
| packaging unit |
| Unit Type of Package 1 |
PCE |
| Number of Units in Package 1 |
1 |
| Package 1 Height |
19.500 cm |
| Package 1 Width |
21.000 cm |
| Package 1 Length |
21.000 cm |
| Package 1 Weight |
2.971kg |
| Unit Type of Package 2 |
P06 |
| Number of Units in Package 2 |
18 |
| Package 2 Height |
75.000 cm |
| Package 2 Width |
60.000 cm |
| Package 2 Length |
80.000 cm |
| Package 2 Weight |
66.478 kg |
| contract warranty |
| Warranty |
18 months |