| Control the output | Supply voltage | 11PIN type | 8PIN type | 
|---|---|---|---|
| Output by Dot: DPDT (Time-limited output) | AC110V (50/60Hz) | H3BA-N AC110V | – | 
| AC220V (50/60Hz) | H3BA-N AC220V | ||
| DC24V | H3BA-N DC24V | ||
| Output by Dot: Limited time SPDT with SPDT can be switched (Limited time ↔, instantaneous) | AC110V (50/60Hz) | – | H3BA-N8H AC110V | 
| AC220V (50/60Hz) | H3BA-N8H AC220V | ||
| DC24V | H3BA-N8H DC24V | 
| project | H3BA-N | H3BA-N8H | 
|---|---|---|
| Action mode | A: ON Delay B: Flashing OFF Start B2: Flashing ON Start C: Signal ON/OFF Delay D: Signal OFF Delay E: Interval G: Signal ON/OFF Delay J: Monostable output | A: ON Delay H: ON Delay with Instantaneous Output Contact | 
| Pin type | 11pin | 8pin | 
| Input method | No voltage input | — | 
| Output mode | DPDT (Limited Time) | SPDT (time-limited) vs. switchable SPDT (time-limited<—>instant) | 
| Installation: | Aluminum rail mounting, surface mounting, and flush mounting | |
| Applicable Standards | UL508, CSA C22.2 No.14, LR and CCC : GB/T 14048.5* according to EN 61812-1 (Pollution 2 / Overvoltage Category III) | |
| EMC | (EMI) EN 61812-1 Radiological hazard intensity: EN 55011 class A AC power supply immunity: EN 55011 class A (EMS) EN 61812-1 8kV Air Discharge 1V/m (2GHz~2.7GHz AM modulation) 10V/m (900MHz pulse modulation) Conducted Noise Immunity: EN 61000-4-6: 10V (0.15MHz~80MHz) Radio Pulse Immunity: EN 61000-4-4: 2kV power cord 2kV I/O Signal Line 1kV Different Modes | |
*About CCC acquisition conditions
| Proposed fuses | 0216005 (250VAC, 5A) manufactured by Littelfuse | 
|---|---|
| Rated operating voltage Ue Rated operating voltage Ie | AC-15: Ue: 250VAC, Ie: 3A AC-13: Ue: 250VAC, Ie: 5A DC-13: Ue: 30VDC, Ie: 0.1A | 
| Rated insulation voltage | 250V | 
| Rated impulse voltage (Height: 2000m or less) | 4kV (at AC240V) | 
| Conditional short-circuit current | 1,000A | 
| Units of time | s (seconds) | x 10s (10 seconds) | min (min) | x 10min (ten minutes) | h (hours) | x 10h (10 hours) | |
|---|---|---|---|---|---|---|---|
| Full scale setting | |||||||
| 1.2 | Set the time | 0.05~1.2 | 1.2~12 | 0.12~1.2 | 1.2~12 | 0.12~1.2 | 1.2~12 | 
| 3 | 0.3~3 | 3~30 | 0.3~3 | 3~30 | 0.3~3 | 3~30 | |
| 12 | 1.2~12 | 12~120 | 1.2~12 | 12~120 | 1.2~12 | 12~120 | |
| 30 | 3~30 | 30~300 | 3~30 | 30~300 | 3~30 | 30~300 | |
| project | H3BA-N | H3BA-N8H | 
|---|---|---|
| Rated supply voltage (Please refer to Notes 1 and 2) | AC110V (50/60Hz)、AC220V (50/60Hz)、DC24V | |
| Voltage range of use (See Note 3) | 85%~110% of rated power supply voltage | |
| Power restoration | Minimum power on time: 0.1s | |
| No voltage input | Impedance at ON: 1 kΩ or less Residual voltage at ON: 1 V or less Impedance at OFF: 200 kΩ or more | |
| Power consumption | AC110V: Approx. 4.6VA (1.5W) AC220V: Approx. 7.6VA (1.3W) DC24V: Approx. 0.6W | AC110V: Approx. 3.6VA (1.6W) AC220V: Approx. 7.8VA (1.9W) DC24V: Approx. 0.9W | 
| Control the output | Contact: 5A at 250V AC, resistive load (cosφ = 1) | |
Note 1. The DC ripple rate is less than 20%.
Note 2. Using models other than the DC24V H3BA-N type will generate a surge current.
When powering on these models through a contactless output such as a sensor, be aware of the surge current.
Note 3. If the timer is used continuously at high ambient temperatures, the DC standard ripple rate is 90% or higher.
| project | H3BA-N | H3BA-N8H | 
|---|---|---|
| Accuracy of action time | ± 0.3% FS or less (±0.3% ±10ms in 1.2s range) | |
| Setting error | ±5% FS ±0.05s or less | |
| Return time | Minimum power on time: 0.1s or less Minimum pulse input time: 50ms | |
| Voltage effects | ± 0.5% FS or less (±0.5% ±10ms in 1.2s range) | |
| Temperature effects | ±2% FS or less (±2% ±10ms in the 1.2s range) | |
| Insulation resistance | 100MΩ min. (at 500 VDC) | |
| Withstand voltage | AC2,000V, 50/60Hz 1min (between conductive metal and exposed non-conductive metal) AC2,000V, 50/60Hz 1min (between control output terminal and operation circuit) AC1,000V, 50/60Hz 1min (between non-continuous contacts) (AC750V for H3BA-N8H type) | |
| Impulse voltage | 1kV (between power terminals) 2kV (between conductive terminals and exposed non-conductive metal parts, 1.5kV for DC24V type) | |
| Noise resistant | Type AC: ± 1.5kV (between power terminals) and 600V (between input terminals) ± Square wave noise generated by noise simulator (pulse width: 100ns/1μs, 1ns rise) ± 480V (between power terminals), ± 600V (between input terminals). Square wave noise generated by the noise simulator (pulse width: 100ns/1μs, 1ns ramp) | |
| Resistant to static electricity | Malfunction: 4kV Durability: 8kV | |
| Vibration resistant | Durability: 10~55Hz, 0.75mm single amplitude, 3 directions, 1 time each Malfunction: 10~55Hz, 0.5mm single amplitude, 3 directions, 1 time each | |
| Impact-resistant | Durability: 1,000 m/s2 (approx. 100 G), 3 directions, 1 time each Malfunction: 100 m/s2 (approx. 10 G), 3 directions, 1 time each | |
| Ambient temperature | Operation: -10°C~55°C (no icing) Storage: -25°C~65°C (no freezing) | |
| Ambient humidity | Operation: 35%~85% | |
| Service life | Mechanical: 10,000,000 cycles or more (1,800 cycles/hour at no load) Electrical: 100,000 cycles or more (AC250V 5A Resistive Load, 1800 times/hour) | Mechanical: 10,000,000 cycles or more (1,800 cycles/hour at no load) Electrical: 100,000 cycles or more (AC250V 5A Resistive Load, 360 times/hour) | 
| Housing color | Light grey (Munsell 5Y7/1) | |
| Ingress protection | IEC: IP40 (panel surface) | |
| weight | Approximately 95g | |
Note. To set the timer limit to a loop of less than 3 seconds or to use forced reset, use the H3BA-N type D mode (signal OFF delay).
| Model | H3BA-N AC110V, H3BA-N AC220V, H3BA-N DC24V, H3BA-N8H AC110V, H3BA-N8H AC220V, H3BA-N8H DC24V | 
|---|