General information | |
based on | 6ES7422-1BL00-0AA0 |
Supply voltage | |
Load voltage L+ | |
● Rated value (DC) | 24 V |
● permissible range, lower limit (DC) | 20.4 V |
● permissible range, upper limit (DC) | 28.8 V |
Input current | |
from load voltage L+ (without load), max. | 30 mA |
from backplane bus 5 V DC, max. | 200 mA |
Power loss | |
Power loss, typ. | 4 W |
Digital outputs | |
Number of digital outputs | 32 |
Short-circuit protection | Yes; Clocked electronically |
● Response threshold, typ. | 0.7 to 1.5 A |
Limitation of inductive shutdown voltage to | -27 V |
Controlling a digital input | Yes; possible |
Switching capacity of the outputs | |
● on lamp load, max. | 5 W |
Load resistance range | |
● lower limit | 48 Ω |
● upper limit | 4 Ω |
Output voltage | |
● for signal “1”, min. | L+ (-0.3 V) |
Output current | |
● for signal “1” rated value | 0.5 A |
● for signal “1” permissible range, min. | 5 mA |
● for signal “1” permissible range, max. | 0.6 A |
● for signal “0” residual current, max. | 0.3 mA |
Output delay with resistive load | |
● “0” to “1”, max. | 1 ms |
● “1” to “0”, max. | 1 ms |
Parallel switching of two outputs | |
● for uprating | Yes; possible (only outputs of the same group) |
● for redundant control of a load | Yes; possible (only outputs of the same group) |
Switching frequency | |
● with resistive load, max. | 100 Hz |
● with inductive load, max. | 0.5 Hz |
● with inductive load (acc. to IEC 60947-5-1, DC13), max. | 2 Hz; 2 Hz at 0.3 A; 0.5 Hz at 0.5 A |
● on lamp load, max. | 10 Hz |
Total current of the outputs (per group) | |
all mounting positions | |
– up to 40 °C, max. | 4:00 AM |
– up to 60 °C, max. | 2 A; 8 adjacent outputs each |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Interrupts/diagnostics/status information | |
Diagnostics function | No |
Potential separation | |
Potential separation digital outputs | |
● between the channels | No |
● between the channels, in groups of | 32 |
● between the channels and backplane bus | Yes |
Isolation | |
Isolation tested with | 500 V DC |
Ambient conditions | |
Ambient temperature during operation | |
● min. | -25 °C; = Tmin |
● max. | 60 °C; = Tmax |
Ambient temperature during storage/transportation | |
● min. | -40 °C |
● max. | 70 °C |
Altitude during operation relating to sea level | |
● Installation altitude above sea level, max. | 5 000 m |
● Ambient air temperature-barometric pressure-altitude | Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) // Tmin … (Tmax – 10 K) at 795 hPa … 658 hPa (+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa (+3 500 m … +5 000 m) |
Relative humidity | |
● With condensation, tested in accordance with IEC 60068- 2-38, max. |
100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
Use in stationary industrial systems | |
– to biologically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
– to chemically active substances according to EN 60721-3-3 |
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
– to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea | |
– to biologically active substances according to EN 60721-3-6 |
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
– to chemically active substances according to EN 60721-3-6 |
Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
– to mechanically active substances according to EN 60721-3-6 |
Yes; Class 6S3 incl. sand, dust; * |
Usage in industrial process technology | |
– Against chemically active substances acc. to EN 60654-4 |
Yes; Class 3 (excluding trichlorethylene) |
– Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 |
Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
Remark | |
– Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 |
* The supplied plug covers must remain in place over the unused interfaces during operation! |
Conformal coating | |
● Coatings for printed circuit board assemblies acc. to EN 61086 |
Yes; Class 2 for high reliability |
● Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
● Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC- CC-830A |
Yes; Conformal coating, Class A |
Dimensions | |
Width | 25 mm |
Height | 290 mm |
Depth | 210 mm |
Weights | |
Weight, approx. | 600 g |
Weight | 0.784 kg |
---|---|
Dimensions | 23 × 30 × 3.5 cm |