SICK sensor one of the world’s leading producers of sensors and sensor solutions for industrial applications. SICK is a technology and market leader in Factory and Logistics Automation as well as Process Automation. The sensor range are: Laser Sensors, Cylinder Sensors, Photoelectric Sensors, Fork Sensors, Encoders, Color Sensors, Distance Sensor, Contrast Sensor, Color Sensor, Inductive Proximity Sensors, Fiber Optic Sensor with our signature range sick sensor intelligence.

Part Number: 6028411
Capacitive Proximity Sensor Model: CM30-16BAP-KW1
OEM Spec Ref 

Features

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Housing Cylindrical thread design
Thread size M30 x 1.5
Diameter Ø 30 mm
Sensing range Sn 2 mm … 16 mm
Safe sensing range Sa 11.52 mm
Installation type Flush
Switching frequency 10 Hz
Connection type Cable, 2-wire, 2 m 1)
Output function NC or NO
Electrical wiring AC 2-wire
Adjustment Potentiometer (Sensitivity)
Enclosure rating IP67 2)

[/fusion_table]

  • 1) Do not bend below 0 °C.
  • 2) According to EN 60529.

 

Mechanics/electronics

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Supply voltage 20 V AC … 250 V AC
Ripple ≤ 10 % 1)
Voltage drop ≤ 10 V DC 2)
Current consumption 10 mA 3)
Time delay before availability ≤ 100 ms
Hysteresis 4 % … 20 %
Reproducibility ≤ 5 % 4) 5)
Temperature drift (of Sr) ± 10 %
EMC According to EN 60947-5-2 6)
Continuous current Ia ≤ 500 mA
Cable material PVC
Conductor size 0.5 mm²
Reverse polarity protection
Power-up pulse protection
Shock and vibration resistance 30 g, 11 ms / 10 … 55 Hz, 1 mm
Ambient operating temperature –25 °C … +80 °C
Housing material Plastic, PBT
Housing length 63.6 mm
Thread length 50 mm
Tightening torque, max. ≤ 7.5 Nm
Items supplied Mounting nut, PA12 plastic (2x)

Screwdriver for potentiometer adjustment (1 x)

[/fusion_table]

  • 1) Of Ub.
  • 2) At Ia max.
  • 3) Without load.
  • 4) Of Sr.
  • 5) Ub and Ta constant.
  • 6) In EMC critical applications, conducted interference levels may lie within the frequency range of the oscillator. This can cause changes to the output signal. (See operating instructions.).

 

Safety-related parameters

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

MTTFD 815 years
DCavg 0 %
TM (mission time) 20 years

[/fusion_table]

Reduction factors

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Note The values are reference values which may vary
Metal 1
Water 1
PVC Approx. 0.4
Oil Approx. 0.25
Glass 0.6
Ceramics 0.5
Alcohol 0.7
Wood 0.2 … 0.7

[/fusion_table]