Manufacturer Part Number: Festo 8086601
Festo Remote I/O and Network Interface Components: CPX-AP-I-4DI4DO-M8-3P
The Festo CPX-AP-I-4DI4DO-M8-3P, with MPN 8086601, is an innovative remote I/O and network interface component module designed to enhance the functionality and integration of automation systems. This module is engineered to provide both input and output capabilities, making it a versatile component for various industrial applications.
Key Features:
Benefits:
Applications:
The Festo CPX-AP-I-4DI4DO-M8-3P remote I/O and network interface component stands as a testament to Festo’s commitment to advancing industrial automation technology, offering a compact, efficient, and reliable solution for managing network interfaces and optimizing the performance of complex systems.
| Feature | Specification | 
|---|---|
| Dimensions W x L x H | 30 mm x 170 mm x 35 mm | 
| Type of mounting | On H-rail with accessories With through-hole | 
| Product weight | 129 g | 
| Ambient temperature | -20 °C … 50 °C | 
| Storage temperature | -40 °C … 70 °C | 
| Relative air humidity | 5 – 95 % Non-condensing | 
| Degree of protection | IP65 IP67 | 
| Note on degree of protection | Unused connections sealed | 
| Corrosion resistance class (CRC) | 1 – Low corrosion stress | 
| Max. cable length | 30 m outputs 30 m inputs 50 m system communication | 
| Information on max. cable length | Power supply according to nominal voltage | 
| LABS (PWIS) conformity | VDMA24364-B2-L | 
| CE marking (see declaration of conformity) | As per EU EMC directive | 
| UKCA marking (see declaration of conformity) | To UK instructions for EMC | 
| KC characters | KC EMC | 
| Certification | RCM compliance mark c UL us – Listed (OL) | 
| Certificate issuing authority | UL E239998 | 
| Note on materials | RoHS-compliant | 
| Housing material | PA PC Die-cast zinc, nickel-plated | 
| O-ring material | FPM | 
| Diagnostics via LED | Diagnostics per module Load power supply Status per channel | 
| Diagnose per internal communication | Load switch-off Short-circuit/overload in output signal Short circuit/overload in sensor supply Electronics/sensors overvoltage Load overvoltage Electronics/sensors undervoltage Load undervoltage | 
| No. of outputs | 4 | 
| Communication interface, function | System communication XF10 IN / XF20 OUT | 
| Communication interface, connection type | 2x socket | 
| Communication interface, connection technology | M8x1, D-coded as per EN 61076-2-114 | 
| Communication interface, number of pins/wires | 4 | 
| Communication interface, protocol | AP | 
| Communication interface, shielding | yes | 
| Power supply, function | Incoming electronics/sensors and load | 
| Power supply, type of connection | Plug | 
| Power supply, connection technology | M8x1, A-coded as per EN 61076-2-104 | 
| Power supply, number of pins/wires | 4 | 
| Voltage forwarding, function | Outgoing electronics/sensors and load | 
| Voltage forwarding, connection type | Socket | 
| Voltage forwarding, connection technology | M8x1, A-coded as per EN 61076-2-104 | 
| Voltage forwarding, number of pins/wires | 4 | 
| Note regarding operating voltage | SELV/PELV fixed power supplies required Note voltage drop | 
| Note voltage drop | Nominal operating voltage DC load | 
| Nominal operating voltage DC load | 24 V | 
| Permissible voltage fluctuations load | ± 25 % | 
| Nominal operating voltage DC for electronics/sensors | 24 V | 
| Permissible voltage fluctuations for electronics/sensors | ± 25 % | 
| Max. power supply | 2 x 4 A (external fuse required) | 
| Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 35 mA | 
| Intrinsic current consumption at nominal operating voltage load | Typically 10 mA | 
| Power failure buffering | 10 ms | 
| Reverse polarity protection | yes | 
| Electrical connection input, function | Digital input | 
| Electrical connection input, connection type | 4x socket | 
| Electrical input connection, connection technology | M8x1, A-coded as per EN 61076-2-104 | 
| Electrical connection, input, number of pins/wires | 3 | 
| No. of inputs | 4 | 
| Input characteristics | As per IEC 61131-2, type 3 | 
| Switching level | Signal 0: <= 5 V Signal 1: >= 11 V | 
| Input switching logic | PNP (positive switching) 2-wire sensors as per IEC 61131-2 3-wire sensors as per IEC 61131-2 | 
| Input debounce time | 0.1 ms 3 ms 10 ms 20 ms | 
| Fuse protection inputs (short circuit) | Internal electronic fuse per module | 
| Max. residual current of inputs per module | 1.8 A | 
| Electrical isolation of inputs between channels | no | 
| Digital inputs, electrical isolation of input – internal communication | yes | 
| Electrical connection output, function | Digital output | 
| Electrical connection output, connection type | 4x socket | 
| Electrical connection output, connection technology | M8x1, A-coded as per EN 61076-2-104 | 
| Electrical output connection, number of pins/wires | 3 | 
| Characteristic curve outputs | As per IEC 61131-2, type 0.5 | 
| Switching logic at outputs | PNP (positive switching) | 
| Fuse protection outputs (short circuit) | Internal electronic fuse per channel | 
| Output delay with resistive load | Signal change 0->1: < 200 µs Signal change 1->0: < 200 µs | 
| Max. residual current of outputs per module | 2 A | 
| Electrical isolation of outputs between channels | no | 
| Electrical isolation of outputs between channel – internal communication | yes | 
| Max. power supply per channel | 0.5 A | 
| Weight | 0.129 kg | 
|---|---|
| Dimensions | 3 × 17 × 3.5 cm |