Manufacturer Part Number: Festo 567347
Festo Remote I/O and Network Interface Components: CPX-CEC-C1
The Festo CPX-CEC-C1, with MPN 567347, is a state-of-the-art remote I/O and network interface component meticulously designed to enhance the functionality and integration of pneumatic systems within industrial automation environments.
Key Features:
Benefits:
Applications:
The Festo CPX-CEC-C1 remote I/O and network interface component stands as a testament to Festo’s innovation in pneumatic and automation technology, offering a sophisticated solution for managing network communication and optimizing the performance of industrial processes.
| Feature | Specification | 
|---|---|
| Protocol | CODESYS level 2 EasyIP Modbus® TCP TCP/IP | 
| Dimensions W x L x H | 50 mm x 107 mm x 55 mm | 
| Product weight | 155 g | 
| Ambient temperature | -5 °C … 50 °C | 
| Storage temperature | -20 °C … 70 °C | 
| Relative air humidity | 95 % Non-condensing | 
| Degree of protection | IP65 IP67 | 
| Corrosion resistance class (CRC) | 2 – Moderate corrosion stress | 
| LABS (PWIS) conformity | VDMA24364-B2-L | 
| Note on materials | RoHS-compliant | 
| Housing material | PA-reinforced PC | 
| LED display (product-specific) | ERR: PLC runtime error M: modify/forcing active PL: load supply PS: electronics supply, sensor supply RUN: PLC status SF: system fault STOP: PLC status | 
| LED display (bus-specific) | TP: link/traffic | 
| Device-specific diagnostics | Channel-oriented and module-oriented diagnostics, Undervoltage/short circuit of modules, Diagnostic memory | 
| Control elements | DIL switch for CAN termination Rotary switch for RUN/Stop | 
| IP address setting | DHCP Via CODESYS Via MMI | 
| Fieldbus interface, type | CAN bus | 
| Fieldbus interface, connection technology | Plug Sub-D 9-pin | 
| Fieldbus interface, galvanic isolation | yes | 
| Fieldbus interface, transmission rate | 125, 250, 500, 800, 1000 kbit/s Adjustable via software | 
| Ethernet interface | RJ 45 (socket, 8-pin) | 
| Ethernet, number | 1 | 
| Ethernet, supported protocols | TCP/IP, EasyIP, Modbus® TCP | 
| Ethernet, connector plug | RJ45 Socket 8-pin | 
| Ethernet, data transmission speed | 10/100 Mbit/s | 
| Parameterization | CODESYS V2.3 | 
| Baud rate | 10/100 bit/s as per IEEE 802.3 (10BaseT) or 802.3u (100BaseTx) | 
| Configuration support | CODESYS V2.3 | 
| Additional functions | Diagnostic functions Motion functions for electric actuators | 
| CPU data | 32 MB flash 32 MB RAM 400 MHz processor | 
| Control interface | CAN bus | 
| Nominal operating voltage DC | 24 V | 
| Nominal operating voltage DC load voltage | Without pneumatics: 18 … 30V 24 V With midi/maxi pneumatic valves types: 21.6 … 26.4 V With pneumatic type CPA: 20.4 … 26.4 V With pneumatics type MPA: 18 … 30 V | 
| Intrinsic current consumption at nominal operating voltage | Typ. 85 mA | 
| Power failure buffering | 10 ms | 
| Programming, operating language | DE, EN | 
| Programming language | as per IEC 61131-3 KOP AWL ST FUP AS Additionally CFC | 
| Programming, file handling support | yes | 
| Programming software | CODESYS provided by Festo V2.3 | 
| Program memory | 4 MB user program | 
| Processing time | Approx. 200 µs/1 k instruction | 
| Function blocks | Read CPX module diagnostics CPX diagnostic status Copy CPX diagnostic trace and others | 
| Flag | 30 kB remanent data 8 MB global data memory CODESYS variable concept | 
| Total number of axes | 31 | 
| Weight | 0.155 kg | 
|---|