Manufacturer Part Number: Festo 2597424
Festo Remote I/O and Network Interface Components: CPX-F8DE-P
The Festo CPX-F8DE-P, with MPN 2597424 remote I/O and network interface component, is an advanced remote I/O module specifically engineered to optimize the efficiency and reliability of automated systems through enhanced digital signal processing and network integration. This component is ideally suited for a wide range of industrial applications, offering both flexibility and performance in a compact design.
Key Features:
Benefits:
Applications:
The Festo CPX-F8DE-P remote I/O and network interface component stands out as a hallmark of Festo’s dedication to advancing industrial automation technology, providing a sophisticated and reliable solution for managing digital inputs and optimizing the performance of complex automation systems.
| Feature | Specification | 
|---|---|
| Dimensions W x L x H | (incl. interlinking block and connection system) 50 mm x 107 mm x 55 mm | 
| Product weight | 46 g | 
| Ambient temperature | -5 °C … 50 °C | 
| Storage temperature | -20 °C … 70 °C | 
| Degree of protection | Depends on manifold block | 
| Corrosion resistance class (CRC) | 1 – Low corrosion stress (when installed) | 
| Max. cable length | 200 m | 
| LABS (PWIS) conformity | VDMA24364-B2-L | 
| CE marking (see declaration of conformity) | As per EU EMC directive as per EU machinery directive As per EU RoHS directive | 
| UKCA marking (see declaration of conformity) | To UK instructions for EMC To UK instructions for machines To UK RoHS instructions | 
| Certification | c UL us – Recognized (OL) | 
| Certificate issuing authority | 01/205/5444.01/21 German Technical Control Board (TÜV) Rh. UK 01/205U/5444.00/22 | 
| Note on materials | RoHS-compliant | 
| PFH | 1.0E-9 | 
| LED indicators | 1 fail-safe mode protocol active 1 group diagnostics 8 channel diagnostics 8 channel status | 
| Diagnostics | Wire break per channel Communication Short circuit per channel Process value error Cross circuit per channel Self-test Overvoltage Over temperature Undervoltage | 
| Control elements | DIL switch | 
| Max. address capacity inputs | 6 byte | 
| Max. address capacity outputs | 7 byte | 
| DC operating voltage range | 20.4 V … 28.8 V | 
| Nominal operating voltage DC | 24 V | 
| Residual ripple | 2 Vss within voltage range | 
| Intrinsic current consumption at nominal operating voltage | Typ. 35 mA (electronics operating voltage supply) | 
| No. of inputs | 8 | 
| Input characteristics | As per IEC 61131-2, type 2 | 
| Input switching logic | PNP (positive switching) | 
| Safety function | Reliable input status detection and evaluation | 
| Safety integrity level (SIL) | Safe recording and analysis of input states as per EN 62061 up to SIL CL3 Reliable recording and analysis of input states as per EN61508 to SIL3 | 
| Performance Level (PL) | Reliable detection and evaluation of input statuses as per ISO 13849 up to category 4 and performance level e | 
| Max. residual current per module | 3 A | 
| Electrical isolation between channels | no | 
| Weight | 0.046 kg | 
|---|