| Main information | ||||
| Part Number | GV2ME05C | GV2ME07C | GV2ME08C | GV2ME10C | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | TeSys Deca | 
| product name | TeSys GV2 | TeSys GV2 | TeSys GV2 | TeSys GV2 | 
| product short name | GV2ME | GV2ME | GV2ME | GV2ME | 
| product type | Breaker | Breaker | Breaker | Breaker | 
| Applications | Motor protection | Motor protection | Motor protection | Motor protection | 
| number of poles | 3P | 3P | 3P | 3P | 
| Additional information | ||||
| Grid type | AC | AC | AC | AC | 
| Network frequency | 50/60 Hz conforming to IEC 60947-2 | 50/60 Hz conforming to IEC 60947-2 | 50/60 Hz conforming to IEC 60947-2 | 50/60 Hz conforming to IEC 60947-2 | 
| control type | (Push) button | (Push) button | (Push) button | (Push) button | 
| installation method | Rail installation | Rail installation | Rail installation | Rail installation | 
| installation location | horizontal vertical | horizontal vertical | Vertical | horizontal vertical | 
| horizontal direction | ||||
| Motor power (kW) | 0.00…0.37 kW at 230 V AC 50/60 Hz | 0.37 kW at 230 V AC 50/60 Hz | 0.75 kW at 230 V AC 50/60 Hz | 1.1 kW at 230 V AC 50/60 Hz | 
| 0.00…0.37 kW at 400 V AC 50/60 Hz | 0.75 kW at 400 V | 1.5 kW at 400 V | 2.2 kW at 400 V | |
| 0.00…0.37 kW at 415 V AC 50/60 Hz | 0.75 kW at 415 V | 1.5 kW at 415 V | 2.2 kW at 415 V | |
| 0.37 kW at 440 V AC 50/60Hz | 1.1 kW at 440 V AC 50/60 Hz | 1.5 kW at 440 V AC 50/60 Hz | 3 kW at 440 V AC 50/60 Hz | |
| Rated current [In] | 1A | 2.5A | 4A | 6.3A | 
| Trip unit type | Thermomagnetic | Thermomagnetic | Thermomagnetic | Thermomagnetic | 
| Electromagnetic trip current | 13A | 33.5A | 51A | 78A | 
| Thermal overload protection setting range | 0.63…1A | 1.6…2.5 A | 2.5…4A | 4…6.3A | 
| isolation function | Applies to IEC 60947-1 § 7-1-6 | Applies to IEC 60947-1 § 7-1-6 | Applies to IEC 60947-1 § 7-1-6 | Applies to IEC 60947-1 § 7-1-6 | 
| Mechanical shock resistance | 0.5 J IK04 | 0.5 J IK04 | 0.5 J IK04 | 0.5 J IK04 | 
| phase loss sensitivity | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | 
| use category | Type AC conforms to IEC 60947-2 | Type AC conforms to IEC 60947-2 | Type AC conforms to IEC 60947-2 | Type AC conforms to IEC 60947-2 | 
| AC-3 conforms to IEC 60947-4-1 | AC-3 conforms to IEC 60947-4-1 | AC-3 conforms to IEC 60947-4-1 | AC-3 conforms to IEC 60947-4-1 | |
| Rated working voltage [Ue] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Rated insulation voltage [Ui] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 600 V AC 50/60 Hz conforming to UL 508 | 600 V AC 50/60 Hz conforming to UL 508 | 600 V AC 50/60 Hz conforming to UL 508 | 600 V AC 50/60 Hz conforming to UL 508 | |
| 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | |
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 947-2 | 6 kV according to IEC 947-2 | 6 kV according to IEC 947-2 | 6 kV according to IEC 947-2 | 
| power consumption per pole | 2.5W | 2.5W | 2.5W | 2.5W | 
| Mechanical life | 100000 times | 100000 times | 100000 times | 100000 times | 
| Electrical life | 100000 cycles for AC-3 at 440 V In | 100000 cycles for AC-3 at 440 V In | 100000 cycles for AC-3 at 440 V In | 100000 cycles for AC-3 at 440 V In | 
| 100000 cycles for AC-3 at 440 V In/2 | 100000 cycles for AC-3 at 440 V In/2 | 100000 cycles for AC-3 at 440 V In/2 | 100000 cycles for AC-3 at 440 V In/2 | |
| maximum conversions | 25 cyc/h | 25 cyc/h | 25 cyc/h | 25 cyc/h | 
| specified load | Continuous according to IEC 60947-4-1 | Continuous according to IEC 60947-4-1 | Continuous according to IEC 60947-4-1 | Continuous according to IEC 60947-4-1 | 
| Wiring capacity | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | 
| Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | |
| Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with cable terminals | Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals | Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with cable terminals | Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with cable terminals | |
| Tightening torque | 1.7 Nm via screw-in terminal cable 1…4 mm² | 1.7 Nm via screw-in terminal cable 1…4 mm² | 1.7 Nm via screw-in terminal cable 1…4 mm² | 1.7 Nm via screw-in terminal cable 1…4 mm² | 
| 1.7 Nm via screw-in terminal cable 1…6 mm² | 1.7 Nm via screw-in terminal cable 1…6 mm² | 1.7 Nm via screw-in terminal cable 1…6 mm² | 1.7 Nm via screw-in terminal cable 1…6 mm² | |
| 1.7 Nm via screw-in terminal cable 1.5…6 mm² | 1.7 Nm via screw-in terminal cable 1.5…6 mm² | 1.7 Nm via screw-in terminal cable 1.5…6 mm² | 1.7 Nm via screw-in terminal cable 1.5…6 mm² | |
| Breaking capacity | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: >= 100 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: >= 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: >= 100 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 3 kA at 690 V AC 50/ 60 Hz conforming to IEC 60947-2 | Icu: 3 kA at 690 V AC 50/ 60 Hz conforming to IEC 60947-2 | Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Rated operating short-circuit breaking capacity [Ics] | 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | ||||
| 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 2 | ||||
| high | 89mm | 89mm | 89 mm | 89mm | 
| width | 44.5 mm | 44.5 mm | 44.5 mm | 44.5 mm | 
| depth | 78.2 mm | 78.2 mm | 78.2 mm | 78.2 mm | 
| product weight | 0.26kg | 0.26kg | 0.26kg | 0.26kg | 
| Environment | ||||
| Standards compliant | GB 14048.4 | GB 14048.4 | GB 14048.4 | GB 14048.4 | 
| IEC 60947-1 | IEC 60947-1 | IEC 60947-1 | IEC 60947-1 | |
| IEC 60947-2 | IEC 60947-2 | IEC 60947-2 | IEC 60947-2 | |
| IEC 60947-4-1 | IEC 60947-4-1 | IEC 60947-4-1 | IEC 60947-4-1 | |
| certified product | CCC | CCC | CCC | CCC | 
| CE | UKCA | UKCA | UKCA | |
| UKCA | CE | CE | CE | |
| Protective measures | TH | TH | TH | TH | 
| IP protection class | IP20 complies with screwed (body) | IP20 complies with screwed (body) | IP20 complies with screwed (body) | IP20 complies with screwed (body) | 
| Shock and vibration resistance | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | 
| Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | |
| ambient temperature | -20…40 °C In cabinet | -20…40 °C In cabinet | -20…40 °C In cabinet | -20…40 °C In cabinet | 
| -20…60 °C Body | -20…60 °C Body | -20…60 °C Body | -20…60 °C Body | |
| storage environment temperature | -40…80°C | -40…80°C | -40…80°C | -40…80°C | 
| Fire resistance and abnormal high temperature resistance | 960 °C conforming to IEC 60695-2-1 | 960 °C conforming to IEC 60695-2-1 | 960 °C conforming to IEC 60695-2-1 | 960 °C conforming to IEC 60695-2-1 | 
| working altitude | <= 2000m | <= 2000m | <= 2000m | <= 2000m | 
| Packaging unit | ||||
| Unit Type of Package 1 | PCE | PCE | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 1 | 1 | 
| Package 1 Height | 4.716 cm | 4.869 cm | 4.799 cm | 4.94cm | 
| Package 1 Width | 8.214 cm | 8.195 cm | 8.242 cm | 8.13cm | 
| Package 1 Length | 9.056 cm | 9.019 cm | 9.08 cm | 9.02 cm | 
| Package 1 Weight | 229.0g | 258.0g | 258.0g | 271.875g | 
| Unit Type of Package 2 | S02 | S02 | S02 | S02 | 
| Number of Units in Package 2 | 32 | 32 | 32 | 32 | 
| Package 2 Height | 15.0cm | 15.0cm | 15.0cm | 15.0cm | 
| Package 2 Width | 30.0cm | 30.0cm | 30.0cm | 30.0cm | 
| Package 2 Length | 40.0cm | 40.0cm | 40.0cm | 40.0cm | 
| Package 2 Weight | 7.752kg | 8.608 kg | 8.648kg | 9.092kg | 
| Unit Type of Package 3 | P06 | P06 | P06 | P06 | 
| Number of Units in Package 3 | 640 | 640 | 640 | 640 | 
| Package 3 Height | 90.0cm | 90.0cm | 90.0cm | 90.0cm | 
| Package 3 Width | 60.0cm | 60.0cm | 60.0cm | 60.0cm | 
| Package 3 Length | 80.0cm | 80.0cm | 80.0cm | 80.0cm | 
| Package 3 Weight | 165.04kg | 182.16kg | 182.96kg | 191.84kg | 
| Contract warranty | ||||
| Warranty | 18 months | 18 months | 18 months | 18 months | 
| Main information | ||||
| Part Number | GV2ME14C | GV2ME16C | GV2ME20C | GV2ME22C | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | TeSys Deca | 
| product name | TeSys GV2 | TeSys GV2 | TeSys GV2 | TeSys GV2 | 
| product short name | GV2ME | GV2ME | GV2ME | GV2ME | 
| product type | Breaker | Breaker | Breaker | Breaker | 
| Applications | Motor protection | Motor protection | Motor protection | Motor protection | 
| number of poles | 3P | 3P | 3P | 3P | 
| Additional information | ||||
| Grid type | AC | AC | AC | AC | 
| Network frequency | 50/60 Hz conforming to IEC 60947-2 | 50/60 Hz conforming to IEC 60947-2 | 50/60 Hz conforming to IEC 60947-2 | 50/60 Hz conforming to IEC 60947-2 | 
| control type | (Push) button | (Push) button | (Push) button | (Push) button | 
| installation method | Rail installation | Rail installation | Rail installation | Rail installation | 
| installation location | horizontal vertical | horizontal vertical | Vertical | Vertical | 
| horizontal direction | horizontal direction | |||
| Motor power (kW) | 2.2 kW at 230 V AC 50/60 Hz | 3 kW at 230 V AC 50/60 Hz | 4 kW at 230 V AC 50/60 Hz | 5.5 kW at 230 V AC 50/60 Hz | 
| 4 kW at 400 V | 5.5 kW at 400 V | 7.5 kW at 400 V | 11 kW at 400 V | |
| 4 kW at 415 V | 5.5 kW at 415 V | 9 kW at 415 V | 11 kW at 415 V | |
| 4 kW at 440 V AC 50/60 Hz | 7.5 kW at 440 V AC 50/60 Hz | 9 kW at 440 V AC 50/60 Hz | 11 kW at 440 V AC 50/60 Hz | |
| Rated current [In] | 10A | 14A | 18A | 25A | 
| Trip unit type | Thermomagnetic | Thermomagnetic | Thermomagnetic | Thermomagnetic | 
| Electromagnetic trip current | 138A | 170A | 223A | 327A | 
| Thermal overload protection setting range | 6…10A | 9…14A | 13…18A | 20…25A | 
| isolation function | Applies to IEC 60947-1 § 7-1-6 | Applies to IEC 60947-1 § 7-1-6 | Applies to IEC 60947-1 § 7-1-6 | Applies to IEC 60947-1 § 7-1-6 | 
| Mechanical shock resistance | 0.5 J IK04 | 0.5 J IK04 | 0.5 J IK04 | 0.5 J IK04 | 
| phase loss sensitivity | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | 
| use category | Type AC conforms to IEC 60947-2 | Type AC conforms to IEC 60947-2 | Type AC conforms to IEC 60947-2 | Type AC conforms to IEC 60947-2 | 
| AC-3 conforms to IEC 60947-4-1 | AC-3 conforms to IEC 60947-4-1 | AC-3 conforms to IEC 60947-4-1 | AC-3 conforms to IEC 60947-4-1 | |
| Rated working voltage [Ue] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Rated insulation voltage [Ui] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 600 V AC 50/60 Hz conforming to UL 508 | 600 V AC 50/60 Hz conforming to UL 508 | 600 V AC 50/60 Hz conforming to UL 508 | 600 V AC 50/60 Hz conforming to UL 508 | |
| 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | |
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 947-2 | 6 kV according to IEC 947-2 | 6 kV according to IEC 947-2 | 6 kV according to IEC 947-2 | 
| power consumption per pole | 2.5W | 2.5W | 2.5W | 2.5W | 
| Mechanical life | 100000 times | 100000 times | 100000 times | 100000 times | 
| Electrical life | 100000 cycles for AC-3 at 440 V In | 100000 cycles for AC-3 at 440 V In | 100000 cycles for AC-3 at 440 V In | 100000 cycles for AC-3 at 440 V In | 
| 100000 cycles for AC-3 at 440 V In/2 | 100000 cycles for AC-3 at 440 V In/2 | 100000 cycles for AC-3 at 440 V In/2 | 100000 cycles for AC-3 at 440 V In/2 | |
| maximum conversions | 25 cyc/h | 25 cyc/h | 25 cyc/h | 25 cyc/h | 
| specified load | Continuous according to IEC 60947-4-1 | Continuous according to IEC 60947-4-1 | Continuous according to IEC 60947-4-1 | Continuous according to IEC 60947-4-1 | 
| Wiring capacity | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | 
| Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | |
| Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with cable terminals | Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals | Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with cable terminals | Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with cable terminals | |
| Tightening torque | 1.7 Nm via screw-in terminal cable 1…4 mm² | 1.7 Nm via screw-in terminal cable 1…4 mm² | 1.7 Nm via screw-in terminal cable 1…4 mm² | 1.7 Nm via screw-in terminal cable 1…4 mm² | 
| 1.7 Nm via screw-in terminal cable 1…6 mm² | 1.7 Nm via screw-in terminal cable 1…6 mm² | 1.7 Nm via screw-in terminal cable 1…6 mm² | 1.7 Nm via screw-in terminal cable 1…6 mm² | |
| 1.7 Nm via screw-in terminal cable 1.5…6 mm² | 1.7 Nm via screw-in terminal cable 1.5…6 mm² | 1.7 Nm via screw-in terminal cable 1.5…6 mm² | 1.7 Nm via screw-in terminal cable 1.5…6 mm² | |
| Breaking capacity | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 50 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 15 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 15 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 15 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 8 kA at… at 440 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 8 kA at… at 440 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 6 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 6 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 6 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 4 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947- 2 | Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947- 2 | Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Rated operating short-circuit breaking capacity [Ics] | 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 | 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 | 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 | 40 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 2 | 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | ||
| 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | ||||
| high | 89mm | 89mm | 89mm | 89 mm | 
| width | 44.5 mm | 44.5 mm | 44.5 mm | 44.5 mm | 
| depth | 78.2 mm | 78.2 mm | 78.2 mm | 78.2 mm | 
| product weight | 0.26kg | 0.26kg | 0.26kg | 0.26kg | 
| Environment | ||||
| Standards compliant | GB 14048.4 | GB 14048.4 | GB 14048.4 | GB 14048.4 | 
| IEC 60947-1 | IEC 60947-1 | IEC 60947-1 | IEC 60947-1 | |
| IEC 60947-2 | IEC 60947-2 | IEC 60947-2 | IEC 60947-2 | |
| IEC 60947-4-1 | IEC 60947-4-1 | IEC 60947-4-1 | IEC 60947-4-1 | |
| certified product | CCC | CCC | CCC | CCC | 
| UKCA | UKCA | UKCA | UKCA | |
| CE | CE | CE | CE | |
| Protective measures | TH | TH | TH | TH | 
| IP protection class | IP20 complies with screwed (body) | IP20 complies with screwed (body) | IP20 complies with screwed (body) | IP20 complies with screwed (body) | 
| Shock and vibration resistance | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | 
| Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | |
| ambient temperature | -20…40 °C In cabinet | -20…40 °C In cabinet | -20…40 °C In cabinet | -20…40 °C In cabinet | 
| -20…60 °C Body | -20…60 °C Body | -20…60 °C Body | -20…60 °C Body | |
| storage environment temperature | -40…80°C | -40…80°C | -40…80°C | -40…80°C | 
| Fire resistance and abnormal high temperature resistance | 960 °C conforming to IEC 60695-2-1 | 960 °C conforming to IEC 60695-2-1 | 960 °C conforming to IEC 60695-2-1 | 960 °C conforming to IEC 60695-2-1 | 
| working altitude | <= 2000m | <= 2000m | <= 2000m | <= 2000m | 
| Packaging unit | ||||
| Unit Type of Package 1 | PCE | PCE | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 1 | 1 | 
| Package 1 Height | 4.87cm | 5.3 cm | 4.78cm | 4.88cm | 
| Package 1 Width | 8.18cm | 9.0cm | 8.18cm | 8.09cm | 
| Package 1 Length | 9.0cm | 9.6cm | 9.03 cm | 9.02 cm | 
| Package 1 Weight | 272.01g | 278.28g | 284.625g | 284.843g | 
| Unit Type of Package 2 | S02 | S02 | S02 | S02 | 
| Number of Units in Package 2 | 32 | 32 | 32 | 32 | 
| Package 2 Height | 15.0cm | 15.0cm | 15.0cm | 15.0cm | 
| Package 2 Width | 30.0cm | 30.0cm | 30.0cm | 30.0cm | 
| Package 2 Length | 40.0cm | 40.0cm | 40.0cm | 40.0cm | 
| Package 2 Weight | 9.079kg | 9.297 kg | 9.5kg | 9.507 kg | 
| Unit Type of Package 3 | P06 | P06 | P06 | P06 | 
| Number of Units in Package 3 | 640 | 640 | 640 | 640 | 
| Package 3 Height | 90.0cm | 90.0cm | 90.0cm | 90.0cm | 
| Package 3 Width | 60.0cm | 60.0cm | 60.0cm | 60.0cm | 
| Package 3 Length | 80.0cm | 80.0cm | 80.0cm | 80.0cm | 
| Package 3 Weight | 191.58kg | 195.94kg | 200.0kg | 200.14kg | 
| Contract warranty | ||||
| Warranty | 18 months | 18 months | 18 months | 18 months | 
| Main information | |
| Part Number | GV2ME32C | 
| Product Series | TeSys Deca | 
| product name | TeSys GV2 | 
| product short name | GV2ME | 
| product type | Breaker | 
| Applications | Motor protection | 
| number of poles | 3P | 
| Additional information | |
| Grid type | AC | 
| Network frequency | 50/60 Hz conforming to IEC 60947-2 | 
| control type | (Push) button | 
| installation method | Rail installation | 
| installation location | horizontal vertical | 
| Motor power (kW) | 7.5 kW at 230 V AC 50/60 Hz | 
| 15 kW at 400 V | |
| 15 kW at 415 V | |
| 15 kW at 440 V AC 50/60 Hz | |
| Rated current [In] | 32A | 
| Trip unit type | Thermomagnetic | 
| Electromagnetic trip current | 416A | 
| Thermal overload protection setting range | 24…32A | 
| isolation function | Applies to IEC 60947-1 § 7-1-6 | 
| Mechanical shock resistance | 0.5 J IK04 | 
| phase loss sensitivity | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | 
| use category | Type AC conforms to IEC 60947-2 | 
| AC-3 conforms to IEC 60947-4-1 | |
| Rated working voltage [Ue] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Rated insulation voltage [Ui] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 600 V AC 50/60 Hz conforming to UL 508 | |
| 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | |
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 947-2 | 
| power consumption per pole | 2.5W | 
| Mechanical life | 100000 times | 
| Electrical life | 100000 cycles for AC-3 at 440 V In | 
| 100000 cycles for AC-3 at 440 V In/2 | |
| maximum conversions | 25 cyc/h | 
| specified load | Continuous according to IEC 60947-4-1 | 
| Wiring capacity | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | 
| Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | |
| Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals | |
| Tightening torque | 1.7 Nm via screw-in terminal cable 1…4 mm² | 
| 1.7 Nm via screw-in terminal cable 1…6 mm² | |
| 1.7 Nm via screw-in terminal cable 1.5…6 mm² | |
| Breaking capacity | Icu: 50 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Icu: 10 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: 6 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: 4 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Rated operating short-circuit breaking capacity [Ics] | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| high | 89mm | 
| width | 44.5 mm | 
| depth | 78.2 mm | 
| product weight | 0.26kg | 
| Environment | |
| Standards compliant | GB 14048.4 | 
| IEC 60947-1 | |
| IEC 60947-2 | |
| IEC 60947-4-1 | |
| certified product | CCC | 
| UKCA | |
| CE | |
| Protective measures | TH | 
| IP protection class | IP20 complies with screwed (body) | 
| Shock and vibration resistance | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | 
| Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | |
| ambient temperature | -20…40 °C In cabinet | 
| -20…60 °C Body | |
| storage environment temperature | -40…80°C | 
| Fire resistance and abnormal high temperature resistance | 960 °C conforming to IEC 60695-2-1 | 
| working altitude | <= 2000m | 
| Packaging unit | |
| Unit Type of Package 1 | PCE | 
| Number of Units in Package 1 | 1 | 
| Package 1 Height | 4.78cm | 
| Package 1 Width | 8.15cm | 
| Package 1 Length | 9.03 cm | 
| Package 1 Weight | 279.6g | 
| Unit Type of Package 2 | S02 | 
| Number of Units in Package 2 | 32 | 
| Package 2 Height | 15.0cm | 
| Package 2 Width | 30.0cm | 
| Package 2 Length | 40.0cm | 
| Package 2 Weight | 9.339 kg | 
| Unit Type of Package 3 | P06 | 
| Number of Units in Package 3 | 640 | 
| Package 3 Height | 90.0cm | 
| Package 3 Width | 60.0cm | 
| Package 3 Length | 80.0cm | 
| Package 3 Weight | 196.784kg | 
| Contract warranty | |
| Warranty | 18 months |