| Main | ||
| Part Number | RM22TR33 | RM22TU23 | 
| Product Series | Harmony Control Relays | Harmony Control Relays | 
| product type | 3-phase control relay | 3-phase control relay | 
| relay type | Control relay | Control relay | 
| Number of grid phases | Phase 3 | Phase 3 | 
| Relay name | RM22TR | RM22TR | 
| Relay Monitoring Parameters | Overvoltage and undervoltage monitoring Phase sequence Phase failure monitoring | Undervoltage Monitoring Phase Sequence Phase Failure Monitoring | 
| delay type | Adjustable 0.1…30 s, +/- 10 % full scale value over threshold Tt | N/A | 
| Switching capacity in VA | 2000VA | 2000VA | 
| Measuring range | 380…480 V voltage AC | 380…480 V voltage AC | 
| contact type | 2 OC | 2 OC | 
| Additional information | ||
| reset time | 1500 ms at maximum voltage | 1500 ms at maximum voltage | 
| Maximum Switching Voltage | 250V AC | 250V AC | 
| Minimum switching current [Imin] | 10 mA at 5 V DC | 10 mA at 5 V DC | 
| Maximum switching current | 8A AC | 8A AC | 
| Rated supply voltage [Us] | 380…480 V AC | 380…480 V AC | 
| Power supply voltage range | 304…576 V AC | 304…576 V AC | 
| operating limits | – 20 % + 20 % Un | – 20 % + 20 % Un | 
| Power consumption VA | 15 VA at 480 V AC 60 Hz | 15 VA at 480 V AC 60 Hz | 
| Voltage Monitoring Threshold | < 100 V AC | < 100 V AC | 
| supply voltage frequency | 50…60 Hz +/- 10 % | 50…60 Hz +/- 10 % | 
| output contact | 2 C/O | 2 C/O | 
| Rated output current | 8A | N/A | 
| set precision | +/- 10 % of full scale | +/- 10 % of full scale | 
| switching threshold error | <= 0.05 % per degree Celsius based on permissible ambient air temperature <= 1 % within supply voltage range | <= 0.05 % per degree Celsius based on permissible ambient air temperature <= 1 % within supply voltage range | 
| Latency Accuracy Settings | 10P | 10P | 
| delay error | <= 0.05 % per degree Celsius based on permissible ambient air temperature <= 1 % within supply voltage range | <= 0.05 % per degree Celsius based on permissible ambient air temperature <= 1 % within supply voltage range | 
| hysteresis | 2 % fixed optional | 2 % fixed optional | 
| Rising delay at power-up | 650ms | 650ms | 
| Maximum measuring cycle | 150 ms period measured in true rms value | 150 ms period measured in true rms value | 
| Threshold adjustment voltage | 2…20 % selected Un | 2…20 % selected Un | 
| voltage range | 380…480 VPP | 380…480 VPP | 
| Repeatability | +/- 0.5 % for input and measurement circuits +/- 3 % for time delay | +/- 0.5 % for input and measurement circuits | 
| Measurement error | < 1 % over the entire range with a voltage change < 0.05 %/°C with a temperature change | < 1 % over the entire range with a voltage change < 0.05 %/°C with a temperature change | 
| Response time | <= 300ms | <= 300ms | 
| Type of overvoltage | III according to IEC 60664-1 III according to UL 508 | III according to IEC 60664-1 III according to UL 508 | 
| Insulation resistance | > 100 MΩ at 500 V DC conforming to IEC 60255-27 | > 100 MΩ at 500 V DC conforming to IEC 60255-27 | 
| installation location | Any position | Any position | 
| Wiring capacity | Screw terminal, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) Solid without wire terminal Screw terminal, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16 ) flexible wire with wire terminal screw terminal, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) rigid wire without wire terminal screw terminal, 1 x 0.2…1 x 2.5 mm² ( AWG 24…AWG 14) flexible wire with wire terminal | Screw terminal, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) Solid without wire terminal Screw terminal, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16 ) flexible wire with wire terminal screw terminal, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) rigid wire without wire terminal screw terminal, 1 x 0.2…1 x 2.5 mm² ( AWG 24…AWG 14) flexible wire with wire terminal | 
| Tightening torque | 0.6…1 Nm conforming to IEC 60947-1 | 0.6…1 Nm conforming to IEC 60947-1 | 
| covering material | Flame retardant plastic | Flame retardant plastic | 
| LED status | LED (yellow) relay ON LED (green) energized | LED (yellow) relay ON LED (green) energized | 
| installation method | 35 mm DIN rail conforming to EN/IEC 60715 | 35 mm DIN rail conforming to EN/IEC 60715 | 
| Electrical life | 100000 times | 100000 times | 
| Mechanical life | 10000000 times | 10000000 times | 
| use category | AC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1 | AC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1 | 
| Safe and reliable data | MTTFd = 388.1 years B10d = 350000 | MTTFd = 388.1 years B10d = 350000 | 
| contact material | Cadmium free | Cadmium free | 
| width | 22.5 mm | 22.5 mm | 
| Product Weight | 0.09 kg | 0.09 kg | 
| environment | ||
| Anti-instantaneous power failure | 10ms | 10ms | 
| electromagnetic compatibility | Exemption for use in residential, commercial and light-industrial environments Transmission standards per EN/IEC 61000-6-1 Exemption for industrial environments per EN/IEC 61000-6-2 Transmission standards for residential, commercial and light-industrial environments per EN/IEC 61000- 6-3 Transmission standards for industrial environments in accordance with EN/IEC 61000-6-4 Anti-static interference – test level: 6 kV (contact discharge) Level 3 in accordance with IEC 61000-4-2 Anti-static interference – test level: 8 kV (air Discharge) Class 3 Complies with IEC 61000-4-2 Radio Frequency Electromagnetic Field Radiation Immunity Test – Test Level: 10 V/m3 Class Complies with IEC 61000-4-3 Immunity to Fast Transients – Test Level: 4 kV (Direct Connection) Class 4 Complies with IEC 61000-4-4 Immunity to fast transients – Test level: 2 kV (capacitive coupling) level 4 Complies with IEC 61000-4-4 Surge discharge immunity – Test level: 4 kV (Common mode) level 4 Conforms to IEC 61000 -4-5 Surge Discharge Immunity- Test Level: 2 kV (Differential Mode) Level 4 Conforms to IEC 61000-4-5 Conducted and Radiated Emissions Group B 1 Conforms to CISPR 11 Conducted and Radiated Emissions Class B Conforms to CISPR 22 | Exemption for use in residential, commercial and light-industrial environments Transmission standards per EN/IEC 61000-6-1 Exemption for industrial environments per EN/IEC 61000-6-2 Transmission standards for residential, commercial and light-industrial environments per EN/IEC 61000- 6-3 Transmission standards for industrial environments in accordance with EN/IEC 61000-6-4 Anti-static interference – test level: 6 kV (contact discharge) Level 3 in accordance with IEC 61000-4-2 Anti-static interference – test level: 8 kV (air Discharge) level 3 according to IEC 61000-4-2 radio frequency electromagnetic field radiation immunity test – test level: 10 V/m3 level according to IEC 61000-4-3 immunity to fast transients – test level: 4 kV (direct connection) level 4 Complies with IEC 61000-4-4 Immunity to Fast Transients – Test Level: 2 kV (Capacitive Coupling) Class 4 Complies with IEC 61000-4-4 Surge Discharge Immunity – Test Class: 4 kV (Common Mode) Class 4 Conforms to IEC 61000 -4-5 Surge Discharge Immunity- Test Level: 2 kV (Differential Mode) Level 4 Conforms to IEC 61000-4-5 Conducted and Radiated Emissions Group B 1 Conforms to CISPR 11 Conducted and Radiated Emissions Class B Conforms to CISPR 22 | 
| Standards compliant | EN/IEC 60255-1 | EN/IEC 60255-1 | 
| certified product | GL CSA RCM CE EAC CCC UL | CSA RCM UL GL CE CCC EAC | 
| storage environment temperature | -40…70°C | -40…70°C | 
| ambient temperature | -20…50 °C at 60 Hz -20…60 °C at 50 Hz AC/DC | -20…50 °C at 60 Hz -20…60 °C at 50 Hz AC/DC | 
| Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 | 
| Anti-vibration | 0.075 mm (f= 10…58.1 Hz) non-operating according to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) non-operating according to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) during operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) conforming to IEC 60068-2-6 during operation | 0.075 mm (f= 10…58.1 Hz) non-operating according to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) non-operating according to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) during operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) conforming to IEC 60068-2-6 during operation | 
| impact resistance | 15 gn (duration = 11 ms) for non-operating according to IEC 60068-2-27 5 gn (duration = 11 ms) for operating according to IEC 60068-2-27 | 15 gn (duration = 11 ms) for non-operating according to IEC 60068-2-27 5 gn (duration = 11 ms) for operating according to IEC 60068-2-27 | 
| IP protection class | IP20 according to IEC 60529 (screw terminals) IP40 according to IEC 60529 (housing) IP50 according to IEC 60529 (front panel) | IP20 according to IEC 60529 (screw terminals) IP40 according to IEC 60529 (housing) IP50 according to IEC 60529 (front panel) | 
| pollution level | 3 according to IEC 60664-1 3 according to UL 508 | 3 according to IEC 60664-1 3 according to UL 508 | 
| Dielectric test winding and winding, winding voltage to ground | 2.5 kV AC 50 Hz, 1 minute conforming to IEC 60255-27 | 2.5 kV AC 50 Hz, 1 minute conforming to IEC 60255-27 | 
| packaging unit | ||
| Unit Type of Package 1 | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 
| Package 1 Height | 2.6cm | 2.6cm | 
| Package 1 Width | 8.2 cm | 8.2 cm | 
| Package 1 Length | 9.5cm | 9.5cm | 
| Package 1 Weight | 104.0g | 103.0g | 
| Unit Type of Package 2 | S02 | S02 | 
| Number of Units in Package 2 | 40 | 40 | 
| Package 2 Height | 15.0cm | 15.0cm | 
| Package 2 Width | 30.0cm | 30.0cm | 
| Package 2 Length | 40.0cm | 40.0cm | 
| Package 2 Weight | 4.535kg | 4.656kg | 
| Unit Type of Package 3 | P06 | P06 | 
| Number of Units in Package 3 | 640 | 640 | 
| Package 3 Height | 75.0cm | 75.0cm | 
| Package 3 Width | 60.0cm | 60.0cm | 
| Package 3 Length | 80.0cm | 80.0cm | 
| Package 3 Weight | 81.06kg | 82.996kg | 
| contract warranty | ||
| Warranty | 18 months | 18 months | 
| Weight | N/A | 
|---|---|
| Dimensions | N/A |