Main |
Part Number |
RM22UA33MR |
Product Series |
Harmony Control Relays |
product type |
Voltage control relay |
relay type |
Voltage control relay |
Number of grid phases |
1 phase |
input type |
DC |
Relay name |
RM22UA |
Relay Monitoring Parameters |
Undervoltage and Overvoltage Overvoltage and Undervoltage Monitoring in Window Mode |
time delay |
Adjustable 0.1…30 s, +/- 10 % full scale value over threshold Tt |
Switching capacity in VA |
2000VA |
Minimum switching current [Imin] |
10 mA at 5 V DC |
Maximum switching current |
8A AC |
Power consumption VA |
3.5VA AC |
Measuring range |
15…500 V voltage AC/DC 50/60 Hz |
use category |
AC-15 conforming to IEC 60947-5-1 |
DC-13 conforming to IEC 60947-5-1 |
AC-1 conforming to IEC 60947-4-1 |
DC-1 conforming to IEC 60947-4-1 |
contact type |
2 OC |
Additional information |
reset time |
1500 ms at maximum voltage |
Maximum Switching Voltage |
250V AC |
Rated supply voltage [Us] |
24…240 V AC/DC 50/60 Hz |
Power supply voltage range |
20.4…264 V AC/DC |
power consumption[W] |
1.5W DC |
Anti-instantaneous power failure |
10ms |
Impedance between terminals |
150 kOhm at E2-M terminals |
300 kOhm at E1-M terminals |
500 kOhm at E3-M terminals |
output contact |
2 C/O |
Rated output current |
8A |
Maximum measuring cycle |
100 ms period measured in true rms value |
hysteresis |
3 % fixed full scale window mode |
5…50 % adjustable threshold setting |
delay at power up |
600ms |
Repeatability |
+/- 0.5 % for input and measurement circuits |
+/- 2 % for time delay |
Measurement error |
< 1 % over the entire measuring range with a voltage change of |
0.05 %/°C with a temperature change |
Response time |
<= 500ms |
Type of overvoltage |
III conforms to IEC 60664-1 |
Insulation resistance |
> 100 MΩ at 500 V DC |
isolation |
Between power supply and measurement |
Wiring capacity |
Screw terminal, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) Solid without wire terminal Screw |
terminal, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16 ) flexible wire with wire terminal |
screw terminal, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) rigid wire without wire terminal screw |
terminal, 1 x 0.2…1 x 2.5 mm² ( AWG 24…AWG 14) flexible wire with wire terminal |
Tightening torque |
0.6…1 Nm conforming to IEC 60947-1 |
covering material |
Flame retardant plastic |
installation method |
35 mm DIN rail conforming to EN/IEC 60715 |
Electrical life |
100000 times |
Mechanical life |
10000000 times |
contact material |
Cadmium free |
Safe and reliable data |
MTTFd = 308.2 years |
B10d = 290000 |
width |
22.5 mm |
Product Weight |
0.11kg |
Feature |
Undervoltage and overvoltage in window mode |
model |
RM22 |
environment |
electromagnetic compatibility |
Exemption for use in residential, commercial and light-industrial environments Transmission standards per EN/IEC 61000-6-1 |
Exemption for industrial environments per EN/IEC 61000-6-2 Transmission standards for residential, commercial and light- |
industrial environments per EN/IEC 61000- 6-3 |
Transmission standards for industrial environments in accordance with EN/IEC 61000-6-4 |
Anti-static interference – test level: 6 kV (contact discharge) Level 3 in accordance with IEC 61000-4-2 |
Anti-static interference – test level: 8 kV (air Discharge) Class 3 Complies with IEC 61000-4-2 |
Radio Frequency Electromagnetic Field Radiation Immunity Test – Test Level: 10 V/m3 Class Complies with IEC 61000-4-3 Immunity |
to Fast Transients – Test Level: 4 kV (Direct Connection) Class 4 Complies with IEC 61000-4-4 |
Immunity to fast transients – Test level: 2 kV (capacitive coupling) level 4 Complies with IEC 61000-4-4 |
Surge discharge immunity – Test level: 4 kV (Common mode) level 4 Conforms to IEC 61000 -4-5 |
Surge Discharge Immunity- Test Level: 2 kV (Differential Mode) Level 4 Conforms to IEC 61000-4-5 |
Conducted and Radiated Emissions Group B 1 Conforms to CISPR 11 |
Conducted and Radiated Emissions Class B Conforms to CISPR 22 |
Standards compliant |
EN/IEC 60255-1 |
certified product |
RCM |
UL |
EAC |
CSA |
CE |
GL |
CCC |
storage environment temperature |
-40…70°C |
ambient temperature |
-20…50 °C at 60 Hz |
-20…60 °C at 50 Hz |
Relative humidity |
93…97 % at 25…55 °C conforming to IEC 60068-2-30 |
Anti-vibration |
0.075 mm (f= 10…58.1 Hz) non-operating according to IEC 60068-2-6 |
1 gn (f= 10…58.1 Hz) non-operating according to IEC 60068-2-6 |
0.035 mm (f= 58.1…150 Hz) during operation conforming to IEC 60068-2-6 |
0.5 gn (f= 58.1…150 Hz) conforming to IEC 60068-2-6 during operation |
impact resistance |
15 gn (duration = 11 ms) for non-operating according to IEC 60068-2-27 |
5 gn (duration = 11 ms) for operating according to IEC 60068-2-27 |
IP protection class |
IP20 according to IEC 60529 (screw terminals) |
IP40 according to IEC 60529 (housing) |
IP50 according to IEC 60529 (front panel) |
pollution level |
3 Conforming to IEC 60664-1 |
Dielectric test winding and winding, winding voltage to ground |
2.5 kV AC 50 Hz, 1 minute conforming to IEC 60255-27 |
packaging unit |
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
2.6cm |
Package 1 Width |
8.2 cm |
Package 1 Length |
9.5cm |
Package 1 Weight |
122g |
contract warranty |
Warranty |