| Main information | ||
| Part Number | GV2L07 | GV2L20 | 
| Product Series | TeSys Deca | TeSys Deca | 
| product name | TeSys GV2 | TeSys GV2 | 
| TeSys Deca | TeSys Deca | |
| product type | Motor circuit breaker | Motor circuit breaker | 
| product short name | Wxya | Wxya | 
| Applications | Motor protection | Motor protection | 
| Trip unit type | Magnetic | Magnetic | 
| Additional information | ||
| number of poles | 3P | 3P | 
| Grid type | AC | AC | 
| use category | Type AC conforms to IEC 60947-2 | Type AC conforms to IEC 60947-2 | 
| AC-3 conforms to IEC 60947-4-1 | AC-3 conforms to IEC 60947-4-1 | |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 | 50/60 Hz conforming to IEC 60947-2 | 
| fixed mode | 35 mm DIN rail: clipped | 35 mm DIN rail: clipped | 
| Panel: screw type (with 2 x M4 screws) | Panel: screw type (with 2 x M4 screws) | |
| Motor power (kW) | 0.75 kW at 400/415 V AC 50/60 Hz | 7.5 kW at 400/415 V AC 50/60 Hz | 
| 1.1 kW at 500 V AC 50/60 Hz | 9 kW at 500 V AC 50/60 Hz | |
| 1.5 kW at 690 V AC 50/60 Hz | 15 kW at 690 V AC 50/60 Hz | |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 100 kA Icu at 440 V AC 50 /60 Hz conforming to IEC 60947-2 | 20 kA Icu at 440 V AC 50 /60 Hz conforming to IEC 60947-2 | |
| 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 | 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Rated operating short-circuit breaking capacity [Ics] | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 | 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
| 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| control type | Rotary handle | Rotary handle | 
| Rated current [In] | 2.5A | 18A | 
| Electromagnetic trip current | 33.5A | 223A | 
| Conventional thermal current [Ith] | 2.5 A conforming to IEC 60947-4-1 | 18 A conforming to IEC 60947-4-1 | 
| Rated working voltage [Ue] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Rated insulation voltage [Ui] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 60947-2 | 6 kV according to IEC 60947-2 | 
| isolation function | Applies to IEC 60947-1 § 7-1-6 | Applies to IEC 60947-1 § 7-1-6 | 
| power consumption per pole | 1.8W | 1.8W | 
| Mechanical life | 100000 times | 100000 times | 
| Electrical life | 100000 cycles for AC-3 at 415 V In | 100000 cycles for AC-3 at 415 V In | 
| specified load | Continuous according to IEC 60947-4-1 | Continuous according to IEC 60947-4-1 | 
| Tightening torque | 1.7 Nm via screw-in terminals | 1.7 Nm via screw-in terminals | 
| width | 45 mm | 45 mm | 
| high | 89 mm | 89 mm | 
| depth | 97 mm | 97 mm | 
| product weight | 0.33kg | 0.33kg | 
| color | Dark gray | Dark gray | 
| Environment | ||
| Standards compliant | TM-D | TM-D | 
| EN/IEC 60947-4-1 | EN/IEC 60947-4-1 | |
| UL 60947-4-1 | UL 60947-4-1 | |
| DIN 3852-Y | ||
| certified product | CCC | CCC | 
| UL | UL | |
| CSA | CSA | |
| EAC | EAC | |
| LROS (Lloyds register of shipping) | LROS (Lloyds register of shipping) | |
| BV | BV | |
| RINA | RINA | |
| DNV-GL | DNV-GL | |
| UKCA | UKCA | |
| IECEE CB Scheme | IECEE CB Scheme | |
| IK protection class | IK04 | IK04 | 
| IP protection class | IP20 complies with screwed | IP20 complies with screwed | 
| climate tolerance | Conforms to IACS E10 | Conforms to IACS E10 | 
| storage environment temperature | -40…80°C | -40…80°C | 
| Fire resistance and abnormal high temperature resistance | 960 °C conforming to IEC 60695-2-11 | 960 °C conforming to IEC 60695-2-11 | 
| ambient temperature | -20…60°C | -20…60°C | 
| Shock and vibration resistance | Shock resistance: 30 Gn for 11 ms | Shock resistance: 30 Gn for 11 ms | 
| Shock resistance: 5 gn (5…150 Hz) | Shock resistance: 5 gn (5…150 Hz) | |
| working altitude | 2000 meters | 2000 meters | 
| Packaging unit | ||
| Unit Type of Package 1 | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 
| Package 1 Height | 4.800 cm | 9.300 cm | 
| Package 1 Width | 9.500 cm | 4.600 cm | 
| Package 1 Length | 10.300 cm | 10.000 cm | 
| Package 1 Weight | 320.000g | 330.000g | 
| Unit Type of Package 2 | S02 | S02 | 
| Number of Units in Package 2 | 20 | 20 | 
| Package 2 Height | 15.000 cm | 15.000 cm | 
| Package 2 Width | 30.000 cm | 30.000 cm | 
| Package 2 Length | 40.000 cm | 40.000 cm | 
| Package 2 Weight | 6.593 kg | 6.930kg | 
| Unit Type of Package 3 | P06 | |
| Number of Units in Package 3 | 320 | |
| Package 3 Height | 75.000 cm | |
| Package 3 Width | 60.000 cm | |
| Package 3 Length | 80.000 cm | |
| Package 3 Weight | 113.490kg | |
| Contract warranty | ||
| Warranty | 18 months | 18 months |