Contact Us:
sales@inosaki.com

LOGO!POWER 5 V / 6.3 A Stabilized Power Supply – Siemens Power Supply

$ 133.40

SKU 6EP3311-6SB00-0AY0 Category

Features

input
type of the power supply network 1-phase AC or DC
supply voltage at AC
● minimum rated value 100 V
● maximum rated value 240 V
● initial value 85 V
● full-scale value 264 V
input voltage at DC 110 … 300 V
wide range input Yes
overvoltage overload capability 300 V AC for 1 s
buffering time for rated value of the output current in the event of
power failure minimum
40 ms
operating condition of the mains buffering at Vin = 187 V
line frequency 50/60 Hz
line frequency 47 … 63 Hz
input current
● at rated input voltage 120 V 0.71 A
● at rated input voltage 230 V 0.37 A
current limitation of inrush current at 25 °C maximum 50 A
I2t value maximum 3 A²·s
fuse protection type internal
fuse protection type in the feeder Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A
characteristic C
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 5 V
output voltage
● at output 1 at DC rated value 5 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 4.6 … 5.4 V
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.1 %
residual ripple
● maximum 100 mV
● typical 30 mV
voltage peak
● maximum 100 mV
● typical 50 mV
display version for normal operation Green LED for output voltage OK
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 0.5 s
voltage increase time of the output voltage
● typical 100 ms
output current
● rated value 6.3 A
● rated range 0 … 6.3 A; +55 … +70 °C: Derating 2%/K
supplied active power typical 31.5 W
bridging of equipment Yes
number of parallel-switched equipment resources for increasing
the power
2
efficiency
efficiency in percent 79.8 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
8 W
● during no-load operation maximum 0.3 W
closed-loop control
relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical
0.2 %
relative control precision of the output voltage at load step of
resistive load 10/90/10 % typical
7 %
setting time
● load step 10 to 90% typical 1 ms
● load step 90 to 10% typical 1 ms
protection and monitoring
design of the overvoltage protection Yes, according to EN 60950-1
property of the output short-circuit proof Yes
design of short-circuit protection Constant current characteristic
● typical 8.2 A
overcurrent overload capability
● when switching on 150% Iout rated typ. 200 ms
● in normal operation overload capability 150% Iout rated typ. 200 ms
enduring short circuit current RMS value
● maximum 8.2 A
measuring point for output current Yes; 50 mV =^ 6.3 A
safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class Class II (without protective conductor)
protection class IP IP20
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation not applicable
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-
Recognized (UL 60950, CSA C22.2 No. 60950), File E151273
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-
Recognized (UL 60950, CSA C22.2 No. 60950), File E151273
● EAC approval Yes
● NEC Class 2 No
● SEMI F47 Yes
type of certification
● CB-certificate Yes
MTBF at 40 °C 2 654 280 h
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx No
● ATEX No
● ULhazloc approval No
● cCSAus, Class 1, Division 2 No
● FM registration No
standards, specifications, approvals marine classification
shipbuilding approval Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) Yes
● Det Norske Veritas (DNV) Yes
● Lloyds Register of Shipping (LRS) Yes
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration Yes
global warming potential [CO2 eq]
● total 222.9 kg
● during manufacturing 3.8 kg
● during operation 218.9 kg
● after end of life 0.14 kg
ambient conditions
ambient temperature
● during operation -25 … +70; with natural convection
● during transport -40 … +85
● during storage -40 … +85
environmental category according to IEC 60721 Climate class 3K3, 5 … 95% no condensation
connection method
type of electrical connection screw terminal
● at input L, N: 1 screw terminal each for 0.5 … 2.5 mm2 single-core/finely stranded
● at output +, -: 1 screw terminal each for 0.5 … 2.5 mm²
● for auxiliary contacts
mechanical data
width × height × depth of the enclosure 54 × 90 × 53 mm
installation width × mounting height 54 mm × 130 mm
required spacing
● top 20 mm
● bottom 20 mm
● left 0 mm
● right 0 mm
fastening method Snaps onto DIN rail EN 60715 35×7.5/15, direct mounting in different mounting
positions
● DIN-rail mounting Yes
● S7 rail mounting No
● wall mounting Yes
housing can be lined up Yes
net weight 0.2 kg
further information internet links
internet link
● to website: Industry Mall https://mall.industry.siemens.com
● to web page: selection aid TIA Selection Tool https://www.siemens.com/tstcloud
● to web page: power supplies https://siemens.com/sitop
● to website: CAx-Download-Manager https://siemens.com/cax
● to website: Industry Online Support https://support.industry.siemens.com
additional information
other information Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
security information
security information Siemens provides products and solutions with industrial cybersecurity functions
that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial cybersecurity concept. Siemens’ products and
solutions constitute one element of such a concept. Customers are responsible
for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or
network segmentation) are in place. For additional information on industrial
cybersecurity measures that may be implemented, please visit
www.siemens.com/cybersecurity-industry. Siemens’ products and solutions
undergo continuous development to make them more secure. Siemens strongly
recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase
customer’s exposure to cyber threats. To stay informed about product updates,
subscribe to the Siemens Industrial Cybersecurity RSS Feed under
https://www.siemens.com/cert. (V4.7)

Additional information

Weight 0.200 kg
Dimensions 6.7 × 9.2 × 7.3 cm

Related Products

M22
ER-VS02
1605779021(1)
M8
Fujinon_Fujifilm_Lens_AE00188
camera-usb3-ueye-le-1
Select your currency