| Main |
|
| Part Number |
33072 |
| Product or component type |
Control unit |
| Trip unit name |
MicroLogic 5.0 A |
| Trip unit technology |
Electronic |
| Range compatibility |
MasterPact NT |
|
MasterPact NW |
|
Compact NS |
|
Masterpact MT |
|
PowerPact P-Frame |
|
PowerPact R-Frame |
| Device application |
Distribution |
| Number of poles |
3P |
|
4P |
| Protected poles description |
4t |
|
3t |
|
3t + N/2 |
| Trip unit protection functions |
Selective protection |
| Protection type |
For short time short-circuit protection |
|
for overload protection (long time) |
|
for instantaneous short-circuit protection |
| Trip unit rating |
630 A at 50 °C |
|
800 A at 50 °C |
|
1000 A at 50 °C |
|
1250 A at 50 °C |
|
1600 A at 50 °C |
|
2000 A at 50 °C |
|
2500 A at 50 °C |
|
3200 A at 50 °C |
|
4000 A at 50 °C |
|
5000 A at 50 °C |
|
6300 A at 50 °C |
| Network type |
AC |
| Network frequency |
50/60 Hz |
| Circuit breaker mounting mode |
Fixed |
|
Drawout |
| Complementary |
|
| Long-time pick-up adjustment type Ir (thermal protection) |
Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range |
0.4…1 x In |
| Long-time protection delay adjustment type tr |
Adjustable 9 settings |
| [tr] long-time protection delay adjustment range |
0.7…16.6 s at 7.2 x Ir |
|
0.7…24 s at 6 x Ir |
|
12.5…600 s at 1.5 x Ir |
| Thermal memory |
20 mn |
| Short-time protection pick-up adjustment type Isd |
Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range |
1.5…10 x Ir |
| Short-time protection delay adjustment type tsd |
Adjustable |
| [tsd] Short-time protection delay adjustment range |
0…0.4 s I²t=off |
|
0.1…0.4 s I²t=on |
| Instantaneous protection pick-up adjustment type Ii |
Adjustable 9 settings |
| [Ii] instantaneous protection pick-up adjustment range |
2…15 x In |
|
Off |
| Earth-leakage protection |
Without |
| Zone selective interlocking ZSI |
With |
| Local signalling |
3 LEDs (red) for electrical fault |
|
1 LED (red) for internal error |
| Display type |
Digital display |
| type of measurement |
Ammeter |
| Communication of data |
Measurement readout |
|
Protection and alarm settings |
| Environment |
|
| Ambient air temperature for operation |
-25…70 °C |
| Ambient air temperature for storage |
-40…85 °C |
| Packing Units |
|
| Unit Type of Package 1 |
PCE |
| Number of Units in Package 1 |
1 |
| Package 1 Height |
6.6 cm |
| Package 1 Width |
8.1 cm |
| Package 1 Length |
21.6 cm |
| Package 1 Weight |
248.0 g |
| Unit Type of Package 2 |
P06 |
| Number of Units in Package 2 |
120 |
| Package 2 Height |
75.0 cm |
| Package 2 Width |
80.0 cm |
| Package 2 Length |
60.0 cm |
| Package 2 Weight |
40.36 kg |
| Unit Type of Package 3 |
S03 |
| Number of Units in Package 3 |
15 |
| Package 3 Height |
30.0 cm |
| Package 3 Width |
30.0 cm |
| Package 3 Length |
40.0 cm |
| Package 3 Weight |
4.17 kg |
| Contractual warranty |
|
| Warranty |
18 months |