Main information |
Part Number |
C2536E250 |
Product Series |
ComPacT new generation |
Product Series |
ComPacT NSX100…250 new generation |
product type |
Trip unit |
Trip unit name |
MicroLogic 6.2E |
Trip unit type |
Electronic |
scope of application |
ComPacT new generation NSX250 |
Applications |
Distribution protection |
number of poles |
3P |
Description of protection pole |
3D |
Trip unit protection function |
LSIG |
protection type |
L : for overload protection (long time delay) |
S : for short circuit short time delay protection |
I : for short circuit instantaneous protection |
G : for ground fault protection |
Trip unit rating |
250 A at 40 °C |
Rated working voltage [Ue] |
690V AC 50/60Hz |
Grid type |
AC |
grid frequency |
50/60Hz |
Circuit breaker mounting mode |
Fixed |
Additional information |
|
Long-time pick-up adjustment type Ir (thermal protection) |
9 steps adjustable |
[Ir] long-time protection pick-up adjustment range |
100…250A |
Long-time protection delay adjustment type tr |
Adjustable |
[tr] long-time protection delay adjustment range |
15…400 s at 1.5 x Ir |
0.35…11 s at 7.2 x Ir |
0.5…16 s at 6 x Ir |
hot memory |
20 minutes before tripping and after tripping |
Short-time protection pick-up adjustment type Isd |
9 steps adjustable |
[Isd] Short-time protection pick-up adjustment range |
1.5…10 x Ir |
Short-time protection delay adjustment type tsd |
Adjustable |
[tsd] Short-time protection delay adjustment range |
0…0.4 s inverse time off I²t=off |
0.1…0.4 s inverse time on I²t=on |
Instantaneous protection pick-up adjustment type II |
Adjustable |
[Ii] Instantaneous protection pick-up adjustment range |
1.5…12 x In |
Ground-fault protection pick-up adjustment type Ig |
Adjustable |
[Ig] ground-fault protection pick-up adjustment range |
0.4…1 x In for In = 40 A |
0.2…1 x In for In > 40 A |
Ig enable on/off |
Ground-fault protection time delay adjustment type tg |
Adjustable |
[tg] ground-fault protection time delay adjustment range |
0…0.4 s inverse time off I²t=off |
0.1…0.4 s inverse time on I²t=on |
Leakage current protection |
No leakage protection |
Zone Selective Interlocking ZSI |
Have |
local signal indication |
LED indicator (green) for function available: |
LED 105 % Ir (red) for overload: |
LED 90 % Ir (orange) for overload: |
display type |
LCD display |
measurement type |
Meter |
data communication |
Energy Metering |
Protection and Alarm Settings |
Timestamp History and Event Meters |
Instantaneous and Demanded Values |
Holding Indicators |
Demanded Current and Power |
Power Quality |
Meter/Micrometer |
Electrical data logging |
Hold indicator |
environment |
|
Standards compliant |
TM-D |
Electric Shock Protection Level |
Class II |
pollution level |
3 Conforming to IEC 60947-1 |
IP protection class |
IP40 complies with screwed |
operating temperature |
-25…70°C |
storage environment temperature |
-40…85°C |
packaging unit |
|
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
9.8 cm |
Package 1 Width |
11.0cm |
Package 1 Length |
15.0cm |
Package 1 Weight |
555.0g |
Unit Type of Package 2 |
S03 |
Number of Units in Package 2 |
11 |
Package 2 Height |
30cm |
Package 2 Width |
30cm |
Package 2 Length |
40cm |
Package 2 Weight |
6.551kg |
Contract warranty |
Warranty |
18 months |