| Model | |
| product brand name | SENTRON | 
| product designation | Miniature circuit breaker | 
| General technical data | |
| number of poles | 3 | 
| design of pole | 3P | 
| tripping characteristic class | D | 
| mechanical service life (operating cycles) typical | 10 000 | 
| overvoltage category | III | 
| degree of pollution | 3 | 
| Voltage | |
| type of voltage of the operating voltage | AC | 
| insulation voltage (Ui) | |
| ● with single-phase operation at AC rated value | 440 V | 
| ● with multi-phase operation at AC rated value | 440 V | 
| supply voltage with single-phase operation at AC rated value | 230 V | 
| operational current | |
| ● at 40 °C rated value | 15.23 A | 
| ● at 50 °C rated value | 14.43 A | 
| ● at 55 °C rated value | 14 A | 
| ● at 60 °C rated value | 13.57 A | 
| ● at AC rated value | 16 A | 
| Supply voltage | |
| supply voltage | |
| ● at AC | 400 V | 
| ● at DC rated value | 60 V | 
| value range of the supply voltage frequency | 50/60 Hz | 
| operating voltage at DC rated value maximum | 72 V | 
| Protection class | |
| protection class IP | IP20, with connected conductors | 
| Breaking Capacity | |
| switching capacity current | |
| ● at DC according to IEC 60947-2 rated value | 15 kA | 
| ● according to EN 60898 rated value | 15 kA | 
| ● according to IEC 60947-2 rated value | 25 kA | 
| Dissipation | |
| power loss [W] for rated value of the current at AC in hot operating state per pole | 1.6 W | 
| suitability for operation | Infrastructure / Industry | 
| Product details | |
| product feature touch protection | Yes | 
| product component | |
| ● combined terminal top | Yes | 
| ● combined terminal bottom | Yes | 
| ● neutral conductor switching | No | 
| product feature | |
| ● properties for main switches in accordance with EN 60204-1 | Yes | 
| ● halogen-free | Yes | 
| ● sealable | Yes | 
| ● silicon-free | Yes | 
| product extension installable supplementary devices | Yes | 
| Product function | |
| set values setting current (Ii) for I-tripping | 14,5 | 
| reference value setting current (Ii) for I-tripping | x In | 
| Short circuit | |
| short-circuit current breaking capacity (Icn) | |
| ● at AC according to UL 1077 and CSA C22.2 No.235 | 5 kA | 
| Connections | |
| connectable conductor cross-section solid | |
| ● minimum | 0.75 mm² | 
| ● maximum | 35 mm² | 
| connectable conductor cross-section stranded | |
| ● minimum | 0.75 mm² | 
| ● maximum | 35 mm² | 
| connectable conductor cross-section finely stranded with core end processing | |
| ● minimum | 0.75 mm² | 
| ● maximum | 25 mm² | 
| AWG number as coded connectable conductor cross section | |
| ● minimum | 18 | 
| ● maximum | 4 | 
| tightening torque [lbf·in] with screw-type terminals | |
| ● minimum | 22 lbf·in | 
| ● maximum | 31 lbf·in | 
| tightening torque with screw-type terminals | |
| ● minimum | 2.5 N·m | 
| ● maximum | 3.5 N·m | 
| position of power supply cord | Any | 
| Mechanical Design | |
| height | 90 mm | 
| width | 54 mm | 
| depth | 76 mm | 
| installation depth | 70 mm | 
| number of modular width units | 3 | 
| fastening method | Quick assembly system | 
| mounting position | any | 
| net weight | 451 g | 
| Environmental conditions | |
| standard | IEC / EN 60898-1, IEC / EN 60947-2 / UL1077 | 
| vibration resistance according to IEC 60068-2-6 | ±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz | 
| ambient temperature during operation | |
| ● minimum | -40 °C | 
| ● maximum | 70 °C | 
| ambient temperature during storage | |
| ● minimum | -40 °C | 
| ● maximum | 75 °C | 
| number of test cycles for environmental testing according to IEC 60068-2-30 | 6 | 
| Weight | 0.451 kg | 
|---|---|
| Dimensions | 5.8 × 9.4 × 8.4 cm |