| Main | |||
| Part Number | TM221CE16R | TM221CE24R | TM221CE40R | 
| Range of product | Modicon M221 | Modicon M221 | Modicon M221 | 
| Product or component type | Logic controller | Logic controller | Logic controller | 
| [Us] rated supply voltage | 100…240 V AC | 100…240 V AC | 100…240 V AC | 
| discrete input number | 9, discrete input conforming to IEC 61131-2 Type 1 | 14, discrete input conforming to IEC 61131-2 Type 1 | 24, discrete input conforming to IEC 61131-2 Type 1 | 
| analogue input number | 2 at 0…10 V | 2 at 0…10 V | 2 at 0…10 V | 
| Discrete output type | Relay normally open | Relay normally open | Relay normally open | 
| discrete output number | 7 relay | 10 relay | 16 relay | 
| discrete output voltage | 5…125 V DC 5…250 V AC | 5…125 V DC 5…250 V AC | 5…125 V DC 5…250 V AC | 
| discrete output current | 2A | 2A | 2A | 
| Complementary | |||
| Discrete I/O number | 16 | 24 | 40 | 
| maximum number of I/O expansion module | 4 for transistor output 4 for relay output | 7 for transistor output 7 for relay output | 7 for relay output | 
| Supply voltage limits | 85…264 V | 85…264 V | 85…264 V | 
| Network frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | 
| Inrush current | 40 A | 40 A | 40 A | 
| maximum power consumption in VA | 49 VA at 100…240 V with max number of I/O expansion module 33 VA at 100…240 V without I/O expansion module | 58 VA at 100…240 V with max number of I/O expansion module 35 VA at 100…240 V without I/O expansion module | 70 VA at 100…240 V with max number of I/O expansion module 41 VA at 100…240 V without I/O expansion module | 
| power supply output current | 0.325 A 5 V for expansion bus 0.12 A 24 V for expansion bus | 0.52 A 5 V for expansion bus 0.16 A 24 V for expansion bus | 0.52 A 5 V for expansion bus 0.24 A 24 V for expansion bus | 
| discrete input logic | Sink or source (positive/negative) | Sink or source (positive/negative) | Sink or source (positive/negative) | 
| Discrete input voltage | 24 V | 24 V | 24 V | 
| Discrete input voltage type | DC | DC | DC | 
| Analogue input resolution | 10 bits | 10 bits | 10 bits | 
| LSB value | 10 mV | 10 mV | 10 mV | 
| conversion time | 1 ms per channel + 1 controller cycle time for analogue input analog input | 1 ms per channel + 1 controller cycle time for analogue input analog input | 1 ms per channel + 1 controller cycle time for analogue input analog input | 
| permitted overload on inputs | +/- 30 V DC for 5 min (maximum) for analog input +/- 13 V DC (permanent) for analog input | +/- 30 V DC for 5 min (maximum) for analog input +/- 13 V DC (permanent) for analog input | +/- 30 V DC for 5 min (maximum) for analog input +/- 13 V DC (permanent) for analog input | 
| voltage state 1 guaranteed | >= 15 V for input | >= 15 V for input | >= 15 V for input | 
| voltage state 0 guaranteed | <= 5 V for input | <= 5 V for input | <= 5 V for input | 
| discrete input current | 7 mA for discrete input 5 mA for fast input | 7 mA for discrete input 5 mA for fast input | 7 mA for discrete input 5 mA for fast input | 
| input impedance | 3.4 kOhm for discrete input 100 kOhm for analog input 4.9 kOhm for fast input | 3.4 kOhm for discrete input 100 kOhm for analog input 4.9 kOhm for fast input | 3.4 kOhm for discrete input 100 kOhm for analog input 4.9 kOhm for fast input | 
| response time | 35 µs turn-off, I2…I5 terminal(s) for input 10 ms turn-on for output 10 ms turn-off for output 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 100 µs turn-off, other terminals terminal(s) for input | 35 µs turn-off, I2…I5 terminal(s) for input 10 ms turn-on for output 10 ms turn-off for output 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 100 µs turn-off, other terminals terminal(s) for input | 35 µs turn-off, I2…I5 terminal(s) for input 10 ms turn-on for output 10 ms turn-off for output 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 100 µs turn-off, other terminals terminal(s) for input | 
| configurable filtering time | 0 ms for input 3 ms for input 12 ms for input | 0 ms for input 3 ms for input 12 ms for input | 0 ms for input 3 ms for input 12 ms for input | 
| output voltage limits | 125 V DC 277 V AC | 125 V DC 277 V AC | 125 V DC 277 V AC | 
| maximum current per output common | 6 A at COM 1 7 A at COM 0 | 4 A at COM 2 7 A at COM 0 7 A at COM 1 | 7A | 
| absolute accuracy error | +/- 1 % of full scale for analog input | +/- 1 % of full scale for analog input | +/- 1 % of full scale for analog input | 
| electrical durability | 100000 cycles AC-12, 120 V, 240 VA, resistive 100000 cycles AC-12, 240 V, 480 VA, resistive 300000 cycles AC-12, 120 V, 80 VA, resistive 300000 cycles AC-12, 240 V, 160 VA, resistive 100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive 100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive 100000 cycles DC-12, 24 V, 48 W, resistive 300000 cycles DC-12, 24 V, 16 W, resistive 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms) 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms) | 100000 cycles AC-12, 120 V, 240 VA, resistive 100000 cycles AC-12, 240 V, 480 VA, resistive 300000 cycles AC-12, 120 V, 80 VA, resistive 300000 cycles AC-12, 240 V, 160 VA, resistive 100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive 100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive 100000 cycles DC-12, 24 V, 48 W, resistive 300000 cycles DC-12, 24 V, 16 W, resistive 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms) 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms) | 100000 cycles AC-12, 120 V, 240 VA, resistive 100000 cycles AC-12, 240 V, 480 VA, resistive 300000 cycles AC-12, 120 V, 80 VA, resistive 300000 cycles AC-12, 240 V, 160 VA, resistive 100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive 100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive 100000 cycles DC-12, 24 V, 48 W, resistive 300000 cycles DC-12, 24 V, 16 W, resistive 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms) 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms) | 
| switching frequency | 20 switching operations/minute with maximum load | 20 switching operations/minute with maximum load | 20 switching operations/minute with maximum load | 
| mechanical durability | 20000000 cycles for relay output | 20000000 cycles for relay output | 20000000 cycles for relay output | 
| minimum load | 1 mA at 5 V DC for relay output | 1 mA at 5 V DC for relay output | 1 mA at 5 V DC for relay output | 
| protection type | Without protection at 5 A | Without protection at 5 A | Without protection at 5 A | 
| reset time | 1 s | 1 s | 1 s | 
| memory capacity | 256 kB for user application and data RAM with 10000 instructions 256 kB for internal variables RAM | 256 kB for user application and data RAM with 10000 instructions 256 kB for internal variables RAM | 256 kB for user application and data RAM with 10000 instructions 256 kB for internal variables RAM | 
| data backed up | 256 kB built-in flash memory for backup of application and data | 256 kB built-in flash memory for backup of application and data | 256 kB built-in flash memory for backup of application and data | 
| data storage equipment | 2 GB SD card (optional) | 2 GB SD card (optional) | 2 GB SD card (optional) | 
| battery type | BR2032 lithium non-rechargeable, battery life: 4 year(s) | BR2032 lithium non-rechargeable, battery life: 4 year(s) | BR2032 lithium non-rechargeable, battery life: 4 year(s) | 
| backup time | 1 year at 25 °C (by interruption of power supply) | 1 year at 25 °C (by interruption of power supply) | 1 year at 25 °C (by interruption of power supply) | 
| execution time for 1 KInstruction | 0.3 ms for event and periodic task | 0.3 ms for event and periodic task | 0.3 ms for event and periodic task | 
| execution time per instruction | 0.2 µs Boolean | 0.2 µs Boolean | 0.2 µs Boolean | 
| exct time for event task | 60 µs response time | 60 µs response time | 60 µs response time | 
| Maximum size of object areas | 255 %C counters 512 %KW constant words 255 %TM timers 512 %M memory bits 8000 %MW memory words | 255 %TM timers 512 %M memory bits 8000 %MW memory words 255 %C counters 512 %KW constant words | 8000 %MW memory words 255 %TM timers 512 %KW constant words 255 %C counters 512 %M memory bits | 
| Realtime clock | With | With | With | 
| clock drift | <= 30 s/month at 25 °C | <= 30 s/month at 25 °C | <= 30 s/month at 25 °C | 
| regulation loop | Adjustable PID regulator up to 14 simultaneous loops | Adjustable PID regulator up to 14 simultaneous loops | Adjustable PID regulator up to 14 simultaneous loops | 
| counting input number | 4 fast input (HSC mode) at 100 kHz 32 bits | 4 fast input (HSC mode) at 100 kHz 32 bits | 4 fast input (HSC mode) at 100 kHz 32 bits | 
| counter function | Pulse/direction A/B Single phase | A/B Single phase Pulse/direction | Single phase A/B Pulse/direction | 
| integrated connection type | USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface Ethernet with RJ45 connector | USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface Ethernet with RJ45 connector | USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface Ethernet with RJ45 connector | 
| supply | (Serial)serial link supply: 5 V, <200 mA | (Serial)serial link supply: 5 V, <200 mA | (Serial)serial link supply: 5 V, <200 mA | 
| transmission rate | 1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for USB | 1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for USB | 1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for USB | 
| communication port protocol | USB port: USB – SoMachine-Network Non isolated serial link: Modbus master/slave – RTU/ASCII or SoMachine-Network Ethernet | USB port: USB – SoMachine-Network Non isolated serial link: Modbus master/slave – RTU/ASCII or SoMachine-Network Ethernet | USB port: USB – SoMachine-Network Non isolated serial link: Modbus master/slave – RTU/ASCII or SoMachine-Network Ethernet | 
| port Ethernet | 10BASE-T/100BASE-TX 1 port with 100 m copper cable | 10BASE-T/100BASE-TX 1 port with 100 m copper cable | 10BASE-T/100BASE-TX 1 port with 100 m copper cable | 
| Communication service | DHCP client Ethernet/IP adapter Modbus TCP server Modbus TCP slave device Modbus TCP client | Modbus TCP server Modbus TCP slave device DHCP client Modbus TCP client Ethernet/IP adapter | DHCP client Modbus TCP client Ethernet/IP adapter Modbus TCP server Modbus TCP slave device | 
| local signalling | 1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED per channel (green) for I/O state 1 LED (green) for SL Ethernet network activity (green) for ACT Ethernet network link (yellow) for Link (Link Status) | 1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED per channel (green) for I/O state 1 LED (green) for SL Ethernet network activity (green) for ACT Ethernet network link (yellow) for Link (Link Status) | 1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED per channel (green) for I/O state 1 LED (green) for SL Ethernet network activity (green) for ACT Ethernet network link (yellow) for Link (Link Status) | 
| electrical connection | Removable screw terminal block for inputs removable screw terminal block for outputs terminal block, 3 terminal(s) for connecting the 24 V DC power supply connector, 4 terminal(s) for analogue inputs Mini B USB 2.0 connector for a programming terminal | Removable screw terminal block for inputs removable screw terminal block for outputs terminal block, 3 terminal(s) for connecting the 24 V DC power supply connector, 4 terminal(s) for analogue inputs Mini B USB 2.0 connector for a programming terminal | Removable screw terminal block for inputs removable screw terminal block for outputs terminal block, 3 terminal(s) for connecting the 24 V DC power supply connector, 4 terminal(s) for analogue inputs Mini B USB 2.0 connector for a programming terminal | 
| maximum cable distance between devices | Shielded cable: <10 m for fast input Unshielded cable: <30 m for output Unshielded cable: <30 m for digital input Unshielded cable: <1 m for analog input | Shielded cable: <10 m for fast input Unshielded cable: <30 m for output Unshielded cable: <30 m for digital input Unshielded cable: <1 m for analog input | Shielded cable: <10 m for fast input Unshielded cable: <30 m for output Unshielded cable: <30 m for digital input Unshielded cable: <1 m for analog input | 
| insulation | Between input and internal logic at 500 V AC Non-insulated between analogue input and internal logic Non-insulated between analogue inputs Between supply and ground at 1500 V AC Between sensor power supply and ground at 500 V AC Between input and ground at 500 V AC Between output and ground at 1500 V AC Between supply and internal logic at 2300 V AC Between sensor power supply and internal logic at 500 V AC Between output and internal logic at 2300 V AC Between Ethernet terminal and internal logic at 500 V AC Between supply and sensor power supply at 2300 V AC | Between input and internal logic at 500 V AC Non-insulated between analogue input and internal logic Non-insulated between analogue inputs Between supply and ground at 1500 V AC Between sensor power supply and ground at 500 V AC Between input and ground at 500 V AC Between output and ground at 1500 V AC Between supply and internal logic at 2300 V AC Between sensor power supply and internal logic at 500 V AC Between output and internal logic at 2300 V AC Between Ethernet terminal and internal logic at 500 V AC Between supply and sensor power supply at 2300 V AC | Between input and internal logic at 500 V AC Non-insulated between analogue input and internal logic Non-insulated between analogue inputs Between supply and ground at 1500 V AC Between sensor power supply and ground at 500 V AC Between input and ground at 500 V AC Between output and ground at 1500 V AC Between supply and internal logic at 2300 V AC Between sensor power supply and internal logic at 500 V AC Between output and internal logic at 2300 V AC Between Ethernet terminal and internal logic at 500 V AC Between supply and sensor power supply at 2300 V AC | 
| Marking | CE | CE | CE | 
| sensor power supply | 24 V DC at 250 mA supplied by the controller | 24 V DC at 250 mA supplied by the controller | 24 V DC at 250 mA supplied by the controller | 
| mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit | 
| Height | 90 mm | 90 mm | 90 mm | 
| Depth | 70 mm | 70 mm | 70 mm | 
| Width | 95 mm | 110 mm | 160 mm | 
| Net weight | 0.346 kg | 0.395 kg | 0.456 kg | 
| Environment | |||
| standards | EN/IEC 61010-2-201 EN/IEC 60664-1 EN/IEC 61131-2 | EN/IEC 61010-2-201 EN/IEC 61131-2 EN/IEC 60664-1 | EN/IEC 60664-1 EN/IEC 61131-2 EN/IEC 61010-2-201 | 
| Product certifications | CSA cULus LR RCM IACS E10 EAC ABS DNV-GL | LR cULus IACS E10 CSA ABS DNV-GL EAC RCM | DNV-GL EAC ABS cULus LR RCM CSA IACS E10 | 
| Environmental characteristic | Ordinary and hazardous location | Ordinary and hazardous location | Ordinary and hazardous location | 
| resistance to electrostatic discharge | 8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2 | 8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2 | 8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2 | 
| resistance to electromagnetic fields | 10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2…2.7 GHz conforming to EN/IEC 61000-4-3 | 10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2…2.7 GHz conforming to EN/IEC 61000-4-3 | 10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2…2.7 GHz conforming to EN/IEC 61000-4-3 | 
| resistance to magnetic fields | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 | 
| resistance to fast transients | 2 kV (power lines) conforming to EN/IEC 61000-4-4 2 kV (relay output) conforming to EN/IEC 61000-4-4 1 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4 | 2 kV (power lines) conforming to EN/IEC 61000-4-4 2 kV (relay output) conforming to EN/IEC 61000-4-4 1 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4 | 2 kV (power lines) conforming to EN/IEC 61000-4-4 2 kV (relay output) conforming to EN/IEC 61000-4-4 1 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4 | 
| surge withstand | 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5 2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 | 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5 2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 | 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5 2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 | 
| resistance to conducted disturbances | 10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6 3 V 0.1…80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) | 10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6 3 V 0.1…80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) | 10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6 3 V 0.1…80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) | 
| electromagnetic emission | Conducted emissions – test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 120…69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions – test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 79…63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011 | Conducted emissions – test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 120…69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions – test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 79…63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011 | Conducted emissions – test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 120…69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions – test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 79…63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011 | 
| Immunity to microbreaks | 10 ms | 10 ms | 10 ms | 
| ambient air temperature for operation | -10…55 °C (horizontal installation) -10…35 °C (vertical installation) | -10…55 °C (horizontal installation) -10…35 °C (vertical installation) | -10…55 °C (horizontal installation) -10…35 °C (vertical installation) | 
| Ambient air temperature for storage | -25…70 °C | -25…70 °C | -25…70 °C | 
| relative humidity | 10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage) | 10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage) | 10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage) | 
| IP degree of protection | IP20 with protective cover in place | IP20 with protective cover in place | IP20 with protective cover in place | 
| Pollution degree | <= 2 | <= 2 | <= 2 | 
| Operating altitude | 0…2000 m | 0…2000 m | 0…2000 m | 
| Storage altitude | 0…3000 m | 0…3000 m | 0…3000 m | 
| vibration resistance | 3.5 mm at 5…8.4 Hz on symmetrical rail 3.5 mm at 5…8.4 Hz on panel mounting 1 gn at 8.4…150 Hz on symmetrical rail 1 gn at 8.4…150 Hz on panel mounting | 3.5 mm at 5…8.4 Hz on symmetrical rail 3.5 mm at 5…8.4 Hz on panel mounting 1 gn at 8.4…150 Hz on symmetrical rail 1 gn at 8.4…150 Hz on panel mounting | 3.5 mm at 5…8.4 Hz on symmetrical rail 3.5 mm at 5…8.4 Hz on panel mounting 1 gn at 8.4…150 Hz on symmetrical rail 1 gn at 8.4…150 Hz on panel mounting | 
| shock resistance | 98 m/s² for 11 ms | 98 m/s² for 11 ms | 98 m/s² for 11 ms | 
| Packing Units | |||
| Unit Type of Package 1 | PCE | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 1 | 
| Package 1 Height | 10.829 cm | 11.156 cm | 11.09 cm | 
| Package 1 Width | 14.04 cm | 14.152 cm | 14.183 cm | 
| Package 1 Length | 14.181 cm | 15.681 cm | 21.085 cm | 
| Package 1 Weight | 590.0 g | 650.0 g | 830.0 g | 
| Unit Type of Package 2 | CAR | CAR | CAR | 
| Number of Units in Package 2 | 20 | 20 | 12 | 
| Package 2 Height | 28.9 cm | 29.9 cm | 29.2 cm | 
| Package 2 Width | 39.5 cm | 39.4 cm | 39.8 cm | 
| Package 2 Length | 57.4 cm | 57.5 cm | 57.9 cm | 
| Package 2 Weight | 12.771 kg | 14.171 kg | 11.04 kg | 
| Weight | N/A | 
|---|---|
| Dimensions | N/A |