TM3DM8R |
TM3DM24R |
Range of product |
Modicon TM3 |
Modicon TM3 |
Product or component type |
Discrete I/O module |
Discrete I/O module |
Range compatibility |
Modicon M241 |
Modicon M241 |
Modicon M251 |
Modicon M251 |
Modicon M221 |
Modicon M221 |
Modicon M262 |
Modicon M262 |
discrete input number |
4 for input conforming to IEC 61131-2 Type 1 |
16 for input conforming to IEC 61131-2 Type 1 |
discrete input logic |
Sink or source (positive/negative) |
Sink or source (positive/negative) |
Discrete input voltage |
24 V |
24 V |
discrete input current |
7 mA for input |
7 mA for input |
Discrete output type |
Relay normally open |
Relay normally open |
discrete output number |
4 |
8 |
Discrete output logic |
Positive or negative |
Positive or negative |
discrete output voltage |
24 V DC for relay output |
24 V DC for relay output |
240 V AC for relay output |
240 V AC for relay output |
discrete output current |
2000 mA for relay output |
2000 mA for relay output |
Complementary |
Discrete I/O number |
8 |
24 |
current consumption |
5 mA at 5 V DC via bus connector (at state off) |
5 mA at 5 V DC via bus connector (at state off) |
0 mA at 24 V DC via bus connector (at state on) |
0 mA at 24 V DC via bus connector (at state on) |
0 mA at 24 V DC via bus connector (at state off) |
0 mA at 24 V DC via bus connector (at state off) |
25 mA at 5 V DC via bus connector (at state on) |
65 mA at 5 V DC via bus connector (at state on) |
Discrete input voltage type |
DC |
DC |
voltage state 1 guaranteed |
15…28.8 V for input |
15…28.8 V for input |
current state 1 guaranteed |
>= 2.5 mA (input) |
>= 2.5 mA (input) |
voltage state 0 guaranteed |
0…5 V for input |
0…5 V for input |
current state 0 guaranteed |
<= 1 mA (input) |
<= 1 mA (input) |
input impedance |
3.4 kOhm |
3.4 kOhm |
response time |
4 ms (turn-on) |
4 ms (turn-on) |
4 ms (turn-off) |
4 ms (turn-off) |
Maximum current per output common |
0.291666667 |
0.291666667 |
mechanical durability |
20000000 cycles |
20000000 cycles |
minimum load |
10 mA at 5 V DC for relay output |
10 mA at 5 V DC for relay output |
local signalling |
1 LED per channel (green) for I/O state |
1 LED per channel (green) for I/O state |
electrical connection |
11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for inputs and outputs |
17 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs |
maximum cable distance between devices |
Unshielded cable: <30 m for regular input |
11 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for outputs |
insulation |
Between input and internal logic at 500 V AC |
Unshielded cable: <30 m for regular input |
Non-insulated between inputs |
Between input and internal logic at 500 V AC |
Between input groups and output groups at 1500 V AC |
Non-insulated between inputs |
Between open contact at 750 V AC |
Between input groups and output groups at 1500 V AC |
Between output and internal logic at 500 V AC |
Between open contact at 750 V AC |
Non-insulated between outputs |
Between output and internal logic at 500 V AC |
Marking |
CE |
Non-insulated between outputs |
mounting support |
Top hat type TH35-15 rail conforming to IEC 60715 |
CE |
Top hat type TH35-7.5 rail conforming to IEC 60715 |
Top hat type TH35-15 rail conforming to IEC 60715 |
plate or panel with fixing kit |
Top hat type TH35-7.5 rail conforming to IEC 60715 |
plate or panel with fixing kit |
Height |
90 mm |
90 mm |
Depth |
84.6 mm |
84.6 mm |
Width |
27.4 mm |
42.9 mm |
Net weight |
0.95 kg |
N/A |
Environment |
Standards |
EN/IEC 61131-2 |
EN/IEC 61131-2 |
EN/IEC 61010-2-201 |
EN/IEC 61010-2-201 |
Product certifications |
C-Tick |
CULus |
cULus |
C-Tick |
resistance to electrostatic discharge |
8 kV in air conforming to EN/IEC 61000-4-2 |
8 kV in air conforming to EN/IEC 61000-4-2 |
4 kV on contact conforming to EN/IEC 61000-4-2 |
4 kV on contact conforming to EN/IEC 61000-4-2 |
resistance to electromagnetic fields |
10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3 |
10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3 |
3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3 |
3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3 |
1 V/m 2 GHz…3 GHz conforming to EN/IEC 61000-4-3 |
1 V/m 2 GHz…3 GHz conforming to EN/IEC 61000-4-3 |
resistance to magnetic fields |
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
resistance to fast transients |
1 kV for I/O conforming to EN/IEC 61000-4-4 |
1 kV for I/O conforming to EN/IEC 61000-4-4 |
2 kV for relay output conforming to EN/IEC 61000-4-4 |
2 kV for relay output conforming to EN/IEC 61000-4-4 |
surge withstand |
2 kV output common mode conforming to EN/IEC 61000-4-5 |
2 kV output common mode conforming to EN/IEC 61000-4-5 |
1 kV input common mode conforming to EN/IEC 61000-4-5 |
1 kV input common mode conforming to EN/IEC 61000-4-5 |
resistance to conducted disturbances |
10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6 |
10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6 |
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
electromagnetic emission |
Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 |
Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 |
Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011 |
Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011 |
ambient air temperature for operation |
-10…35 °C vertical installation |
-10…35 °C vertical installation |
-10…55 °C horizontal installation |
-10…55 °C horizontal installation |
Ambient air temperature for storage |
-25…70 °C |
-25…70 °C |
relative humidity |
10…95 %, without condensation (in operation) |
10…95 %, without condensation (in operation) |
10…95 %, without condensation (in storage) |
10…95 %, without condensation (in storage) |
IP degree of protection |
IP20 with protective cover in place |
IP20 with protective cover in place |
Pollution degree |
2 |
2 |
Operating altitude |
0…2000 m |
0…2000 m |
Storage altitude |
0…3000 m |
0…3000 m |
vibration resistance |
3.5 mm at 5…8.4 Hz on DIN rail |
3.5 mm at 5…8.4 Hz on DIN rail |
3 gn at 8.4…150 Hz on DIN rail |
3 gn at 8.4…150 Hz on DIN rail |
3.5 mm at 5…8.4 Hz on panel |
3.5 mm at 5…8.4 Hz on panel |
3 gn at 8.4…150 Hz on panel |
3 gn at 8.4…150 Hz on panel |
shock resistance |
15 gn for 11 ms |
15 gn for 11 ms |
Packing Units |
Unit Type of Package 1 |
PCE |
PCE |
Number of Units in Package 1 |
1 |
1 |
Package 1 Height |
7.5 cm |
7.551 cm |
Package 1 Width |
12.5 cm |
10.686 cm |
Package 1 Length |
10.5 cm |
12.849 cm |
Package 1 Weight |
230.0 g |
281.0 g |
Unit Type of Package 2 |
S04 |
CAR |
Number of Units in Package 2 |
42 |
42 |
Package 2 Height |
30.0 cm |
30.6 cm |
Package 2 Width |
40.0 cm |
40.1 cm |
Package 2 Length |
60.0 cm |
57.6 cm |
Package 2 Weight |
10.643 kg |
12.61 kg |