This communication module is proposed as an option Modicon M241/251 controllers. This module provides an Ethernet connection with 4 ports on controllers without embedded Ethernet. It also provides a second Ethernet connection with 4 ports on controllers with embedded Ethernet (except on TM241CEC24x). It is equipped with 4 x RJ45 connectors (10/100 Mbps, MDI/MDIX).

Specifications

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Part Number TM4ES4
product or component type Ethernet unmanaged switch
Complementary
range compatibility Modicon M251
Modicon M241
product compatibility Modicon M241 logic controller
Modicon M251 logic controller
current consumption 360 mA at 5 V DC for communication bus
integrated connection type Ethernet: 4 RJ45 connector
transmission rate 10/100 Mbit/s
port Ethernet 10BASE-T/100BASE-TX – 4 port(s) copper cable
web services Web server
communication service Modbus TCP server
Modbus TCP slave device
FTP
NGVL
Monitoring
IEC VAR ACCESS
Programming
SNMP
Modbus TCP client
Downloading
Updating firmware
Ethernet/IP slave device
DHCP client
maximum number of connections 8 Modbus server
16 Ethernet/IP device
communication port protocol Ethernet IP/Modbus TCP
TCP (Transmission Control Protocol)
UDP (User Datagram Protocol)
SNMP
redundancy No
local signalling 1 LED (green) for PWR
1 LED per channel (green/yellow) for Ethernet link
1 LED per channel (green) for Ethernet port activity
electrical connection RJ45 4 connectors for connecting Ethernet network
Screw connector terminal for connecting the functional ground
Marking CE
surge withstand 1 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5
2 kV relay output common mode conforming to EN/IEC 61000-4-5
1 kV I/O common mode conforming to EN/IEC 61000-4-5
1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5
1 kV relay output differential mode conforming to EN/IEC 61000-4-5
0.5 kV I/O differential mode conforming to EN/IEC 61000-4-5
mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
width 25 mm
Height 90 mm
Depth 90 mm
Net weight 0.125 kg
Environment
Standards UL 508
EN/IEC 61131-2
product certifications CULus
C-Tick
resistance to electrostatic discharge 8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to Marine specification (LR, ABS, DNV, GL)
6 kV on contact conforming to Marine specification (LR, ABS, DNV, GL)
resistance to electromagnetic fields 10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2…2.7 GHz conforming to EN/IEC 61000-4-3
resistance to fast transients 2 kV (power lines) conforming to EN/IEC 61000-4-4
2 kV (relay output) conforming to EN/IEC 61000-4-4
1.5 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (Ethernet line) conforming to EN/IEC 61000-4-4
1 kV (serial link) conforming to EN/IEC 61000-4-4
resistance to conducted disturbances 10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6
3 V 0.1…80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
electromagnetic emission Conducted emissions – test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011
Conducted emissions – test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011
Conducted emissions – test level: 120…69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011
Conducted emissions – test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011
Radiated emissions – test level: 40 dBμV/m QP class A at 30…230 MHz conforming to EN/IEC 55011
Radiated emissions – test level: 60…54 dBμV/m QP at 30…100 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions – test level: 24 dBμV/m QP at 156…165 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Conducted emissions – test level: 79…63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011
Radiated emissions – test level: 47 dBμV/m QP class A at 230…1000 MHz conforming to EN/IEC 55011
Radiated emissions – test level: 80…50 dμV/m QP at 150…30000 kHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions – test level: 54 dBμV/m QP at 100…2000 MHz conforming to Marine specification (LR, ABS, DNV, GL)
ambient air temperature for operation -10…55 °C horizontal installation
-10…50 °C vertical installation
Ambient air temperature for storage -25…70 °C
relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protection IP20 with protective cover in place
pollution degree 2
Operating altitude 0…2000 m
Storage altitude 0…3000 m
vibration resistance 1 mm at 5…13.2 Hz on symmetrical rail
3 gn at 8.7…150 Hz on symmetrical rail
1 mm at 5…13.2 Hz on panel mounting
0.7 gn at 13.2…100 Hz on panel mounting
shock resistance 15 gn for 11 ms
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 5.635 cm
Package 1 Width 11.532 cm
Package 1 Length 17.033 cm
Package 1 Weight 210.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 20
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 5.04 k+B+A1:B112

[/fusion_table]

Weight 0.125 kg
Dimensions 9.0 × 2.5 × 9.0 cm