| General specifications |
| Switching function |
Normally open (NO) |
| Output type |
NPN |
| Rated operating distance |
40 mm |
| Installation |
non-flush |
| Output polarity |
DC |
| Assured operating distance |
0 … 32.4 mm |
| Actual operating distance |
36 … 44 mm |
| Reduction factor rAl |
0.3 |
| Reduction factor rCu |
0.28 |
| Reduction factor r304 |
0.75 |
| Reduction factor rBrass |
0.38 |
| Output type |
3-wire |
| Nominal ratings |
| Operating voltage |
10 … 30 V DC |
| Switching frequency |
0 … 180 Hz |
| Hysteresis |
typ. 5 % |
| Reverse polarity protection |
reverse polarity protected |
| Short-circuit protection |
pulsing |
| Voltage drop |
≤ 2 V |
| Operating current |
0 … 200 mA |
| Off-state current |
0 … 0.5 mA |
| No-load supply current |
≤ 20 mA |
| Time delay before availability |
80 ms |
| Operating voltage indicator |
LED, green |
| Switching state indicator |
LED, yellow |
| Functional safety related parameters |
| MTTFd |
1510 a |
| Mission Time (TM) |
20 a |
| Diagnostic Coverage (DC) |
0 % |
| Compliance with standards and directives |
| Standard conformity |
|
|
Standards |
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
| Approvals and certificates |
| Protection class |
II |
|
Rated insulation voltage |
253 V |
|
Rated impulse withstand voltage |
4000 V |
| UL approval |
cULus Listed, General Purpose |
| CCC approval |
CCC approval / marking not required for products rated ≤36 V |
| Ambient conditions |
| Ambient temperature |
-25 … 85 °C (-13 … 185 °F) |
| Storage temperature |
-40 … 85 °C (-40 … 185 °F) |
| Mechanical specifications |
| Connection type |
Connector plug M12 x 1 , 4-pin |
| Housing material |
PA |
| Sensing face |
PA |
| Degree of protection |
IP68 / IP69K |
| Cable |
|
|
Cable diameter |
3.3 mm ± 0.15 mm |