| General specifications |
| Switching function |
Normally closed (NC) |
| Output type |
NAMUR |
| Rated operating distance |
40 mm |
| Installation |
non-flush |
| Assured operating distance |
0 … 32.4 mm |
| Actual operating distance |
36 … 44 mm |
| Reduction factor rAl |
0.31 |
| Reduction factor rCu |
0.3 |
| Reduction factor r304 |
0.74 |
| Nominal ratings |
| Nominal voltage |
8.2 V (Ri approx. 1 kΩ) |
| Switching frequency |
0 … 150 Hz |
| Hysteresis |
typ. 5 % |
| Reverse polarity protection |
reverse polarity protected |
| Short-circuit protection |
yes |
| Current consumption |
|
|
Measuring plate not detected |
≥ 2.2 mA |
|
Measuring plate detected |
≤ 1 mA |
| Switching state indicator |
LED, yellow |
| Functional safety related parameters |
| Safety Integrity Level (SIL) |
SIL 2 |
| MTTFd |
1670 a |
| Mission Time (TM) |
20 a |
| Diagnostic Coverage (DC) |
0 % |
| Compliance with standards and directives |
| Standard conformity |
|
|
Standards |
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
| Approvals and certificates |
| IECEx approval |
|
|
Equipment protection level Ga |
IECEx PTB 11.0021X |
|
Equipment protection level Gb |
IECEx PTB 11.0021X |
|
Equipment protection level Da |
IECEx PTB 11.0021X |
|
Equipment protection level Dc (tc) |
IECEx TUR 21.0020X |
|
Equipment protection level Mb |
IECEx PTB 11.0021X |
| ATEX approval |
|
|
Equipment protection level Ga |
PTB 00 ATEX 2032 X |
|
Equipment protection level Gb |
PTB 00 ATEX 2032 X |
|
Equipment protection level Da |
PTB 00 ATEX 2032 X |
|
Equipment protection level Dc (tc) |
TÜV 20 ATEX 8526 X |
| Protection class |
II |
|
Rated insulation voltage |
253 V |
|
Rated impulse withstand voltage |
4000 V |
| UL approval |
|
|
Ordinary Location |
E87056 |
|
Hazardous Location |
E501628 |
|
Control drawing |
116-0451 |
| CCC approval |
|
|
Hazardous Location |
2020322315002302 |
| NEPSI approval |
|
|
NEPSI certificate |
GYJ16.1394X |
| CML approval |
on request |
| ANZEx |
19.3001X |
| Marine approval |
DNVGL TAA00001A5 |
| Ambient conditions |
| Ambient temperature |
-25 … 100 °C (-13 … 212 °F) |
| Storage temperature |
-40 … 100 °C (-40 … 212 °F) |
| Mechanical specifications |
| Connection type |
Connector plug |
| Housing material |
PA |
| Sensing face |
PA |
| Degree of protection |
IP69K |
| Connector |
|
|
Threading |
M12 x 1 |
|
Number of pins |
4 |
| Mass |
130 g |
| General information |
| Use in the hazardous area |
see instruction manuals |