| Main Information | 
| Part Number | C25H3 | 
| Product Series | ComPacT new generation | 
| product name | ComPacT NSX new generation | 
| product short name | NSX250H | 
| product type | Ontology | 
| Applications | Distribution protection | 
| number of poles | 3P | 
| Rated current [In] | 250 A at 40 °C | 
| Rated working voltage [Ue] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Grid type | AC | 
| grid frequency | 50/60Hz | 
| isolation function | Applies to TM-D | 
| use category | AC class | 
| [Icu] rated ultimate short-circuit breaking capacity | 85 kA at 240 V AC 50/60 Hz conforming to UL 508 | 
| 65 kA at 480 V AC 50/60 Hz conforming to UL 508 | 
| 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 15 kA at 600 V AC 50/60 Hz according to UL 508 | 
| Performance level | H 70 kA 415 V AC | 
| control type | Handle | 
| installation type | Fixed | 
| Additional Information | 
| Rated insulation voltage [Ui] | 800 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Rated impulse withstand voltage [Uimp] | 8 kV according to IEC 60947-2 | 
| [Ics] rated service short-circuit breaking capacity | 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | 
| 70 kA at 380/415 V AC 50 /60 Hz conforming to IEC 60947-2 | 
| Mechanical life | 20000 times according to IEC 60947-2 | 
| Electrical life | 10000 cycles of 440 V AC 50/60 Hz In conforming to IEC 60947-2 | 
| 10000 cycles of 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 | 
| 20000 cycles of 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 | 
| 5000 Secondary 690 V AC 50/60 Hz In conforming to IEC 60947-2 | 
| installation method | Chassis mount | 
| Connection method – top | Front connection | 
| Connection method – lower end | Front connection | 
| Phase spacing | 35 mm | 
| protection type | Unprotected | 
| width (W) | 105 mm | 
| High (H) | 161 mm | 
| Depth (D) | 86 mm | 
| Environment | 
| Standards compliant | TM-D | 
| UL 508 | 
| certified product | UL | 
| CSA | 
| pollution level | 3 Conforming to IEC 60664-1 | 
| IP protection class | IP40 complies with screwed | 
| IK protection class | IK07 conforms to IEC 62262 | 
| operating temperature | -25…70°C | 
| storage environment temperature | -50…85 °C | 
| Packaging Unit | 
| Unit Type of Package 1 | PCE | 
| Number of Units in Package 1 | 1 | 
| Package 1 Height | 14cm | 
| Package 1 Width | 11.2 cm | 
| Package 1 Length | 19.2 cm | 
| Package 1 Weight | 1.586kg | 
| Unit Type of Package 2 | S03 | 
| Number of Units in Package 2 | 7 | 
| Package 2 Height | 30cm | 
| Package 2 Width | 30cm | 
| Package 2 Length | 40cm | 
| Package 2 Weight | 11.48kg | 
| Unit Type of Package 3 | P12 | 
| Number of Units in Package 3 | 56 | 
| Package 3 Height | 42.5cm | 
| Package 3 Width | 80cm | 
| Package 3 Length | 120cm | 
| Package 3 Weight | 104kg | 
| Contract Warranty | 
| Warranty | 18 months |