| Power rating | Input voltage | Output voltage (VDC) | Output current | Built- in fan | Model with terminal block facing upward | 
|---|---|---|---|---|---|
| 100 W | 100 to 120 VAC, 200 to 240 VAC (allowable range: 85 to 132 VAC, 176 to 264 VAC, or 248 to 373 VDC (Select with the switch.) *2) | 5 V | 20 A | None | S8FS-C10005 | 
| 12 V | 8.5 A | S8FS-C10012 | |||
| 15 V | 7 A | S8FS-C10015 | |||
| 24 V | 4.5 A | S8FS-C10024 | |||
| 36 V | 2.8 A | S8FS-C10036 | |||
| 48 V | 2.3 A | S8FS-C10048 | 
Note: You can use brackets that are sold separately to mount the Power Supplies to DIN Rail. Refer to Mounting Brackets
(Order Separately) on Data Sheet.
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC.
*2. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 120 VAC, 200 to 240 VAC.
| Power rating | 100 W | |||||||
|---|---|---|---|---|---|---|---|---|
| Output voltage (VDC) | 5 V | 12 V | 15 V | 24 V | 36 V | 48 V | ||
| Efficiency * | 115 VAC input | 80% typ. | 82% typ. | 83% typ. | 85% typ. | 86% typ. | 87% typ. | |
| 230 VAC input | 81% typ. | 83% typ. | 84% typ. | 87% typ. | 87% typ. | 88% typ. | ||
| Input | Voltage range * | Single phase 85 to 132 VAC, 176 to 264 VAC, 248 to 373 VDC Select with the switch. (The L terminal for the DC input is the positive side and safety standards do not apply.) (Derating is required according to the input voltage. Refer to Derating Curves on Data Sheet.) | ||||||
| Frequency * | 50 /60 Hz (47 to 450 Hz) | |||||||
| Current * | 115 VAC input | 2 A typ. | ||||||
| 230 VAC input | 1.1 A typ. | |||||||
| Power factor | — | |||||||
| Leakage current | 115 VAC input | 0.35 mA | 0.35 mA | 0.35 mA | 0.35 mA | 0.40 mA | 0.40 mA | |
| 230 VAC input | 0.60 mA | 0.55 mA | 0.60 mA | 0.50 mA | 0.60 mA | 0.60 mA | ||
| Inrush current * (for a cold start at 25°) | 115 VAC input | 32 A typ. | ||||||
| 230 VAC input | 32 A typ. | |||||||
| Output | Rated Output Current | 20 A | 8.5 A | 7 A | 4.5 A | 2.8 A | 2.3 A | |
| Voltage adjustment range * | -10% to 10% (with V. ADJ) | |||||||
| Ripple & Noise voltage * | 100 to 120 VAC/200 to 240 VAC input | 70 mVp-p max. | 100 mVp-p max. | 70 mVp-p max. | 120 mVp-p max. | 90 mVp-p max. | 120 mVp-p max. | |
| Input variation influence * | 0.5% max. | |||||||
| Load variation influence * | 1.0% max. | |||||||
| Temperature variation influence | 100 to 120 VAC/200 to 240 VAC input | 0.03%/°C max. | ||||||
| Startup time * | 115 VAC input | 710 ms typ. | 440 ms typ. | 440 ms typ. | 430 ms typ. | 450 ms typ. | 430 ms typ. | |
| 230 VAC input | 720 ms typ. | 700 ms typ. | 720 ms typ. | 660 ms typ. | 690 ms typ. | 660 ms typ. | ||
| Hold time * | 115 VAC input | 23 ms typ. | 37 ms typ. | 36 ms typ. | 34 ms typ. | 36 ms typ. | 34 ms typ. | |
| 230 VAC input | 29 ms typ. | 40 ms typ. | 39 ms typ. | 39 ms typ. | 41 ms typ. | 38 ms typ. | ||
| Addi- tional func- tions | Overload protection | Yes, automatic reset | ||||||
| Overvoltage protection * | Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) | |||||||
| Overheat protection | No | |||||||
| Series operation | Yes (For up to 2 Power Supplies, external diodes are required.) | |||||||
| Parallel operation | No (However, backup operation is possible, external diodes are required.) | |||||||
| Remote sensing | No | |||||||
| Remote control | No | |||||||
| Output indicator | Yes (LED: Green) | |||||||
| Insula- tion | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA | ||||||
| 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA | ||||||||
| 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA | ||||||||
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC | |||||||
| Envi- ron- ment | Ambient operating temperature | -20 to 60°C (Derating is required according to the temperature. Refer to Derating Curves on Data Sheet.) (with no condensation or icing) | ||||||
| Storage temperature | -40 to 85°C (with no condensation or icing) | |||||||
| Ambient operating humidity | 20% to 90% (Storage humidity: 10% to 95%) | |||||||
| Vibration resistance | 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions 10 to 500 Hz, 0.26-mm half amplitude for 1 h each in X, Y, and Z directions | |||||||
| Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||||
| Relia- bility | MTBF | 135,000 hrs min. | ||||||
| Life expectancy * | 10 years min. | |||||||
| Con- struc- tion | Dimensions (W × H × D) | Refer to Dimensions. | ||||||
| Weight | 400 g max. | |||||||
| Cooling fan | No | |||||||
| Degree of protection | — | |||||||
| Stan- dards | Harmonic current emissions | Conforms to EN 61000-3-2, GB17625.1 | ||||||
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B, GB9254 | ||||||
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B, GB9254 | |||||||
| EMS | Conforms to EN 61204-3 high severity levels | |||||||
| Safety Standards | Approved Standards UL: cURus UL 62368-1 (Recognition) OVC II Pol2 CSA: cURus C22.2 No62368-1 CCC: GB4943 Conformed Standards EN: EN 62368-1 OVC II Pol2 RCM (EN61000-6-4) | |||||||
| Marine Standards | No | |||||||
| SEMI | No | |||||||
| Weight | N/A | 
|---|---|
| Model |