| Power rating | Input voltage | Output voltage (VDC) | Output current | Built- in fan | Model with terminal block facing forward | 
|---|---|---|---|---|---|
| 75 W | 100 to 240 VAC (allowable range: 85 to 264 VAC or 120 to 370 VDC *1) | 5 V | 14 A | None | S8FS-C07505J | 
| 12 V | 6.2 A | S8FS-C07512J | |||
| 15 V | 5 A | S8FS-C07515J | |||
| 24 V | 3.2 A | S8FS-C07524J | |||
| 48 V | 1.6 A | S8FS-C07548J | 
Note: You can use brackets that are sold separately to mount the Power Supplies to DIN Rail. Refer to Mounting Brackets
(Order Separately) on Data Sheet.
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC.
*2. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 120 VAC, 200 to 240 VAC.
| Power rating | 75 W | ||||||
|---|---|---|---|---|---|---|---|
| Output voltage (VDC) | 5 V | 12 V | 15 V | 24 V | 48 V | ||
| Efficiency * | 115 VAC input | 75% typ. | 83% typ. | 84% typ. | 87% typ. | 87% typ. | |
| 230 VAC input | 77% typ. | 83% typ. | 84% typ. | 87% typ. | 87% typ. | ||
| Input | Voltage range * | Single phase 85 to 264 VAC, 120 to 370 VDC (The L terminal for the DC input is the positive side and safety standards do not apply.) (Derating is required according to the input voltage. Refer to Derating Curves on Data Sheet.) | |||||
| Frequency * | 50 /60 Hz (47 to 450 Hz) | ||||||
| Current * | 115 VAC input | 1.4 A typ. | |||||
| 230 VAC input | 0.83 A typ. | ||||||
| Power factor | — | ||||||
| Leakage current | 115 VAC input | 0.25 mA | 0.25 mA | 0.25 mA | 0.25 mA | 0.25 mA | |
| 230 VAC input | 0.60 mA | 0.60 mA | 0.60 mA | 0.60 mA | 0.60 mA | ||
| Inrush current * (for a cold start at 25°) | 115 VAC input | 16 A typ. | |||||
| 230 VAC input | 32 A typ. | ||||||
| Output | Rated Output Current | 14 A | 6.2 A | 5 A | 3.2 A | 1.6 A | |
| Voltage adjustment range * | -10% to 10% (with V. ADJ) | ||||||
| Ripple & Noise voltage * | 100 to 240 VAC input | 80 mVp-p max. | 110 mVp-p max. | 90 mVp-p max. | 110 mVp-p max. | 140 mVp-p max. | |
| Input variation influence * | 0.5% max. | ||||||
| Load variation influence * | 1.0% max. | ||||||
| Temperature variation influence | 100 to 240 VAC input | 0.03%/°C max. | |||||
| Startup time * | 115 VAC input | 750 ms typ. | 720 ms typ. | 730 ms typ. | 750 ms typ. | 700 ms typ. | |
| 230 VAC input | 710 ms typ. | 680 ms typ. | 690 ms typ. | 690 ms typ. | 730 ms typ. | ||
| Hold time * | 115 VAC input | 12 ms typ. | 13 ms typ. | 13 ms typ. | 14 ms typ. | 15 ms typ. | |
| 230 VAC input | 75 ms typ. | 74 ms typ. | 74 ms typ. | 76 ms typ. | 78 ms typ. | ||
| Addi- tional func- tions | Overload protection | Yes, automatic reset | |||||
| Overvoltage protection * | Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) | ||||||
| Overheat protection | No | ||||||
| Series operation | Yes (For up to 2 Power Supplies, external diodes are required.) | ||||||
| Parallel operation | No (However, backup operation is possible, external diodes are required.) | ||||||
| Remote sensing | No | ||||||
| Remote control | No | ||||||
| Output indicator | Yes (LED: Green) | ||||||
| Insula- tion | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA | |||||
| 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA | |||||||
| 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA | |||||||
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC | ||||||
| Envi- ron- ment | Ambient operating temperature | -20 to 60°C (Derating is required according to the temperature. Refer to Derating Curves on Data Sheet.) (with no condensation or icing) | |||||
| Storage temperature | -40 to 85°C (with no condensation or icing) | ||||||
| Ambient operating humidity | 20% to 90% (Storage humidity: 10% to 95%) | ||||||
| Vibration resistance | 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions 10 to 500 Hz, 0.26-mm half amplitude for 1 h each in X, Y, and Z directions | ||||||
| Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||||
| Relia- bility | MTBF | 135,000 hrs min. | |||||
| Life expectancy * | 10 years min. | ||||||
| Con- struc- tion | Dimensions (W × H × D) | Refer to Dimensions. | |||||
| Weight | 350 g max. | ||||||
| Cooling fan | No | ||||||
| Degree of protection | — | ||||||
| Stan- dards | Harmonic current emissions | Conforms to EN 61000-3-2, GB17625.1 | |||||
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B, GB9254 | |||||
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B, GB9254 | ||||||
| EMS | Conforms to EN 61204-3 high severity levels | ||||||
| Safety Standards | Approved Standards UL: cURus UL 62368-1 (Recognition) OVC II Pol2 CSA: cURus C22.2 No62368-1 CCC: GB4943 Conformed Standards EN: EN 62368-1 OVC II Pol2 RCM (EN61000-6-4) | ||||||
| Marine Standards | No | ||||||
| SEMI | No | ||||||
| Weight | N/A | 
|---|---|