$ 447.12
Model | |
product brand name | SENTRON |
product designation | Multimeter |
design of the product | basic |
product type designation | 7KM PA3220 |
Measurements | |
measuring procedure ● for voltage measurement ● for current measurement |
TRMS TRMS |
type of measured value detection | complete |
voltage curve | Sinusoidal or distorted |
measurable line frequency ● initial value 45 Hz ● full-scale value |
45 Hz 65 Hz |
operating mode for measured value detection automatic line frequency detection |
Yes |
operating mode for measured value detection ● set at 50 Hz ● set to 60 Hz |
No No |
Supply voltage | |
design of the power supply | Extra-low voltage power supply unit |
type of voltage of the supply voltage | DC |
supply voltage at DC | 24 … 60 V |
Degree of protection protection class | |
protection class IP on the front | IP65 |
Suitability | |
suitability for operation | Installation in stationary panels in closed rooms |
Product Functions | |
product function ● voltage measurement ● current measurement ● active power measurement ● reactive power measurement ● frequency measurement |
Yes Yes Yes Yes Yes |
Display and operation | |
design of the display | LCD |
height of the display | 54 mm |
width of the display | 72 mm |
color of the background of the display | white |
illuminance of display backlight adjustable | No |
time-controlled reduction of the illuminance of display backlight possible |
Yes |
display contrast adjustable | Yes |
national language on the display screen is supported | de, en, fr, spa, ita, por, tur, chi, pol |
number of keys | 4 |
Communication | |
transfer rate minimum | 10 000 kbit/s |
transfer rate maximum | 101 000 kbit/s |
number of interfaces according to Fast Ethernet | 2 |
type of electrical connection of the fast Ethernet interface | 2 x RJ45 |
protocol at the Ethernet interface is supported | MODBUS TCP |
Fault limits | |
reference condition for metering accuracy | In accordance with IEC61557-12, IEC62053-22 and IEC62053-23 |
formula for relative total measurement inaccuracy ● for measured variable voltage ● for measured variable current ● for measured variable active power ● for measured variable reactive power ● for measured variable output factor ● for measured variable active energy ● for measured variable reactive energy |
+/- 0.2 % +/- 0.2 % +/- 0.5 % +/- 1 % +/- 0,5 % Cl. 0.5 acc. to… IEC62053-22 Class 2 according to IEC61557-12 and/or IEC62053-23 |
Inputs Outputs | |
number of digital inputs | 2 |
type of electrical connection at the digital inputs | screw-type terminals |
operating conditions for digital inputs external voltage supply | Yes |
input voltage at digital input at DC maximum | 30 V |
input current at digital input ● initial value for signal<1>-recognition |
7 mA |
number of digital outputs | 2 |
type of switching output | bidirectional |
digital output version | switching or pulse output function |
operating voltage as output voltage at DC maximum permissible | 30 V |
type of electrical connection at the digital outputs | screw-type terminals |
output current ● at the digital outputs at DC limited to 100 ms maximum |
130 mA |
internal resistance at the digital outputs | 55 Ω |
standard for pulse emitter | according to IEC62053-31 |
pulse duration ● initial value ● full-scale value |
30 ms 500 ms |
adjustable time period minimum | 10 ms |
switching frequency at digital output maximum | 17 Hz |
property of the output short-circuit proof | Yes |
Measuring inputs | |
measurable supply voltage between (PE)N and L at AC maximum rated value |
400 V |
measurable supply voltage between (PE)N and L at AC ● minimum ● maximum |
11.5 V 480 V |
measurable supply voltage between the line conductors at AC maximum rated value |
690 V |
voltage measuring range extension with external voltage transformers |
yes |
line conductors and neutral conductors internal resistance for voltage measurement |
1.5 MΩ |
measuring category for voltage measurement | CAT III |
measurable current ● 1 at AC rated value ● 2 at AC rated value |
1A 5A |
relative measurable current at AC ● minimum ● maximum |
1% 100% |
current measuring range extension with external current transformers |
Yes |
zero point suppression for current measurement | 0…10% |
apparent power consumption for current measurement ● with measuring range 5 A per phase |
0.3 VA |
measuring category for current measurement | CATIII |
Connections | |
type of electrical connection ● at the measurement inputs for voltage ● at the measurement inputs for current |
screw-type terminals screw-type terminals |
Mechanical Design | |
fastening method DIN-rail mounting | No |
size of Power Monitoring Device | size 96 |
height | 96 mm |
width | 96 mm |
depth | 56 mm |
installation depth | 51 mm |
net weight | 325 g |
mounting position | vertical |
Environmental conditions | |
ambient temperature during operation ● minimum ● maximum |
-25 °C 55 °C |
ambient temperature during storage ● minimum ● maximum |
-25 °C 70 °C |
relative humidity at 25 °C without condensation during operation maximum |
75% |
installation altitude at height above sea level maximum | 2 000 m |
degree of pollution | 2 |
Weight | 0.425 kg |
---|---|
Dimensions | 9.6 × 5.8 × 9.6 cm |