Modern appliances often have quite different characteristics in terms of current consumption than earlier equipment due, for example, to the use of frequency converters in washing machines, or switched-mode power supply units in TVs, PCs or LED lights. All of this requires new protection strategies for electrical installations. This also includes appropriate residual current protection devices or residual current circuit breakers that will cut the current immediately and safely in the event of a fault.
Siemens Residual Current Protective Devices Product Specifications:
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Article Number | 5SU1354-6KK06 |
product brand name | SENTRON |
product designation | RCBO |
design of the product | Instantaneous |
General technical data | |
number of poles | 2 |
number of poles with protection | 1 |
design of pole | 1P+N |
tripping characteristic class | B |
mechanical service life (switching cycles) typical | 10 000 |
overvoltage category | III |
degree of pollution | 2 |
Voltage | |
type of voltage of the operating voltage | AC |
insulation voltage (Ui) rated value | 264 V |
surge voltage resistance rated value | 4 000 V |
surge current resistance at (8/20) µs | 1 kA |
Supply voltage | |
supply voltage | |
● at AC rated value | 230/240 V |
● for testing equipment minimum | 195 V |
operating frequency | 50 Hz |
supply voltage frequency rated value | 50 Hz |
Protection class | |
protection class IP | IP20, if the distribution board is installed, with connected conductors |
Switching capacity | |
breaking capacity short-circuit current (Icn) according to EN 61009-1 rated value | 10 kA |
switching capacity current | |
● according to EN 60898 rated value | 10 kA |
● according to IEC 60947-2 rated value | 35 kA |
rated residual switching capacity (IΔm) according to IEC 61009-1 | 10 kA |
energy limitation class | 3 |
Dissipation | |
power loss [W] | |
● for rated value of the current at AC in hot operating state per pole | 2.7 W |
● maximum | 5.4 W |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Article Number | 5SU1354-6KK10 |
product brand name | SENTRON |
product designation | RCBO |
design of the product | Instantaneous |
General technical data | |
number of poles | 2 |
number of poles with protection | 1 |
design of pole | 1P+N |
tripping characteristic class | B |
mechanical service life (switching cycles) typical | 10 000 |
overvoltage category | III |
degree of pollution | 2 |
Voltage | |
type of voltage of the operating voltage | AC |
insulation voltage (Ui) rated value | 264 V |
surge voltage resistance rated value | 4 000 V |
surge current resistance at (8/20) µs | 1 kA |
Supply voltage | |
supply voltage | |
● at AC rated value | 230/240 V |
● for testing equipment minimum | 195 V |
operating frequency | 50 Hz |
supply voltage frequency rated value | 50 Hz |
Protection class | |
protection class IP | IP20, if the distribution board is installed, with connected conductors |
Switching capacity | |
breaking capacity short-circuit current (Icn) according to EN 61009-1 rated value | 10 kA |
switching capacity current | |
● according to EN 60898 rated value | 10 kA |
● according to IEC 60947-2 rated value | 20 kA |
rated residual switching capacity (IΔm) according to IEC 61009-1 | 10 kA |
energy limitation class | 3 |
Dissipation | |
power loss [W] | |
● for rated value of the current at AC in hot operating state per pole | 1.8 W |
● maximum | 3.6 W |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Article Number | 5SU1354-6KK16 |
product brand name | SENTRON |
product designation | RCBO |
design of the product | Instantaneous |
General technical data | |
number of poles | 2 |
number of poles with protection | 1 |
design of pole | 1P+N |
tripping characteristic class | C |
mechanical service life (switching cycles) typical | 10 000 |
overvoltage category | III |
degree of pollution | 2 |
Voltage | |
type of voltage of the operating voltage | AC |
insulation voltage (Ui) rated value | 264 V |
surge voltage resistance rated value | 4 000 V |
surge current resistance at (8/20) µs | 1 kA |
Supply voltage | |
supply voltage | |
● at AC rated value | 230/240 V |
● for testing equipment minimum | 195 V |
operating frequency | 50 Hz |
supply voltage frequency rated value | 50 Hz |
Protection class | |
protection class IP | IP20, if the distribution board is installed, with connected conductors |
Switching capacity | |
breaking capacity short-circuit current (Icn) according to EN 61009-1 rated value | 10 kA |
switching capacity current | |
● according to EN 60898 rated value | 10 kA |
● according to IEC 60947-2 rated value | 20 kA |
rated residual switching capacity (IΔm) according to IEC 61009-1 | 10 kA |
energy limitation class | 3 |
Dissipation | |
power loss [W] | |
● for rated value of the current at AC in hot operating state per pole | 3 W |
● maximum | 6 W |
[/fusion_table]
Weight | N/A |
---|---|
Dimensions | N/A |