| Article Number |
5SU1353-1KK16 |
| product brand name |
SENTRON |
| product designation |
RCBO |
| design of the product |
Instantaneous |
| General technical data |
|
| number of poles |
2 |
| number of poles with protection |
1 |
| design of pole |
1P+N |
| tripping characteristic class |
C |
| mechanical service life (switching cycles) typical |
10 000 |
| overvoltage category |
III |
| degree of pollution |
2 |
| Voltage |
|
| type of voltage of the operating voltage |
AC |
| insulation voltage (Ui) rated value |
264 V |
| surge voltage resistance rated value |
4 000 V |
| surge current resistance at (8/20) µs |
1 kA |
| Supply voltage |
|
| supply voltage |
|
| ● at AC rated value |
230/240 V |
| ● for testing equipment minimum |
195 V |
| operating frequency |
50 Hz |
| supply voltage frequency rated value |
50 Hz |
| Protection class |
|
| protection class IP |
IP20, if the distribution board is installed, with connected conductors |
| Switching capacity |
|
| breaking capacity short-circuit current (Icn) according to EN 61009-1 rated value |
4.5 kA |
| switching capacity current |
|
| ● according to EN 60898 rated value |
4.5 kA |
| ● according to IEC 60947-2 rated value |
15 kA |
| rated residual switching capacity (IΔm) according to IEC 61009-1 |
4.5 kA |
| energy limitation class |
3 |
| Dissipation |
|
| power loss [W] |
|
| ● for rated value of the current at AC in hot operating state per pole |
2.8 W |
| ● maximum |
5.6 W |