| Model |
|
| product number |
3LD2064-1GP51 |
| product brand name |
SENTRON |
| product designation |
3LD Switch disconnector |
| design of the product |
Main switch |
| display version for switch position indicator manual operation |
1 ON – 0 OFF |
| type of switch |
Molded-plastic enclosure for metric threaded joint |
| design of the actuating element |
Short rotary knob |
| color of the actuating element |
black |
| design of handle |
rotary operating mechanism, black |
| type of the driving mechanism motor drive |
No |
| General technical data |
|
| number of poles |
3 |
| number of poles note |
N |
| size of switch disconnector |
1 |
| mechanical service life (operating cycles) typical |
100 000 |
| electrical endurance (operating cycles) |
6 000 |
| ● at AC-23 A at 690 V |
| operating frequency maximum |
50 1/h |
| degree of pollution |
3 |
| Voltage |
|
| insulation voltage rated value |
690 V |
| surge voltage resistance rated value |
6 kV |
| operating voltage |
|
| ● at AC rated value |
690 V |
| operating frequency rated value |
|
| ● minimum |
50 Hz |
| ● maximum |
60 Hz |
| Protection class |
|
| protection class IP |
IP65 |
| degree of protection NEMA rating |
1, 4X, 12 |
| protection class IP on the front |
IP65 |
| Dissipation |
|
| power loss [W] for rated value of the current at AC in hot operating state per pole |
0.5 W |
| Current |
|
| operational current rated value |
16 A |
| operational current |
|
| ● at 40 °C rated value |
16 A |
| ● at 45 °C rated value |
16 A |
| ● at 50 °C rated value |
16 A |
| ● at 55 °C rated value |
16 A |
| ● at AC °C rated value |
16 A |
| Main circuit |
|
| operational current |
|
| ● at AC-21 at 690 V rated value |
16 A |
| ● at AC-21 A at 240 V rated value |
16 A |
| ● at AC-21 A at 400 V rated value |
16 A |
| ● at AC-21 A at 440 V rated value |
16 A |
| ● at AC-23 A at 400 V rated value |
16 A |
| operating power |
|
| ● at AC-23 A at 240 V rated value |
4 kW |
| ● at AC-23 A at 400 V rated value |
8 kW |
| ● at AC-23 A at 440 V rated value |
7.5 kW |
| ● at AC-23 A at 690 V rated value |
8 kW |
| ● at AC-3 at 240 V rated value |
3 kW |
| ● at AC-3 at 400 V rated value |
6 kW |
| ● at AC-3 at 690 V rated value |
5.5 kW |
| Auxiliary circuit |
|
| number of CO contacts for auxiliary contacts |
0 |
| number of NC contacts for auxiliary contacts |
1 |
| number of NO contacts for auxiliary contacts |
1 |
| operating voltage of auxiliary contacts at AC maximum |
500 V |
| continuous current of the auxiliary contact rated value |
10A |
| insulation voltage of the auxiliary switch rated value |
500 V |
| Suitability |
|
| suitability for use |
|
| ● main switch |
Yes |
| ● switch disconnector |
Yes |
| ● EMERGENCY OFF switch |
No |
| ● safety switch |
Yes |
| ● maintenance/repair switch |
Yes |
| Product details |
|
| product feature can be locked into OFF position |
Yes |
| accessories |
|
| product extension optional |
|
| ● motor drive |
No |
| ● voltage trigger |
No |
| number of connectable NC contacts for auxiliary contacts attachable maximum |
2 |
| number of connectable NO contacts for auxiliary contacts attachable maximum |
3 |
| number of connectable CO contacts for auxiliary contacts attachable maximum |
0 |
| number of bracket locks maximum |
3 |
| hasp thickness of the bracket locks |
4 … 8 mm |
| Short circuit |
|
| conditional short-circuit current with line-side fuse protection |
|
| ● at 690 V by gG fuse rated value |
50 kA |
| let-through current with closed switch |
|
| ● at 240 V for combination switch + gG fuse maximum |
3 kA |
| ● at 440 V for combination switch + gG fuse maximum |
3 kA |
| ● at 690 V for combination switch + gG fuse maximum permissible |
3 kA |
| I2t value with closed switch |
|
| ● at 240 V for combination switch + gG fuse maximum |
2.5 kA2.s |
| ● at 440 V for combination switch + gG fuse maximum |
2.5 kA2.s |
| ● at 690 V for combination switch + gG fuse maximum |
3 kA2.s |
| design of the fuse link |
|
| ● for short-circuit protection of the main circuit required |
fuse gL/gG: 20 A |
| ● for short-circuit protection of the auxiliary switch required |
fuse gL/gG: 10 A |
| operational current of upstream fuse rated value |
20 A |
| according UL |
|
| operational current at AC according to UL 508/UL 609474-1 rated value |
16 A |
| operating voltage at AC at 50/60 Hz according to UL 508/UL 60947-4-1 rated value |
600 V |
| active power [hp] at AC at 480 V according to UL 508/UL 60947-4-1 rated value |
7.5 |
| active power [hp] at AC at 600 V according to UL 508/UL 60947-4-1 rated value |
10 |
| short-time withstand current (SCCR) at 600 V according to UL 508/UL 60947-4-1 |
5 kA |
| continuous current of upstream fuse according to UL rated value |
50 A |
| type of fuse according to UL |
RK5 |
| Connections |
|
| AWG number as coded connectable conductor cross section solid |
|
| ● maximum |
10 |
| ● minimum |
18 |
| type of connectable conductor cross-sections for copper conductor |
|
| ● solid |
1x (1…6mm²) |
| ● finely stranded with core end processing |
1x (1…4mm²) |
| ● stranded |
1x (1..6mm²) |
| type of connectable conductor cross-sections for auxiliary contacts |
|
| ● solid |
lateral auxiliary switch 2x (0,75 … 2,5mm²), 1x 4mm²; front auxiliary switch 1x (0,75 … 2,5mm²) |
| ● finely stranded with core end processing |
lateral auxiliary switch 2x (0,75 … 1,5mm²), 1x 2,5mm²; front auxiliary switch 1x 2,5mm² |
| ● stranded |
lateral auxiliary switch 2x (0,75 … 2,5mm²), 1x 4mm²; front auxiliary switch 1x (0,75 … 2,5mm²) |
| type of electrical connection |
|
| ● for main current circuit |
box terminal |
| ● for auxiliary contacts |
connection terminals |
| Mechanical Design |
|
| height |
152 mm |
| width |
100 mm |
| depth |
117 mm |
| type of device |
fixed mounting |
| fastening method |
Complete unit in enclosure |
| fastening method |
|
| ● 4-hole front mounting |
No |
| ● front mounting with central attachment |
Yes |
| ● rail mounting |
No |
| net weight |
455 g |
| Environmental conditions |
|
| ambient temperature during operation |
-25 °C |
| ● minimum |
| ● maximum |
55 °C |
| ambient temperature during storage |
-25 °C |
| ● minimum |
| ● maximum |
55 °C |