ET 200AL, IM 157-1 PN |
General information |
|
Product type designation |
IM 157-1 PN |
HW functional status |
FS02 |
Firmware version |
V1.0.x |
Vendor identification (VendorID) |
002AH |
Product function |
|
● I&M data |
Yes; I&M0 to I&M4 |
Engineering with |
|
● STEP 7 TIA Portal configurable/integrated from version |
STEP 7 V13 SP1 or higher |
● STEP 7 configurable/integrated from version |
From V5.5 SP4 Hotfix 3 |
● PROFINET from GSD version/GSD revision |
GSDML V2.3.1 |
Configuration control |
|
via dataset |
Yes |
Supply voltage |
|
power supply according to NEC Class 2 required |
No |
Load voltage 1L+ |
|
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
● Reverse polarity protection |
Yes; against destruction |
Input current |
|
Current consumption (rated value) |
100 mA |
from load voltage 1L+ (unswitched voltage) |
4 A; Maximum value |
from load voltage 2L+, max. |
4 A; Maximum value |
Power loss |
|
Power loss, typ. |
2.9 W |
Address area |
|
Address space per station |
|
● Address space per station, max. |
1 430 byte |
Interfaces |
|
Number of PROFINET interfaces |
1 |
1. Interface |
|
Interface type |
PROFINET |
Interface types |
|
● M12 port |
Yes; 2x M12 D-coded |
● integrated switch |
Yes |
Protocols |
|
● PROFINET IO Device |
Yes |
● Open IE communication |
Yes |
Interface types |
|
M12 port |
|
● Transmission procedure |
PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
● 10 Mbps |
Yes; for Ethernet services |
● 100 Mbps |
Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
● Autonegotiation |
Yes |
● Autocrossing |
Yes |
Protocols |
|
PROFINET IO Device |
|
Services |
|
— IRT |
Yes; 250 µs, 500 µs, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms |
— PROFIenergy |
Yes |
— Shared device |
Yes |
— Number of IO Controllers with shared device, max. |
4 |
Redundancy mode |
|
Media redundancy |
|
— MRP |
Yes |
— MRPD |
Yes |
Open IE communication |
|
● TCP/IP |
Yes |
● SNMP |
Yes |
● LLDP |
Yes |
Interrupts/diagnostics/status information |
|
Diagnostics function |
Yes |
Alarms |
|
● Diagnostic alarm |
Yes |
Diagnostics indication LED |
|
● RUN LED |
Yes; green LED |
● ERROR LED |
Yes; red LED |
● MAINT LED |
Yes; Yellow LED |
● Connection display LINK TX/RX |
Yes; 2x green LED |
Potential separation |
|
between the load voltages |
Yes |
between PROFINET and all other circuits |
Yes |
Isolation |
|
Isolation tested with |
707 V DC (type test) |
Degree and class of protection |
|
IP degree of protection |
IP65/67 |
Standards, approvals, certificates |
|
Suitable for safety-related tripping of standard modules |
Yes; From FS01 |
Highest safety class achievable for safety-related tripping of standard modules |
|
● Performance level according to ISO 13849-1 |
PL d |
● Category according to ISO 13849-1 |
Cat. 3 |
● SIL acc. to IEC 62061 |
SIL 2 |
Ambient conditions |
|
Ambient temperature during operation |
|
● min. |
-25 °C |
● max. |
55 °C |
connection method / header |
|
Design of electrical connection for supply voltage |
M8, 4-pole |
ET-Connection |
|
● ET-Connection |
M8, 4-pin, shielded |
Dimensions |
|
Width |
45 mm |
Height |
159 mm |
Depth |
40 mm |
Weights |
|
Weight, approx. |
263 g |