SM331, 8AI, 0/4-20MA HART |
General information |
|
Product function |
|
● Isochronous mode |
No |
Supply voltage |
|
Load voltage L+ |
|
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
|
from load voltage L+ (without load), max. |
20 mA |
from backplane bus 5 V DC, max. |
120 mA |
output voltage / header |
|
supply voltage of the transmitters / header |
|
● product function / supply voltage for transmitters |
Yes |
● supply voltage / of the transmitters / at DC / rated value |
24 V |
● product feature / of the supply voltage for transmitters / short-circuit proof |
Yes |
● supply current / from supply voltage for transmitter / maximum |
60 mA |
Power loss |
|
Power loss, typ. |
1.5 W |
Analog inputs |
|
Number of analog inputs |
8 |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges (rated values), currents |
|
● 0 to 20 mA |
Yes |
— Input resistance (0 to 20 mA) |
140 Ω |
● -20 mA to +20 mA |
|
— Input resistance (-20 mA to +20 mA) |
140 Ω |
● 4 mA to 20 mA |
|
— Input resistance (4 mA to 20 mA) |
140 Ω |
Cable length |
|
● shielded, max. |
800 m |
Analog value generation for the inputs |
|
Measurement principle |
Sigma Delta |
Integration and conversion time/resolution per channel |
|
● Resolution with overrange (bit including sign), max. |
16 bit |
● Integration time, parameterizable |
Yes |
● Integration time (ms) |
20 ms at 50 Hz; 16.6 ms at 60 Hz; 100 ms at 100 Hz |
● Basic conversion time, including integration time (ms) |
55 ms @ 60 Hz, 65 ms @ 50 Hz, 305 ms @ 100 Hz |
● Interference voltage suppression for interference frequency f1 in Hz |
10 / 50 / 60 Hz |
Smoothing of measured values |
|
● parameterizable |
Yes |
● Step: None |
Yes |
● Step: low |
Yes |
● Step: Medium |
Yes |
● Step: High |
Yes |
Encoder |
|
Connection of signal encoders |
|
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
Errors/accuracies |
|
Operational error limit in overall temperature range |
|
● Current, relative to input range, (+/-) |
0.15 % |
Basic error limit (operational limit at 25 °C) |
|
● Current, relative to input range, (+/-) |
0.1 % |
Interrupts/diagnostics/status information |
|
Diagnostics function |
Yes |
Alarms |
|
● Diagnostic alarm |
Yes |
● Limit value alarm |
Yes |
Diagnostics indication LED |
|
● Group error SF (red) |
Yes |
● Channel fault indicator F (red) |
Yes |
Potential separation |
|
Potential separation analog inputs |
|
● between the channels |
No |
● between the channels and backplane bus |
Yes |
Isolation |
|
Isolation tested with |
500 V DC |
Degree and class of protection |
|
IP degree of protection |
IP20 |
connection method / header |
|
required front connector |
20-pin |
Dimensions |
|
Width |
40 mm |
Height |
125 mm |
Depth |
117 mm |
Weights |
|
Weight, approx. |
205 g |