| Article number |
6ES7155-5BA00-0AB0 |
|
ET 200MP, IM155-5 DP ST |
| General information |
|
| Product type designation |
IM 155-5 DP ST |
| HW functional status |
From FS01 |
| Firmware version |
V2.0.0 |
| Vendor identification (VendorID) |
81AAh |
| Product function |
|
| ● I&M data |
Yes; I&M0 to I&M3 |
| ● Module swapping during operation (hot swapping) |
No |
| ● Isochronous mode |
No |
| Engineering with |
|
| ● STEP 7 TIA Portal configurable/integrated from version |
V13 / V13 |
| ● STEP 7 configurable/integrated from version |
V5.5 SP3 / – |
| ● PROFIBUS from GSD version/GSD revision |
V1.0 / V5.1 |
| Configuration control |
|
| via user data |
No |
| via dataset |
No |
| Supply voltage |
|
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
19.2 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes |
| Short-circuit protection |
Yes |
| Mains buffering |
|
| ● Mains/voltage failure stored energy time |
5 ms |
| Input current |
|
| Current consumption (rated value) |
0.2 A; at 24 V DC and without load |
| Current consumption, max. |
1.2 A; at 20.4 V DC and max. load |
| Inrush current, max. |
4 A |
| I²t |
0.09 A²·s |
| from interface 5 V DC, max. |
80 mA |
| Power |
|
| Infeed power to the backplane bus |
14 W |
| Power loss |
|
| Power loss, typ. |
4 W |
| Address area |
|
| Address space per module |
|
| ● Address space per module, max. |
32 byte; per input / output |
| Address space per station |
|
| ● Address space per station, max. |
244 byte; per input / output |
| Hardware configuration |
|
| Integrated power supply |
Yes |
| System power supply can be plugged in to left of IM |
No |
| Number of permissible power segments |
1 |
| Rack |
|
| ● Modules per rack, max. |
12; I/O modules |
| Interfaces |
|
| Number of PROFIBUS interfaces |
1 |
| 1. Interface |
|
| Interface types |
|
| ● RS 485 |
Yes |
| Protocols |
|
| ● PROFIBUS DP slave |
Yes |
| Interface types |
|
| RS 485 |
|
| ● Transmission rate, max. |
12 Mbit/s |
| Protocols |
|
| Open IE communication |
|
| ● TCP/IP |
No |
| PROFIBUS DP |
|
| Services |
|
| — SYNC capability |
Yes |
| — FREEZE capability |
Yes |
| — DPV1 |
Yes |
| Interrupts/diagnostics/status information |
|
| Status indicator |
Yes |
| Alarms |
Yes |
| Diagnostics function |
Yes |
| Diagnostics indication LED |
|
| ● RUN LED |
Yes; green LED |
| ● ERROR LED |
Yes; red LED |
| ● MAINT LED |
Yes; Yellow LED |
| ● Connection display DP |
Yes; green LED |
| Potential separation |
|
| between backplane bus and electronics |
No |
| between PROFIBUS DP and all other circuit components |
Yes |
| between supply and all other circuits |
No |
| Isolation |
|
| Isolation tested with |
707 V DC (type test) |
| Ambient conditions |
|
| Ambient temperature during operation |
|
| ● horizontal installation, min. |
-25 °C; from FS04 |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
-25 °C; from FS04 |
| ● vertical installation, max. |
40 °C |
| Altitude during operation relating to sea level |
|
| ● Installation altitude above sea level, max. |
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| connection method / header |
|
| ET-Connection |
|
| ● via BU/BA Send |
No |
| Dimensions |
|
| Width |
35 mm |
| Height |
147 mm |
| Depth |
129 mm |
| Weights |
|
| Weight, approx. |
360 g |