The intelligent interface module IM 154-8 F PN/DP CPU features integrated PLC functionality. The functions included correspond to those of the S7-300 CPU 315F PN/DP.
The IM 154-8 F PN/DP CPU can be used simultaneously as an IO Controller and as an I-Device on PROFINET via the integral PROFINET interface.
| Article number | 6ES7154-8FB01-0AB0 | 6ES7154-8FX00-0AB0 |
| ET 200pro: IM 154-8F PN/DP CPU, 512KB | ET 200pro: IM 154-8FX PN/DP CPU, 1,5MB | |
| General information | ||
| HW functional status | 1 | 1 |
| Firmware version | V3.2 | V3.2 |
| Product function | ||
| ● Isochronous mode | Yes; Via PROFIBUS DP or PROFINET interface | Yes; Via PROFIBUS DP or PROFINET interface |
| Engineering with | ||
| ● Programming package | STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4 | As of STEP 7 V5.5 with HSP 222 + Distributed Safety V5.4 SP4 |
| Supply voltage | ||
| Rated value (DC) | 24 V | 24 V |
| external protection for power supply lines (recommendation) | MCB 24 V DC / 16 A with tripping characteristic Type B and C (see ET 200pro manual) | MCB 24 V DC / 16 A with tripping characteristic Type B and C (see ET 200pro manual) |
| Load voltage L+ | ||
| ● Rated value (DC) | 24 V | 24 V |
| ● permissible range, lower limit (DC) | 20.4 V | 20.4 V |
| ● permissible range, upper limit (DC) | 28.8 V | 28.8 V |
| ● Reverse polarity protection | Yes | Yes |
| Input current | ||
| Current consumption, typ. | 350 mA | 350 mA |
| Current consumption (in no-load operation), typ. | 250 mA; Typical, current consumption for CPU in STOP state | 250 mA; Typical, current consumption for CPU in STOP state |
| Inrush current, typ. | 2 A | 2 A |
| I²t | 0.25 A²·s; Typical | 0.25 A²·s; Typical |
| Power loss | ||
| Power loss, typ. | 8.5 W | 8.5 W |
| Memory | ||
| Work memory | ||
| ● integrated | 512 kbyte | 1 536 kbyte |
| ● expandable | No | No |
| Load memory | ||
| ● Plug-in (MMC) | Yes | Yes |
| ● Plug-in (MMC), max. | 8 Mbyte | 8 Mbyte |
| ● Data management on MMC (after last programming), min. | 10 y | 10 y |
| Backup | ||
| ● present | Yes; Guaranteed by MMC (maintenance-free) | Yes; Guaranteed by MMC (maintenance-free) |
| ● without battery | Yes; Program and data | Yes; Program and data |
| CPU processing times | ||
| for bit operations, typ. | 0.05 µs | 0.025 µs |
| for word operations, typ. | 0.09 µs | 0.03 µs |
| for fixed point arithmetic, typ. | 0.12 µs | 0.04 µs |
| for floating point arithmetic, typ. | 0.45 µs | 0.16 µs |
| CPU-blocks | ||
| Number of blocks (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
| DB | ||
| ● Number, max. | 1 024; Number range: 1 to 16000 | 1 024; Number range: 1 to 16000 |
| ● Size, max. | 64 kbyte | 64 kbyte |
| FB | ||
| ● Number, max. | 1 024; Number range: 0 to 7999 | 1 024; Number range: 0 to 7999 |
| ● Size, max. | 64 kbyte | 64 kbyte |
| FC | ||
| ● Number, max. | 1 024; Number range: 0 to 7999 | 1 024; Number range: 0 to 7999 |
| ● Size, max. | 64 kbyte | 64 kbyte |
| OB | ||
| ● Size, max. | 64 kbyte | 64 kbyte |
| ● Number of free cycle OBs | 1; OB 1 | 1; OB 1 |
| ● Number of time alarm OBs | 1; OB 10 | 1; OB 10 |
| ● Number of delay alarm OBs | 2; OB 20, 21 | 2; OB 20, 21 |
| ● Number of cyclic interrupt OBs | 4; OB 32, 33, 34, 35 | 4; OB 32, 33, 34, 35 |
| ● Number of process alarm OBs | 1; OB 40 | 1; OB 40 |
| ● Number of DPV1 alarm OBs | 3; OB 55, 56, 57 | 3; OB 55, 56, 57 |
| ● Number of isochronous mode OBs | 1; OB 61 | 1; OB 61 |
| ● Number of startup OBs | 1; OB 100 | 1; OB 100 |
| ● Number of asynchronous error OBs | 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for centralized I/O and PROFINET IO) | 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for centralized I/O and PROFINET IO) |
| ● Number of synchronous error OBs | 2; OB 121, 122 | 2; OB 121, 122 |
| Nesting depth | ||
| ● per priority class | 16 | 16 |
| ● additional within an error OB | 4 | 4 |
| Counters, timers and their retentivity | ||
| S7 counter | ||
| ● Number | 256 | 256 |
| Retentivity | ||
| — adjustable | Yes | Yes |
| — lower limit | 0 | 0 |
| — upper limit | 255 | 255 |
| — preset | Z 0 to Z 7 | Z 0 to Z 7 |
| Counting range | ||
| — adjustable | Yes | Yes |
| — lower limit | 0 | 0 |
| — upper limit | 999 | 999 |
| IEC counter | ||
| ● present | Yes | Yes |
| ● Type | SFB | SFB |
| ● Number | Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) |
| S7 times | ||
| ● Number | 256 | 256 |
| Retentivity | ||
| — adjustable | Yes | Yes |
| — lower limit | 0 | 0 |
| — upper limit | 255 | 255 |
| — preset | No retentivity | No retentivity |
| Time range | ||
| — lower limit | 10 ms | 10 ms |
| — upper limit | 9 990 s | 9 990 s |
| IEC timer | ||
| ● present | Yes | Yes |
| ● Type | SFB | SFB |
| ● Number | Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) |
| Data areas and their retentivity | ||
| Retentive data area (incl. timers, counters, flags), max. | 128 kbyte | 128 kbyte |
| Flag | ||
| ● Size, max. | 2 048 byte | 2 048 byte |
| ● Retentivity available | Yes; MB 0 to MB 2 047 | Yes; MB 0 to MB 2 047 |
| ● Retentivity preset | MB 0 to MB 15 | MB 0 to MB 15 |
| ● Number of clock memories | 8 | 8 |
| Data blocks | ||
| ● Retentivity adjustable | Yes; via non-retain property on DB | Yes; via non-retain property on DB |
| ● Retentivity preset | Yes | Yes |
| Local data | ||
| ● per priority class, max. | 32 768 byte; Max. 2048 bytes per block | 32 768 byte; Max. 2048 bytes per block |
| Address area | ||
| I/O address area | ||
| ● Inputs | 2 048 byte | 2 048 byte |
| ● Outputs | 2 048 byte | 2 048 byte |
| of which distributed | ||
| — Inputs | 2 048 byte | 2 048 byte |
| — Outputs | 2 048 byte | 2 048 byte |
| Process image | ||
| ● Inputs, adjustable | 2 048 byte | 2 048 byte |
| ● Outputs, adjustable | 2 048 byte | 2 048 byte |
| ● Inputs, default | 128 byte | 128 byte |
| ● Outputs, default | 128 byte | 128 byte |
| Subprocess images | ||
| ● Number of subprocess images, max. | 1; With PROFINET IO, the length of the user data is limited to 1600 bytes | 1; With PROFINET IO, the length of the user data is limited to 1600 bytes |
| Digital channels | ||
| ● Inputs | 16 384 | 16 384 |
| — of which central | 128 | 128 |
| ● Outputs | 16 384 | 16 384 |
| — of which central | 64 | 64 |
| Analog channels | ||
| ● Inputs | 1 024 | 1 024 |
| — of which central | 64 | 64 |
| ● Outputs | 1 024 | 1 024 |
| — of which central | 64 | 64 |
| Hardware configuration | ||
| Integrated power supply | No | No |
| Number of DP masters | ||
| ● integrated | 1 | 1 |
| Rack | ||
| ● Racks, max. | 1 | 1 |
| ● Modules per rack, max. | 16; Expansion width max. 1 m | 16; Expansion width max. 1 m |
| Time of day | ||
| Clock | ||
| ● Hardware clock (real-time) | Yes | Yes |
| ● retentive and synchronizable | Yes | Yes |
| ● Backup time | 6 wk; At 40 °C ambient temperature | 6 wk; At 40 °C ambient temperature |
| ● Deviation per day, max. | 10 s; Typ.: 2 s | 10 s; Typ.: 2 s |
| Operating hours counter | ||
| ● Number | 1 | 1 |
| ● Number/Number range | 0 | 0 |
| ● Range of values | 0 to 2^31 hours (when using SFC 101) | 0 to 2^31 hours (when using SFC 101) |
| ● Granularity | 1 h | 1 h |
| ● retentive | Yes; Must be restarted at each restart | Yes; Must be restarted at each restart |
| Clock synchronization | ||
| ● supported | Yes | Yes |
| ● to MPI, master | Yes | Yes |
| ● to MPI, slave | Yes | Yes |
| ● to DP, master | Yes; With DP slave only slave clock | Yes; With DP slave only slave clock |
| ● to DP, slave | Yes | Yes |
| ● on Ethernet via NTP | Yes; As client | Yes; As client |
| 1. Interface | ||
| Interface type | Integrated RS 485 interface | Integrated RS 485 interface |
| Isolated | Yes | Yes |
| Interface types | ||
| ● RS 485 | Yes | Yes |
| ● Output current of the interface, max. | May only be used for external terminating resistor | May only be used for external terminating resistor |
| ● Design of the connection | 2x M12 B-coded | 2x M12 B-coded |
| Protocols | ||
| ● MPI | Yes | Yes |
| ● PROFIBUS DP master | Yes | Yes |
| ● PROFIBUS DP slave | Yes | Yes |
| ● Point-to-point connection | No | No |
| MPI | ||
| ● Transmission rate, max. | 12 Mbit/s | 12 Mbit/s |
| Services | ||
| — PG/OP communication | Yes | Yes |
| — Routing | Yes | Yes |
| — Global data communication | Yes | Yes |
| — S7 basic communication | Yes | Yes |
| — S7 communication | Yes | Yes |
| — S7 communication, as client | No | No |
| — S7 communication, as server | Yes | Yes |
| PROFIBUS DP master | ||
| ● Transmission rate, max. | 12 Mbit/s | 12 Mbit/s |
| ● Number of DP slaves, max. | 124 | 124 |
| Services | ||
| — PG/OP communication | Yes | Yes |
| — Routing | Yes | Yes |
| — Global data communication | No | No |
| — S7 basic communication | Yes; I blocks only | Yes; I blocks only |
| — S7 communication | Yes | Yes |
| — S7 communication, as client | No | No |
| — S7 communication, as server | Yes; Connection configured on one side only | Yes; Connection configured on one side only |
| — Equidistance | Yes | Yes |
| — Isochronous mode | Yes; OB 61 – isochronous mode is possible either on DP or PROFINET IO (not simultaneously) | Yes; OB 61 – isochronous mode is possible either on DP or PROFINET IO (not simultaneously) |
| — SYNC/FREEZE | Yes | Yes |
| — Activation/deactivation of DP slaves | Yes | Yes |
| — Direct data exchange (slave-to-slave communication) | Yes; as subscriber | Yes; as subscriber |
| — DPV1 | Yes | Yes |
| Address area | ||
| — Inputs, max. | 2 048 byte | 2 048 byte |
| — Outputs, max. | 2 048 byte | 2 048 byte |
| User data per DP slave | ||
| — Inputs, max. | 244 byte | 244 byte |
| — Outputs, max. | 244 byte | 244 byte |
| PROFIBUS DP slave | ||
| ● Transmission rate, max. | 12 Mbit/s | 12 Mbit/s |
| ● automatic baud rate search | Yes; only with passive interface | Yes; only with passive interface |
| ● Address area, max. | 32 | 32 |
| ● User data per address area, max. | 32 byte | 32 byte |
| Services | ||
| — Routing | Yes; with interface active | Yes; with interface active |
| — Global data communication | No | No |
| — S7 basic communication | No | No |
| — S7 communication | Yes | Yes |
| — S7 communication, as client | No | No |
| — S7 communication, as server | Yes; Connection configured on one side only | Yes; Connection configured on one side only |
| — Direct data exchange (slave-to-slave communication) | Yes | Yes |
| — DPV1 | No | No |
| Transfer memory | ||
| — Inputs | 244 byte | 244 byte |
| — Outputs | 244 byte | 244 byte |
| 2. Interface | ||
| Interface type | PROFINET | PROFINET |
| Isolated | Yes; Galvanic isolation for P3 is implemented in IM154-8, for P1 and P2 in CM | Yes; Galvanic isolation for P3 is implemented in IM154-8, for P1 and P2 in CM |
| automatic detection of transmission rate | Yes; 10/100 Mbit/s | Yes; 10/100 Mbit/s |
| Autonegotiation | Yes | Yes |
| Autocrossing | Yes | Yes |
| Change of IP address at runtime, supported | Yes | Yes |
| Interface types | ||
| ● Number of ports | 3 | 3 |
| ● integrated switch | Yes | Yes |
| ● Design of the connection | Ethernet (2x M12 D-coded; 1x RJ45) | Ethernet (2x M12 D-coded; 1x RJ45) |
| Protocols | ||
| ● MPI | No | No |
| ● PROFINET IO Controller | Yes; Also simultaneously with IO-Device functionality | Yes; Also simultaneously with IO-Device functionality |
| ● PROFINET IO Device | Yes; Also simultaneously with IO Controller functionality | Yes; Also simultaneously with IO Controller functionality |
| ● PROFINET CBA | Yes | Yes |
| ● PROFIBUS DP master | No | No |
| ● PROFIBUS DP slave | No | No |
| ● Open IE communication | Yes; Via TCP/IP, ISO on TCP, and UDP | Yes; Via TCP/IP, ISO on TCP, and UDP |
| ● Web server | Yes | Yes |
| ● Media redundancy | Yes | Yes |
| PROFINET IO Controller | ||
| ● Transmission rate, max. | 100 Mbit/s | 100 Mbit/s |
| Services | ||
| — PG/OP communication | Yes | Yes |
| — Routing | Yes | Yes |
| — S7 communication | Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32 | Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32 |
| — Isochronous mode | Yes; OB 61 – isochronous mode is possible either on DP or PROFINET IO (not simultaneously) | Yes; OB 61 – isochronous mode is possible either on DP or PROFINET IO (not simultaneously) |
| — IRT | Yes | Yes |
| — Prioritized startup | Yes | Yes |
| — Number of IO devices with prioritized startup, max. | 32 | 32 |
| — Number of connectable IO Devices, max. | 128 | 128 |
| — Of which IO devices with IRT, max. | 64 | 64 |
| — of which in line, max. | 64 | 64 |
| — Number of IO Devices with IRT and the option “high flexibility” | 128 | 128 |
| — of which in line, max. | 61 | 61 |
| — Number of connectable IO Devices for RT, max. | 128 | 128 |
| — of which in line, max. | 128 | 128 |
| — Activation/deactivation of IO Devices | Yes | Yes |
| — Number of IO Devices that can be simultaneously activated/deactivated, max. | 8 | 8 |
| — IO Devices changing during operation (partner ports), supported | Yes | Yes |
| — Number of IO Devices per tool, max. | 8 | 8 |
| — Device replacement without swap medium | Yes | Yes |
| — Send cycles | 250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with “high flexibility” option) | 250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with “high flexibility” option) |
| — Updating time | 250 µs to 512 ms (depending on the operating mode, see “IM 154-8 CPU Interface Module” operating instructions for more details) | 250 µs to 512 ms (depending on the operating mode, see “IM 154-8 CPU Interface Module” operating instructions for more details) |
| Address area | ||
| — Inputs, max. | 2 048 byte | 2 048 byte |
| — Outputs, max. | 2 048 byte | 2 048 byte |
| — User data consistency, max. | 1 024 byte | 1 024 byte |
| PROFINET IO Device | ||
| Services | ||
| — PG/OP communication | Yes | Yes |
| — Routing | Yes | Yes |
| — S7 communication | Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32 | Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32 |
| — Isochronous mode | No | No |
| — IRT | Yes | Yes |
| — PROFIenergy | Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device | Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device |
| — Shared device | Yes | Yes |
| — Number of IO Controllers with shared device, max. | 2 | 2 |
| Transfer memory | ||
| — Inputs, max. | 1 440 byte; Per IO Controller with shared device | 1 440 byte; Per IO Controller with shared device |
| — Outputs, max. | 1 440 byte; Per IO Controller with shared device | 1 440 byte; Per IO Controller with shared device |
| Submodules | ||
| — Number, max. | 64 | 64 |
| — User data per submodule, max. | 1 024 byte | 1 024 byte |
| PROFINET CBA | ||
| ● acyclic transmission | Yes | Yes |
| ● cyclic transmission | Yes | Yes |
| Open IE communication | ||
| ● Number of connections, max. | 8 | 8 |
| ● Local port numbers used at the system end | 0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535 | 0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535 |
| ● Keep-alive function, supported | Yes | Yes |
| Protocols | ||
| Redundancy mode | ||
| Media redundancy | ||
| — Switchover time on line break, typ. | 200 ms; PROFINET MRP | 200 ms; PROFINET MRP |
| — Number of stations in the ring, max. | 50 | 50 |
| SIMATIC communication | ||
| ● S7 routing | Yes | Yes |
| Open IE communication | ||
| ● TCP/IP | Yes; via integrated PROFINET interface and loadable FBs | Yes; via integrated PROFINET interface and loadable FBs |
| — Number of connections, max. | 8 | 8 |
| — Data length, max. | 32 768 byte; 1 460 bytes with connection type 01H; 32 768 bytes with connection type 11H | 32 768 byte; 1 460 bytes with connection type 01H; 32 768 bytes with connection type 11H |
| — several passive connections per port, supported | Yes | Yes |
| ● ISO-on-TCP (RFC1006) | Yes | Yes |
| — Number of connections, max. | 8 | 8 |
| — Data length, max. | 32 768 byte | 32 768 byte |
| ● UDP | Yes | Yes |
| — Number of connections, max. | 8 | 8 |
| — Data length, max. | 1 472 byte | 1 472 byte |
| Web server | ||
| ● supported | Yes | Yes |
| ● User-defined websites | Yes | Yes |
| ● Number of HTTP clients | 5 | 5 |
| communication functions / header | ||
| PG/OP communication | Yes | Yes |
| Global data communication | ||
| ● supported | Yes | Yes |
| ● Number of GD loops, max. | 8 | 8 |
| ● Number of GD packets, max. | 8 | 8 |
| ● Number of GD packets, transmitter, max. | 8 | 8 |
| ● Number of GD packets, receiver, max. | 8 | 8 |
| ● Size of GD packets, max. | 22 byte | 22 byte |
| ● Size of GD packet (of which consistent), max. | 22 byte | 22 byte |
| S7 basic communication | ||
| ● supported | Yes | Yes |
| ● User data per job, max. | 76 byte | 76 byte |
| ● User data per job (of which consistent), max. | 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) | 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
| S7 communication | ||
| ● supported | Yes | Yes |
| ● as server | Yes | Yes |
| ● as client | Yes; via integrated PROFINET interface and loadable FBs | Yes; via integrated PROFINET interface and loadable FBs |
| ● User data per job, max. | See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication) | See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication) |
| communication functions / PROFINET CBA (with set target communication load) / header | ||
| ● Setpoint for the CPU communication load | 50 % | 50 % |
| ● number of remote connection partners / with PROFINET CBA | 32 | 32 |
| ● number of technological functions / with PROFINET CBA / for master or slave | 30 | 30 |
| ● number of connections / with PROFINET CBA / for master or slave / total | 1 000 | 1 000 |
| ● data volume / of the input variables / with PROFINET CBA / for master or slave | 4 000 byte | 4 000 byte |
| ● data volume / of the output variables / with PROFINET CBA / for master or slave | 4 000 byte | 4 000 byte |
| ● number of internal and PROFIBUS interconnections / with PROFINET CBA / maximum | 500 | 500 |
| ● data volume / of internal and PROFIBUS interconnections / with PROFINET CBA / for master or slave | 4 000 byte | 4 000 byte |
| ● data volume / with PROFINET CBA / per connection / maximum | 1 400 byte | 1 400 byte |
| performance data / PROFINET CBA / remote interconnection / with acyclic transfer / header | ||
| — update time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA | 500 ms | 500 ms |
| — number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 100 | 100 |
| — number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 100 | 100 |
| — data volume / as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA | 2 000 byte | 2 000 byte |
| — data volume / as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA | 2 000 byte | 2 000 byte |
| — data volume / as user data for remote interconnections / in the case of acyclic transmission / with PROFINET CBA / per connection / maximum | 1 400 byte | 1 400 byte |
| performance data / PROFINET CBA / remote interconnection / with cyclic transfer / header | ||
| — update time / of the remote interconnections / with cyclical transfer / with PROFINET CBA | 1 ms | 1 ms |
| — number of remote connections to input variables / with PROFINET CBA / with cyclic transfer / maximum | 200 | 200 |
| — number of remote connections to output variables / with cyclical transfer / with PROFINET CBA / maximum | 200 | 200 |
| — data volume / as user data for remote interconnections with input variables / with cyclical transfer / with PROFINET CBA / maximum | 2 000 byte | 2 000 byte |
| — data volume / as user data for remote interconnections with output variables / with cyclical transfer / with PROFINET CBA / maximum | 2 000 byte | 2 000 byte |
| — data volume / as user data for remote interconnections / with cyclical transfer / with PROFINET CBA / per connection / maximum | 450 byte | 450 byte |
| performance data / PROFINET CBA / HMI variables via PROFINET / acyclic / header | ||
| — number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA | 3; 2x PN OPC/1x iMap | 3; 2x PN OPC/1x iMap |
| — update time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA | 500 ms | 500 ms |
| — number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 200 | 200 |
| — data volume / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 2 000 byte | 2 000 byte |
| performance data / PROFINET CBA / PROFIBUS proxy functionality / header | ||
| — product function / with PROFINET CBA / PROFIBUS proxy functionality | Yes | Yes |
| — number of coupled PROFIBUS devices / with PROFIBUS functionality | 16 | 16 |
| — data volume / with PROFIBUS proxy functionality / with PROFINET CBA / per connection / maximum | 240 byte; Slave-dependent | 240 byte; Slave-dependent |
| Number of connections | ||
| ● overall | 16 | 16 |
| ● usable for PG communication | 15 | 15 |
| — reserved for PG communication | 1 | 1 |
| — adjustable for PG communication, min. | 1 | 1 |
| — adjustable for PG communication, max. | 15 | 15 |
| ● usable for OP communication | 15 | 15 |
| — reserved for OP communication | 1 | 1 |
| — adjustable for OP communication, min. | 1 | 1 |
| — adjustable for OP communication, max. | 15 | 15 |
| ● usable for S7 basic communication | 14 | 14 |
| — reserved for S7 basic communication | 0 | 0 |
| — adjustable for S7 basic communication, min. | 0 | 0 |
| — adjustable for S7 basic communication, max. | 14 | 14 |
| ● usable for routing | X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max. | X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max. |
| S7 message functions | ||
| Number of login stations for message functions, max. | 16; Depending on the configured connections for PG/OP and S7 basic communication | 16; Depending on the configured connections for PG/OP and S7 basic communication |
| Process diagnostic messages | Yes | Yes |
| simultaneously active Alarm-S blocks, max. | 300 | 300 |
| Test commissioning functions | ||
| Status block | Yes; Up to 2 simultaneously | Yes; Up to 2 simultaneously |
| Single step | Yes | Yes |
| Number of breakpoints | 4 | 4 |
| Status/control | ||
| ● Status/control variable | Yes | Yes |
| ● Variables | Inputs, outputs, memory bits, DB, times, counters | Inputs, outputs, memory bits, DB, times, counters |
| ● Number of variables, max. | 30 | 30 |
| — of which status variables, max. | 30 | 30 |
| — of which control variables, max. | 14 | 14 |
| Forcing | ||
| ● Forcing | Yes | Yes |
| ● Forcing, variables | I/O | I/O |
| ● Number of variables, max. | 10 | 10 |
| Diagnostic buffer | ||
| ● present | Yes | Yes |
| ● Number of entries, max. | 500; Only the last 100 entries are retentive at power on/off | 500; Only the last 100 entries are retentive at power on/off |
| — adjustable | No | No |
| — preset | 10 | 10 |
| Potential separation | ||
| between backplane bus and electronics | No | No |
| between backplane bus and all other circuit components | Yes | Yes |
| between supply and all other circuits | Yes | Yes |
| Isolation | ||
| Isolation tested with | In general, 707 V DC (type test), Ethernet interface 1 500 V AC (for P1 and P2 on CM, for P3 on IM) | In general, 707 V DC (type test), Ethernet interface 1 500 V AC (for P1 and P2 on CM, for P3 on IM) |
| Degree and class of protection | ||
| IP degree of protection | IP65/67 | IP65/67 |
| Standards, approvals, certificates | ||
| CE mark | Yes | Yes |
| CSA approval | No | No |
| cULus | Yes | Yes |
| FM approval | No | No |
| RCM (formerly C-TICK) | Yes | Yes |
| Highest safety class achievable in safety mode | ||
| ● Performance level according to ISO 13849-1 | PLe | PLe |
| ● SIL acc. to IEC 61508 | SIL 3 | SIL 3 |
| configuration / header | ||
| Configuration software | ||
| ● STEP 7 | Yes; V5.5 or higher | Yes; V5.5 or higher |
| configuration / programming / header | ||
| ● Command set | see instruction list | see instruction list |
| ● Nesting levels | 8 | 8 |
| ● System functions (SFC) | see instruction list | see instruction list |
| ● System function blocks (SFB) | see instruction list | see instruction list |
| Programming language | ||
| — LAD | Yes | Yes |
| — FBD | Yes | Yes |
| — STL | Yes | Yes |
| — SCL | Yes | Yes |
| — CFC | Yes | Yes |
| — GRAPH | Yes | Yes |
| — HiGraph® | Yes | Yes |
| Know-how protection | ||
| ● User program protection/password protection | Yes | Yes |
| ● Block encryption | Yes; With S7 block Privacy | Yes; With S7 block Privacy |
| Dimensions | ||
| Width | 135 mm | 135 mm |
| Height | 130 mm | 130 mm |
| Depth | 65 mm; 60 mm without cover for RJ45 socket; 65 mm with cover for RJ45 socket | 65 mm; 60 mm without cover for RJ45 socket; 65 mm with cover for RJ45 socket |
| Weights | ||
| Weight, approx. | 720 g | 720 g |
| Weight | N/A |
|---|---|
| Dimensions | N/A |