ET200pro, EM 4 IO-Link HF |
| Supply voltage |
|
| Rated value (DC) |
24 V |
| Reverse polarity protection |
Yes |
| Load voltage 2L+ |
|
| ● Rated value (DC) |
24 V |
| ● Short-circuit protection |
Yes |
| ● Reverse polarity protection |
Yes; against destruction; load increasing |
| Input current |
|
| from supply voltage 1L+, max. |
40 mA |
| from load voltage 2L+ (without load), max. |
20 mA |
| from backplane bus 3.3 V DC, max. |
20 mA |
| Encoder supply |
|
| Number of outputs |
4 |
| Short-circuit protection |
Yes; per module, electronic |
| Output current |
|
| ● up to 55 °C, max. |
2 A |
| Power loss |
|
| Power loss, typ. |
2.6 W |
| IO-Link |
|
| Number of ports |
4 |
| ● of which simultaneously controllable |
4 |
| IO-Link protocol 1.0 |
Yes |
| IO-Link protocol 1.1 |
Yes |
| Transmission rate |
4.8 kBaud (COM1); 38.4 kBaud (COM2), 230.4 kBaud (COM3) |
| Size of process data, input per port |
32 byte |
| Size of process data, input per module |
32 byte |
| Size of process data, output per port |
32 byte |
| Size of process data, output per module |
32 byte |
| Memory size for device parameter |
2 kbyte; for each port |
| Master backup |
Possible with function block IO_LINK_MASTER |
| Configuration without S7-PCT |
Possible; autostart/manual function |
| Cable length unshielded, max. |
20 m |
| Operating modes |
|
| ● IO-Link |
Yes |
| ● DI |
Yes |
| ● DQ |
Yes; max. 100 mA |
| Connection of IO-Link devices |
|
| ● Port type A |
Yes; via 3-core cable |
| ● Port type B |
Yes; Additional device supply: for X1 and X2 max. 2 A in total, for X3 and X4 max. 2 A in total |
| Interrupts/diagnostics/status information |
|
| Diagnostics function |
Yes |
| Alarms |
|
| ● Diagnostic alarm |
Yes |
| Diagnoses |
|
| ● Diagnostic information readable |
Yes |
| ● Wire-break |
Yes; channel by channel |
| ● Short-circuit |
Yes; channel by channel |
| Diagnostics indication LED |
|
| ● Channel status display |
Yes; One green LED for channel status Qn (SIO mode) and port status IO-Ln (IO-Link mode) |
| ● Group error SF (red) |
Yes |
| ● Channel fault indicator F (red) |
Yes; combined with the IO-Link port status |
| Potential separation |
|
| between the load voltages |
Yes |
| between backplane bus and all other circuit components |
Yes |
| Potential separation channels |
|
| ● between the channels |
No |
| Isolation |
|
| Isolation tested with |
707 V DC (type test) |
| Degree and class of protection |
|
| IP degree of protection |
IP65/67 |
| Standards, approvals, certificates |
|
| Suitable for safety-related tripping of standard modules |
No |
| Dimensions |
|
| Width |
45 mm |
| Height |
130 mm |
| Depth |
35 mm |
| Weights |
|
| Weight, approx. |
150 g |