| Article number | 6ES7138-4FA05-0AB0 |
| ET200S, El-Mod., 4/8 F-DI, DC 24V | |
| Supply voltage | |
| Rated value (DC) | 24 V |
| Encoder supply | |
| Number of outputs | 2 |
| Type of output voltage | min. L+ (-1.5 V) |
| Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 1.8 A) |
| Output current | |
| ● Rated value | 300 mA |
| ● permissible range, lower limit | 0 mA |
| ● permissible range, upper limit | 300 mA |
| Power loss | |
| Power loss, typ. | 4 W |
| Address area | |
| Address space per module | |
| ● Inputs | 6 byte |
| ● Outputs | 4 byte |
| Digital inputs | |
| Number of digital inputs | 8; 8 (one-channel); 4 (two-channel) |
| Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
| Input voltage | |
| ● Type of input voltage | DC |
| ● Rated value (DC) | 24 V |
| Input current | |
| ● for signal “1”, typ. | 3.7 mA |
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| — parameterizable | Yes |
| — at “0” to “1”, min. | 0.3 ms |
| — at “0” to “1”, max. | 17 ms |
| — at “1” to “0”, min. | 0.3 ms |
| — at “1” to “0”, max. | 17 ms |
| Cable length | |
| ● shielded, max. | 500 m |
| ● unshielded, max. | 500 m |
| Encoder | |
| Connectable encoders | |
| ● 2-wire sensor | No |
| — permissible quiescent current (2-wire sensor), max. | 0.6 mA; max. |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Alarms | |
| ● Diagnostic alarm | Yes |
| Diagnoses | |
| ● Diagnostic information readable | Yes |
| ● Short-circuit | Yes |
| Diagnostics indication LED | |
| ● Group error SF (red) | Yes |
| ● Status indicator digital input (green) | Yes |
| Potential separation | |
| Potential separation digital inputs | |
| ● between the channels | No |
| ● between the channels and backplane bus | Yes |
| ● Between the channels and load voltage L+ | No |
| Standards, approvals, certificates | |
| Highest safety class achievable in safety mode | |
| ● acc. to EN 954 | 4 |
| ● Performance level according to ISO 13849-1 | PLe |
| ● SIL acc. to IEC 61508 | SIL 2 (single-channel), SIL 3 (two-channel) |
| Dimensions | |
| Width | 30 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weights | |
| Weight, approx. | 78 g |
| Article number | 6ES7138-4FB04-0AB0 |
| ET200S, El-Mod., 4 F-DO, DC 24V/2A | |
| Supply voltage | |
| Load voltage L+ | |
| ● Rated value (DC) | 24 V |
| ● Reverse polarity protection | No |
| Input current | |
| From load voltage L+ (no load), typ. | 100 mA |
| from backplane bus 3.3 V DC, max. | 28 mA |
| Power loss | |
| Power loss, typ. | 3.5 W |
| Digital outputs | |
| Type of digital output | Transistor |
| Number of digital outputs | 4 |
| Short-circuit protection | Yes |
| Limitation of inductive shutdown voltage to | Typ. (2L+) -47 V |
| Controlling a digital input | No |
| Switching capacity of the outputs | |
| ● on lamp load, max. | 10 W |
| Load resistance range | |
| ● lower limit | 12 Ω |
| ● upper limit | 1 kΩ |
| Output voltage | |
| ● for signal “1”, min. | L+ (-2,0 V), current sourcing switch: L+ (-1,5 V), voltage drop on current sinking switch: max. 0.5 V |
| Output current | |
| ● for signal “1” rated value | 2 A |
| ● for signal “1” permissible range, min. | 20 mA |
| ● for signal “1” permissible range, max. | 2.4 A |
| ● for signal “0” residual current, max. | 0.5 mA; Current-sourcing and current-sinking switches |
| Parallel switching of two outputs | |
| ● for uprating | No |
| ● for redundant control of a load | No |
| Switching frequency | |
| ● with resistive load, max. | 30 Hz; Symmetrical |
| ● with inductive load, max. | 0.1 Hz; Symmetrical |
| ● on lamp load, max. | 10 Hz; Symmetrical |
| Total current of the outputs | |
| ● Current per module, max. | 6 A |
| Total current of the outputs (per group) | |
| horizontal installation | |
| — up to 40 °C, max. | 6 A |
| — up to 55 °C, max. | 5 A |
| — up to 60 °C, max. | 4 A |
| vertical installation | |
| — up to 40 °C, max. | 4 A |
| Cable length | |
| ● shielded, max. | 500 m |
| ● unshielded, max. | 500 m |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Diagnoses | |
| ● Wire-break | Yes |
| ● Short-circuit | Yes |
| Diagnostics indication LED | |
| ● Group error SF (red) | Yes |
| ● Status indicator digital output (green) | Yes |
| Potential separation | |
| Potential separation digital outputs | |
| ● between the channels | No |
| ● between the channels and backplane bus | Yes |
| ● Between the channels and load voltage L+ | No |
| Standards, approvals, certificates | |
| Highest safety class achievable in safety mode | |
| ● acc. to EN 954 | 4 |
| ● Performance level according to ISO 13849-1 | PLe |
| ● SIL acc. to IEC 61508 | SIL 3 |
| Dimensions | |
| Width | 30 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weights | |
| Weight, approx. | 85 g |
| Article number | 6ES7138-4FC01-0AB0 |
| ET200S, El-Mod.,4 F-DI/3 F-DO, DC 24V/2A | |
| Supply voltage | |
| Rated value (DC) | 24 V |
| Power loss | |
| Power loss, typ. | 3.5 W |
| Digital inputs | |
| Number of digital inputs | 4 |
| Input voltage | |
| ● Type of input voltage | DC |
| Input current | |
| ● for signal “1”, typ. | 3.5 mA |
| Standards, approvals, certificates | |
| Highest safety class achievable in safety mode | |
| ● acc. to EN 954 | 3 |
| ● Performance level according to ISO 13849-1 | d |
| ● SIL acc. to IEC 61508 | 2 |
| Dimensions | |
| Width | 30 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weight | N/A |
|---|---|
| Dimensions | N/A |