| Potential isolation module |
6ES7138-4FD00-0AA0 |
| Module-specific specifications |
| Supported synchronous operation |
no |
| Number of outputs |
4 |
| Cable length |
| Unshielded |
max. 600 m |
| Shielded |
max. 1000 m |
| Parameter length |
1 byte |
| Voltages, Currents, Potentials |
| Nominal load voltage L+ (from power module) |
24 … 48 V DC; 24 AC … 230 V |
| Polarity reversal protection |
no |
| Total current of the outputs (per module) |
max. 10 A |
| Potential isolation |
| Between the channels |
no |
| Between the channels and backplane bus |
Yes |
| Permissible potential difference |
| Between the supply voltage and the backplane bus |
75 V DC, 240 V AC |
| Isolation tested |
| Between the supply voltage and the backplane bus |
500 V DC, 1500 V AC |
| Diagnostic alarm |
no |
| Data for selecting an actuator |
| Short-circuit protection for the output |
No, possible via PM-E or external |
| Dimensions and weight |
| Dimensions W × H × D (mm, the total dimensions depend on the selected terminal module) |
15 x 81 x 52 |
| Weight |
Approx. 33 g |