| Article number |
6ES7137-6BD00-0BA0 |
|
ET 200SP, cm 4 X IO-Link ST |
| General information |
|
| Product type designation |
CM 4 x IO-Link ST |
| HW functional status |
FS20 |
| Firmware version |
V2.2.2 |
| ● FW update possible |
Yes |
| usable BaseUnits |
BU type A0 |
| Color code for module-specific color identification plate |
CC04 |
| Product function |
|
| ● I&M data |
Yes; I&M0 to I&M3 |
| ● Isochronous mode |
No; Only for PROFINET and configuration as version with FW V2.0 or V2.1 |
| Engineering with |
|
| ● STEP 7 TIA Portal configurable/integrated from version |
STEP 7 V15 or higher |
| ● STEP 7 configurable/integrated from version |
STEP 7 V5.5 or higher |
| ● PROFIBUS from GSD version/GSD revision |
One GSD file each, Revision 3 and 5 and higher |
| ● PROFINET from GSD version/GSD revision |
GSDML V2.3 |
| Supply voltage |
|
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
19.2 V; 20.5 V if IO-Link is used, as the supply voltage for IO-Link devices has to be at least 20 V at the master. |
| permissible range, upper limit (DC) |
28.8 V |
| power supply according to NEC Class 2 required |
No |
| Input current |
|
| Current consumption, max. |
45 mA; without load |
| Encoder supply |
|
| Number of outputs |
4 |
| Output current |
|
| ● Rated value |
700 mA; Per channel |
| 24 V encoder supply |
|
| ● Short-circuit protection |
Yes |
| ● Output current, max. |
2.1 A |
| Power loss |
|
| Power loss, typ. |
1 W |
| Hardware configuration |
|
| Automatic encoding |
Yes |
| ● Electronic coding element type H |
Yes |
| Digital outputs |
|
| Cable length |
|
| ● unshielded, max. |
20 m; Also applies for shielded cables |
| IO-Link |
|
| Number of ports |
4 |
| ● of which simultaneously controllable |
4 |
| IO-Link protocol 1.0 |
Yes |
| IO-Link protocol 1.1 |
Yes |
| Transmission rate |
4.8 kBaud (COM1); 38.4 kBaud (COM2), 230.4 kBaud (COM3) |
| Cycle time, min. |
2 ms; dynamic, depending on user data length |
| Size of process data, input per port |
32 byte; max. |
| Size of process data, input per module |
144 byte; max. |
| Size of process data, output per port |
32 byte; max. |
| Size of process data, output per module |
128 byte; max. |
| Memory size for device parameter |
2 kbyte; for each port |
| Master backup |
Yes |
| Configuration without S7-PCT |
Yes |
| Cable length unshielded, max. |
20 m |
| Operating modes |
|
| ● IO-Link |
Yes |
| ● DI |
Yes |
| ● DQ |
Yes; max. 100 mA per channel |
| Time Based IO |
|
| — TIO IO-Link IN |
No; Only for PROFINET and configuration as version with FW V2.0 or V2.1 |
| — TIO IO-Link OUT |
No; Only for PROFINET and configuration as version with FW V2.0 or V2.1 |
| — TIO IO-Link IN/OUT |
No; Only for PROFINET and configuration as version with FW V2.0 or V2.1 |
| Connection of IO-Link devices |
|
| ● Port type A |
Yes |
| ● Port type B |
Yes; 24 V DC via external terminal |
| ● via three-wire connection |
Yes |
| Interrupts/diagnostics/status information |
|
| Alarms |
|
| ● Diagnostic alarm |
Yes; The port diagnosis is available in the IO-Link mode only. |
| Diagnoses |
|
| ● Monitoring the supply voltage |
Yes |
| ● Wire-break |
Yes |
| ● Short-circuit |
Yes |
| ● Group error |
Yes |
| Diagnostics indication LED |
|
| ● Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
| ● Channel status display |
Yes; one green LED for channel status Qn (SIO mode) and port status Cn (IO-Link mode) per channel |
| ● for channel diagnostics |
Yes; red Fn LED |
| ● for module diagnostics |
Yes; green/red DIAG LED |
| Potential separation |
|
| Potential separation channels |
|
| ● between the channels |
No |
| ● between the channels and backplane bus |
Yes |
| ● between the channels and the power supply of the electronics |
No |
| Isolation |
|
| Isolation tested with |
707 V DC (type test) |
| Ambient conditions |
|
| Ambient temperature during operation |
|
| ● horizontal installation, min. |
-30 °C |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
-30 °C |
| ● vertical installation, max. |
50 °C |
| Altitude during operation relating to sea level |
|
| ● Installation altitude above sea level, max. |
2 000 m; On request: Installation altitudes greater than 2 000 m |
| Dimensions |
|
| Width |
13 mm |
| Height |
73 mm |
| Depth |
58 mm |
| Weights |
|
| Weight, approx. |
30 g |