Article number |
6ES7136-6BA00-0CA0 |
|
ET 200SP, El-Mod., F-DI 8x24VDC HF |
General information |
|
Product type designation |
F-DI 8x24VDC HF |
Firmware version |
|
● FW update possible |
|
usable BaseUnits |
BU type A0 |
Color code for module-specific color identification plate |
|
Product function |
|
● I&M data |
Yes; I&M0 to I&M3 |
Engineering with |
|
● STEP 7 TIA Portal configurable/integrated from version |
V12 |
● STEP 7 configurable/integrated from version |
V5.5 SP3 / – |
● PROFINET from GSD version/GSD revision |
V2.31 |
CiR – Configuration in RUN |
|
Reparameterization possible in RUN |
|
Supply voltage |
|
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
power supply according to NEC Class 2 required |
No |
Input current |
|
Current consumption (rated value) |
75 mA; without load |
Current consumption, max. |
21 mA; From the backplane bus |
Encoder supply |
|
Number of outputs |
8 |
Short-circuit protection |
Yes; Electronic (response threshold 0.7 A to 1.8 A) |
Output current |
|
● up to 60 °C, max. |
0.3 A |
24 V encoder supply |
|
● 24 V |
Yes; min. L+ (-1.5 V) |
● Short-circuit protection |
Yes |
● Output current, max. |
800 mA; Total current of all encoders |
● Output current per channel, max. |
|
● Output current per module, max. |
|
Power |
|
Power available from the backplane bus |
70 mW |
Power loss |
|
Power loss, typ. |
4 W |
Address area |
|
Address space per module |
|
● Inputs |
6 byte |
● Outputs |
4 byte |
Hardware configuration |
|
Automatic encoding |
Yes |
● Electronic coding element type F |
Yes |
Digital inputs |
|
Number of digital inputs |
8 |
Source/sink input |
Yes; P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Input voltage |
|
● Rated value (DC) |
24 V |
● for signal “0” |
-30 to +5 V |
● for signal “1” |
+15 to +30 V |
Input current |
|
● for signal “1”, typ. |
3.7 mA |
Input delay (for rated value of input voltage) |
|
for standard inputs |
|
— parameterizable |
Yes |
— at “0” to “1”, min. |
0.4 ms |
— at “0” to “1”, max. |
20 ms |
— at “1” to “0”, min. |
0.4 ms |
— at “1” to “0”, max. |
20 ms |
for technological functions |
|
— parameterizable |
No |
Cable length |
|
● shielded, max. |
1 000 m |
● unshielded, max. |
500 m |
Interrupts/diagnostics/status information |
|
Diagnostics function |
Yes |
Alarms |
|
● Diagnostic alarm |
Yes |
● Hardware interrupt |
No |
Diagnostics indication LED |
|
● RUN LED |
Yes; green LED |
● ERROR LED |
Yes; red LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
● Channel status display |
Yes; green LED |
● for channel diagnostics |
Yes; red LED |
● for module diagnostics |
Yes; green/red DIAG LED |
Potential separation |
|
Potential separation channels |
|
● between the channels |
No |
● between the channels and backplane bus |
Yes |
● between the channels and the power supply of the electronics |
No |
Isolation |
|
Isolation tested with |
707 V DC (type test) |
Standards, approvals, certificates |
|
Suitable for safety functions |
Yes |
Highest safety class achievable in safety mode |
|
● Performance level according to ISO 13849-1 |
PLe |
● Category according to ISO 13849-1 |
|
● SIL acc. to IEC 61508 |
SIL 3 |
Probability of failure (for service life of 20 years and repair time of 100 hours) |
|
— Low demand mode: PFDavg in accordance with SIL3 |
< 2.00E-05 |
— High demand/continuous mode: PFH in accordance with SIL3 |
< 1.00E-09 1/h |
Ambient conditions |
|
Ambient temperature during operation |
|
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C |
● vertical installation, min. |
0 °C |
● vertical installation, max. |
50 °C |
Altitude during operation relating to sea level |
|
● Installation altitude above sea level, max. |
4 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions |
|
Width |
15 mm |
Height |
73 mm |
Depth |
58 mm |
Weights |
|
Weight, approx. |
49 g |