Article number |
6ES7136-6DB00-0CA0 |
6ES7136-6DC00-0CA0 |
|
ET 200SP, El-Mod., F-DQ 4xDC 24V/2A |
ET 200SP, F-DQ 8x 24VDC/0.5A PP |
General information |
|
|
Product type designation |
F-DQ 4×24 V DC/2A HF |
F-DQ 8×24 V DC/0.5 A PP HF |
Firmware version |
|
|
● FW update possible |
|
Yes |
usable BaseUnits |
BU type A0 |
BU type A0 |
Color code for module-specific color identification plate |
|
CC02 |
Product function |
|
|
● I&M data |
Yes; I&M0 to I&M3 |
Yes; I&M0 to I&M3 |
Engineering with |
|
|
● STEP 7 TIA Portal configurable/integrated from version |
V12 |
V14 SP1 with HSP 202 |
● STEP 7 configurable/integrated from version |
V5.5 SP3 / – |
V5.5 SP4 HF5 |
● PROFINET from GSD version/GSD revision |
V2.31 |
V2.31 |
Supply voltage |
|
|
Rated value (DC) |
24 V |
24 V |
permissible range, lower limit (DC) |
20.4 V |
19.2 V |
permissible range, upper limit (DC) |
28.8 V |
28.8 V |
Reverse polarity protection |
Yes |
Yes |
power supply according to NEC Class 2 required |
No |
No |
Input current |
|
|
Current consumption (rated value) |
75 mA; without load |
75 mA; without load |
Current consumption, max. |
21 mA; From the backplane bus |
21 mA; From the backplane bus |
output voltage / header |
|
|
Rated value (DC) |
24 V |
24 V |
Power |
|
|
Power available from the backplane bus |
70 mW |
70 mW |
Power loss |
|
|
Power loss, typ. |
4 W |
3 W |
Address area |
|
|
Address space per module |
|
|
● Inputs |
5 byte |
6 byte; 5 bytes non-RIOforFA; 6 bytes RIOforFA |
● Outputs |
5 byte |
6 byte; 5 bytes non-RIOforFA; 6 bytes RIOforFA |
Hardware configuration |
|
|
Automatic encoding |
Yes |
Yes |
● Electronic coding element type F |
Yes |
Yes |
Digital outputs |
|
|
Type of digital output |
Transistor |
Transistor |
Number of digital outputs |
4 |
8 |
Digital outputs, parameterizable |
Yes |
Yes |
Short-circuit protection |
Yes |
Yes |
● Response threshold, typ. |
> 3.3 A |
Min. 0.7 A |
Open-circuit detection |
Yes |
No |
● Response threshold, typ. |
8 mA |
|
Overload protection |
Yes |
|
● Response threshold, typ. |
2.9 A |
|
Limitation of inductive shutdown voltage to |
Typ. -2x 47 V |
Typ. -39 V |
Controlling a digital input |
|
Yes |
Switching capacity of the outputs |
|
|
● with resistive load, max. |
2 A |
0.5 A |
● on lamp load, max. |
10 W |
2 W |
Load resistance range |
|
|
● lower limit |
12 Ω |
48 Ω |
● upper limit |
2 000 Ω |
12 000 Ω |
Output voltage |
|
|
● for signal “1”, min. |
24 V; L+ (-0.5 V) |
24 V; L+ (-0.5 V) |
Output current |
|
|
● for signal “1” rated value |
2 A |
0.5 A |
● for signal “0” residual current, max. |
0.5 mA |
0.5 mA |
Switching frequency |
|
|
● with resistive load, max. |
30 Hz; Symmetrical |
30 Hz; Symmetrical |
● with inductive load, max. |
0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
● with capacitive load, max. |
|
2 Hz; Symmetrical |
● on lamp load, max. |
10 Hz; Symmetrical |
10 Hz; Symmetrical |
Total current of the outputs |
|
|
● Current per channel, max. |
2 A; note derating data in the manual |
0.5 A; note derating data in the manual |
● Current per module, max. |
6 A; note derating data in the manual |
3 A; note derating data in the manual |
Total current of the outputs (per module) |
|
|
horizontal installation |
|
|
— up to 40 °C, max. |
|
3 A |
— up to 50 °C, max. |
|
2.5 A |
— up to 60 °C, max. |
|
2 A |
vertical installation |
|
|
— up to 50 °C, max. |
|
2 A |
Cable length |
|
|
● shielded, max. |
1 000 m |
100 m |
● unshielded, max. |
500 m |
100 m |
Interrupts/diagnostics/status information |
|
|
Diagnostics function |
Yes |
Yes |
Substitute values connectable |
No |
No |
Alarms |
|
|
● Diagnostic alarm |
Yes |
Yes |
Diagnostics indication LED |
|
|
● RUN LED |
Yes; green LED |
Yes; green LED |
● ERROR LED |
Yes; red LED |
Yes; red LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
Yes; green PWR LED |
● Channel status display |
Yes; green LED |
Yes; green LED |
● for channel diagnostics |
Yes; red LED |
Yes; red LED |
● for module diagnostics |
Yes; green/red DIAG LED |
Yes; green/red DIAG LED |
Potential separation |
|
|
Potential separation channels |
|
|
● between the channels |
No |
No |
● between the channels and backplane bus |
Yes |
Yes |
● between the channels and the power supply of the electronics |
No |
No |
Isolation |
|
|
Isolation tested with |
707 V DC (type test) |
707 V DC (type test) |
Standards, approvals, certificates |
|
|
Suitable for safety functions |
Yes |
Yes |
Highest safety class achievable in safety mode |
|
|
● Performance level according to ISO 13849-1 |
PLe |
PLe |
● Category according to ISO 13849-1 |
|
Cat. 4 |
● SIL acc. to IEC 61508 |
SIL 3 |
SIL 3 |
Probability of failure (for service life of 20 years and repair time of 100 hours) |
|
|
— Low demand mode: PFDavg in accordance with SIL2 |
< 2.00E-04 |
|
— Low demand mode: PFDavg in accordance with SIL3 |
< 2.00E-05 |
< 6.00E-05 |
— High demand/continuous mode: PFH in accordance with SIL2 |
< 1.00E-08 1/h |
|
— High demand/continuous mode: PFH in accordance with SIL3 |
< 1.00E-09 1/h |
< 2.00E-09 1/h |
Ambient conditions |
|
|
Ambient temperature during operation |
|
|
● horizontal installation, min. |
0 °C |
0 °C |
● horizontal installation, max. |
60 °C |
60 °C |
● vertical installation, min. |
0 °C |
0 °C |
● vertical installation, max. |
50 °C |
50 °C |
Altitude during operation relating to sea level |
|
|
● Installation altitude above sea level, max. |
4 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
4 000 m; with derating |
Dimensions |
|
|
Width |
15 mm |
15 mm |
Height |
73 mm |
73 mm |
Depth |
58 mm |
58 mm |
Weights |
|
|
Weight, approx. |
57 g |
48 g |