| Article number | 6AV3688-3AY36-0AX0 | 
|  | SIMATIC HMI KP8 PN | 
| General information |  | 
| Product type designation | KP8 PN | 
| Control elements |  | 
| With parameterizable keys | Yes | 
| Keyboard fonts |  | 
| ● Membrane keyboard |  | 
| — user-definable label membrane keys | Yes | 
| ● Function keys |  | 
| — Number of function keys | 8 | 
| ● Short-stroke keys |  | 
| — Number of short-stroke keys | 8 | 
| Expansions for operator control of the process |  | 
| ● DP direct LEDs (LEDs as S7 output I/O) | 8; Adjustable brightness | 
| ● Number of color modes for LED | 5; red, green, blue, yellow, white | 
| ● Direct keys (keys as S7 input I/O) | 8 | 
| Installation type/mounting |  | 
| Mounting type | Mounting clip | 
| Mounting position | vertical | 
| Rack mounting | No | 
| Front mounting | Yes; Compatible with Extension Units dimensions | 
| Rail mounting | No | 
| Wall mounting/direct mounting | No | 
| Mounting in portrait format possible | Yes | 
| Mounting in landscape format possible | Yes | 
| maximum permissible angle of inclination without external ventilation | 30°; To the front/rear | 
| Number of slots for command devices and signaling units | 0 | 
| Supply voltage |  | 
| Type of supply voltage | DC | 
| Rated value (DC) | 24 V; 24 V can be looped through connector, interrupted when pulled | 
| permissible range, lower limit (DC) | 20.4 V | 
| permissible range, upper limit (DC) | 28.8 V | 
| Input current |  | 
| Current consumption (rated value) | 0.3 A | 
| Type of output |  | 
| LED colors |  | 
| ● red | Yes | 
| ● yellow | Yes | 
| ● green | Yes | 
| ● white | Yes | 
| ● blue | Yes | 
| Digital inputs |  | 
| Number of digital inputs | 8; Total inputs and outputs max. 8 and 1x SIL 2 or 2x SIL 3 | 
| Input voltage |  | 
| ● Rated value (DC) | 24 V | 
| Digital outputs |  | 
| Number of digital outputs | 8; Max. 8 inputs and outputs (total) | 
| Short-circuit protection | Yes | 
| Switching capacity of the outputs |  | 
| ● with resistive load, max. | 100 mA | 
| Output voltage |  | 
| ● Rated value (DC) | 24 V; Non-isolated | 
| Total current of the outputs |  | 
| ● Current per channel, max. | 100 mA | 
| ● Current per group, max. | 800 mA | 
| Interfaces |  | 
| Number of industrial Ethernet interfaces | 2; For the construction of lines and rings without external switch | 
| Number of PROFINET interfaces | 2; Incl. switch | 
| Industrial Ethernet |  | 
| ● Industrial Ethernet status LED | 2; Per port | 
| ● Number of ports of the integrated switch | 2; Per port | 
| Protocols |  | 
| PROFINET | Yes; also 3rd party PLC | 
| Supports protocol for PROFINET IO | Yes | 
| PROFINET CBA | No | 
| IRT | Yes | 
| PROFIsafe | No | 
| PROFIBUS | No | 
| EtherNet/IP | No | 
| MPI | No | 
| AS-Interface | No | 
| EIB/KNX | No | 
| Protocols (Ethernet) |  | 
| ● TCP/IP | No | 
| Redundancy mode |  | 
| Media redundancy |  | 
| — MRP | Yes | 
| Further protocols |  | 
| ● AS-Interface Safety at Work | No | 
| ● CAN | No | 
| ● Data-Highway | No | 
| ● DeviceNet | No | 
| ● DeviceNet Safety | No | 
| ● Foundation Fieldbus | No | 
| ● INTERBUS | No | 
| ● INTERBUS-Safety | No | 
| ● Local Operating Network | No | 
| ● MODBUS | No | 
| ● SafetyBUS p | No | 
| ● SERCOS | No | 
| ● SUCOnet | No | 
| ● other bus systems | No | 
| Test commissioning functions |  | 
| Illuminant test | Yes; During switch on | 
| Key and signal lamp test | Yes; automatically when switching on | 
| EMC |  | 
| Emission of radio interference acc. to EN 55 011 |  | 
| ● Limit class A, for use in industrial areas | Yes; Group 1, measured at a distance of 10 m | 
| ● Limit class B, for use in residential areas | No | 
| Degree and class of protection |  | 
| IP (at the front) | IP65 | 
| IP (rear) | IP20 | 
| NEMA (front) |  | 
| ● Enclosure Type 4 at the front | No | 
| ● Enclosure Type 4x at the front | Yes; Incl. NEMA12 | 
| ● Enclosure Type 12 at the front |  | 
| Standards, approvals, certificates |  | 
| CE mark | Yes | 
| CSA approval |  | 
| UL approval |  | 
| cULus | Yes | 
| FM approval |  | 
| RCM (formerly C-TICK) | Yes | 
| KC approval | Yes | 
| EAC (formerly Gost-R) | Yes | 
| CCC |  | 
| Suitable for safety functions | Yes | 
| Marine approval |  | 
| Use in hazardous areas |  | 
| ● ATEX Zone 2 | Yes | 
| ● ATEX Zone 22 | Yes | 
| ● cULus Class I Zone 1 | No | 
| ● cULus Class I Zone 2, Division 2 | Yes | 
| ● FM Class I Division 2 | Yes | 
| Marine approval |  | 
| ● Germanischer Lloyd (GL) | No | 
| ● American Bureau of Shipping (ABS) | No | 
| ● Bureau Veritas (BV) | No | 
| ● Det Norske Veritas (DNV) | No | 
| ● Lloyds Register of Shipping (LRS) | No | 
| ● Nippon Kaiji Kyokai (Class NK) | No | 
| ● Polski Rejestr Statkow (PRS) | No | 
| Ambient conditions |  | 
| Ambient temperature during operation |  | 
| ● min. | 0 °C | 
| ● max. | 55 °C | 
| Operation (vertical installation) |  | 
| — For vertical installation, min. | 0 °C | 
| — For vertical installation, max. | 55 °C | 
| Operation (max. tilt angle) |  | 
| — At maximum tilt angle, min. | 0 °C | 
| — At maximum tilt angle, max. | 45 °C | 
| Operation (vertical installation, portrait format) |  | 
| — For vertical installation, min. | 0 °C | 
| — For vertical installation, max. | 55 °C | 
| Operation (max. tilt angle, portrait format) |  | 
| — At maximum tilt angle, min. | 0 °C | 
| — At maximum tilt angle, max. | 45 °C | 
| Ambient temperature during storage/transportation |  | 
| ● min. | -20 °C | 
| ● max. | 60 °C | 
| Relative humidity |  | 
| ● Operation, max. | 95 %; no condensation | 
| configuration / header |  | 
| Configuration software |  | 
| ● STEP 7 Basic (TIA Portal) | Yes | 
| ● STEP 7 Professional (TIA Portal) | Yes | 
| Functionality under WinCC (TIA Portal) |  | 
| Process coupling |  | 
| ● S7-1200 | Yes; with ET 200pro CPU and ET 200S CPU | 
| ● S7-1500 | Yes | 
| ● S7-200 | No | 
| ● S7-300/400 | Yes; with F-CPU: STEP 7 V11 SP1 (or higher) and Safety V11 (or higher) or SIMATIC STEP 7 Basic V11 (or higher) | 
| ● LOGO! | No | 
| ● WinAC | Yes | 
| ● SINUMERIK | No | 
| ● SIMOTION | No | 
| ● Allen Bradley (EtherNet/IP) | No | 
| ● Allen Bradley (DF1) | No | 
| ● Mitsubishi (MC TCP/IP) | No | 
| ● Mitsubishi (FX) | No | 
| ● OMRON (FINS TCP) | No | 
| ● OMRON (LINK/Multilink) | No | 
| ● Modicon (Modbus TCP/IP) | No | 
| ● Modicon (Modbus) | No | 
| Mechanics/material |  | 
| Enclosure material (front) |  | 
| ● Plastic | Yes | 
| ● Aluminum | No | 
| ● Stainless steel | No | 
| Service life |  | 
| ● Short-stroke keys (in switching cycles) | 1 500 000 | 
| ● LEDs (ON period) | 100 % | 
| Dimensions |  | 
| Width of the housing front | 98 mm | 
| Height of housing front | 155 mm | 
| Mounting cutout, width | 68 mm; Max. thickness of mounting plate 2 – 6 mm | 
| Mounting cutout, height | 129 mm | 
| Overall depth | 49 mm; Incl. angled SIMATIC Ethernet connector | 
| Weights |  | 
| Weight (without packaging) | 280 g | 
| Weight (with packaging) |  | 
| Other |  | 
| Merchandise |  | 
| Manufacturer name |  | 
| Manufacturer’s address |  | 
| Note: |  |