Article number |
6ES7226-6RA32-0XB0 |
|
Digital Output SM 1226, F-DQ 2x Relay |
General information |
|
Product type designation |
SM 1226, F-DQ 2x relay/5 A |
Supply voltage |
|
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
power supply according to NEC Class 2 required |
No |
Input current |
|
from backplane bus 5 V DC, max. |
120 mA |
Digital outputs |
|
● from load voltage L+, max. |
300 mA |
Power loss |
|
Power loss, typ. |
10 W |
Digital outputs |
|
Number of digital outputs |
2 |
Short-circuit protection |
No |
Output voltage |
|
● Rated value (DC) |
5 V DC to 30 V DC |
● Rated value (AC) |
5 V AC to 250 V AC |
Output current |
|
● for signal “1” permissible range, max. |
5 A maximum per circuit and 10 A maximum of all circuits per module |
Relay outputs |
|
● Number of relay outputs |
2; 2 circuits per output |
Switching capacity of contacts |
|
— with inductive load, max. |
0.1 Hz, accordance with IEC 60947-5-1, DC-13; 2 Hz, accordance with IEC 60947-5-1, AC-15 |
— with resistive load, max. |
2 Hz |
Cable length |
|
● shielded, max. |
200 m |
● unshielded, max. |
200 m |
Interrupts/diagnostics/status information |
|
Diagnostics indication LED |
|
● for status of the outputs |
Yes |
Degree and class of protection |
|
IP degree of protection |
IP20 |
Standards, approvals, certificates |
|
CE mark |
Yes |
cULus |
Yes |
FM approval |
Yes |
Highest safety class achievable in safety mode |
|
● Performance level according to ISO 13849-1 |
Category 4, PL e |
● SIL acc. to IEC 61508 |
SIL 3 |
Probability of failure (for service life of 20 years and repair time of 100 hours) |
|
— Low demand mode: PFDavg in accordance with SIL3 |
< 1.00E-05 |
— High demand/continuous mode: PFH in accordance with SIL3 |
< 4.00E-09 |
Ambient conditions |
|
Free fall |
|
● Fall height, max. |
0.3 m; five times, in product package |
Ambient temperature during operation |
|
● min. |
0 °C |
● max. |
55 °C |
● permissible temperature change |
5°C to 55°C, 3°C / minute |
Ambient temperature during storage/transportation |
|
● min. |
-40 °C |
● max. |
70 °C |
Air pressure acc. to IEC 60068-2-13 |
|
● Storage/transport, min. |
660 hPa |
● Storage/transport, max. |
1 080 hPa |
Relative humidity |
|
● Operation at 25 ℃ without condensation, max. |
95 % |
Mechanics/material |
|
Enclosure material (front) |
|
● Plastic |
Yes |
Dimensions |
|
Width |
70 mm |
Height |
100 mm |
Depth |
75 mm |
Weights |
|
Weight, approx. |
300 g |