Analog input modules record process signals such as pressure or temperature and forward them in digitalized format (16-bit format) to the PLC. They are suitable for measuring current (2-wire and 4-wire transducers), voltage, and resistance, as well as for the connection of resistance thermometers and thermocouples (measurement types depend on the module).
The following analog input modules are available:
| Article number | 6ES7531-7QD00-0AB0 | 6ES7531-7KF00-0AB0 | 6ES7531-7NF10-0AB0 | 6ES7531-7NF00-0AB0 | |
| S7-1500, AI 4xU/I/RTD/TC ST | S7-1500, AI 8xU/I/RTD/TC ST | S7-1500, AI 8xU/I HS | S7-1500, AI 8xU/I HF | ||
| General information | |||||
| Product type designation | AI 4xU/I/RTD/TC ST | AI 8xU/I/RTD/TC ST | AI 8xU/I HS | AI 8xU/I HF | |
| HW functional status | From FS01 | FS04 | From FS01 | From FS01 | |
| Firmware version | V1.0.0 | V2.0.0 | V2.1.0 | V1.1.0 | |
| ● FW update possible | Yes | Yes | Yes | Yes | |
| Product function | |||||
| ● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | |
| ● Isochronous mode | No | No | Yes | No | |
| ● Prioritized startup | No | No | Yes | Yes | |
| ● Measuring range scalable | No | No | No | No | |
| ● Scalable measured values | No | No | No | Yes | |
| ● Adjustment of measuring range | No | No | No | Yes | |
| Engineering with | |||||
| ● STEP 7 TIA Portal configurable/integrated from version | V13 / V13.0.2 | V12 / V12 | V14 / – | V14 / – | |
| ● STEP 7 configurable/integrated from version | V5.5 SP3 / – | V5.5 SP3 / – | V5.5 SP3 / – | V5.5 SP3 / – | |
| ● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 | |
| ● PROFINET from GSD version/GSD revision | V2.3 / – | V2.3 / – | V2.3 / – | V2.3 / – | |
| Operating mode | |||||
| ● Oversampling | No | No | Yes | No | |
| ● MSI | Yes | Yes | Yes | Yes | |
| CiR – Configuration in RUN | |||||
| Reparameterization possible in RUN | Yes | Yes | Yes | Yes | |
| Calibration possible in RUN | Yes | Yes | Yes | Yes | |
| Supply voltage | |||||
| Rated value (DC) | 24 V | 24 V | 24 V | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | 19.2 V | 19.2 V | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | 28.8 V | |
| Reverse polarity protection | Yes | Yes | Yes | Yes | |
| Input current | |||||
| Current consumption, max. | 165 mA | 240 mA; with 24 V DC supply | 240 mA; with 24 V DC supply | 50 mA; with 24 V DC supply | |
| Encoder supply | |||||
| 24 V encoder supply | |||||
| ● Short-circuit protection | Yes | Yes | Yes | ||
| ● Output current, max. | 20 mA; Max. 47 mA per channel for a duration < 10 s | 20 mA; Max. 47 mA per channel for a duration < 10 s | 20 mA; Max. 47 mA per channel for a duration < 10 s | ||
| Power | |||||
| Power available from the backplane bus | 0.7 W | 0.7 W | 1.15 W | 0.85 W | |
| Power loss | |||||
| Power loss, typ. | 2.3 W | 2.7 W | 3.4 W | 1.9 W | |
| Analog inputs | |||||
| Number of analog inputs | 4 | 8 | 8 | 8 | |
| ● For current measurement | 4 | 8 | 8 | 8 | |
| ● For voltage measurement | 4 | 8 | 8 | 8 | |
| ● For resistance/resistance thermometer measurement | 2 | 4 | |||
| ● For thermocouple measurement | 4 | 8 | |||
| permissible input voltage for voltage input (destruction limit), max. | 28.8 V | 28.8 V | 28.8 V | 28.8 V | |
| permissible input current for current input (destruction limit), max. | 40 mA | 40 mA | 40 mA | 40 mA | |
| Constant measurement current for resistance-type transmitter, typ. | 150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA | 150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA | |||
| Technical unit for temperature measurement adjustable | Yes; °C/°F/K | Yes; °C/°F/K | |||
| Analog input with oversampling | No | ||||
| Standardization of measured values | No | ||||
| Input ranges (rated values), voltages | |||||
| ● 0 to +5 V | No | No | No | No | |
| ● 0 to +10 V | No | No | No | No | |
| ● 1 V to 5 V | Yes | Yes | Yes | Yes | |
| — Input resistance (1 V to 5 V) | 100 kΩ | 100 kΩ | 50 kΩ | 100 kΩ | |
| ● -1 V to +1 V | Yes | Yes | |||
| — Input resistance (-1 V to +1 V) | 10 MΩ | 10 MΩ | |||
| ● -10 V to +10 V | Yes | Yes | Yes | Yes | |
| — Input resistance (-10 V to +10 V) | 100 kΩ | 100 kΩ | 100 kΩ | 100 kΩ | |
| ● -2.5 V to +2.5 V | Yes | Yes | No | Yes | |
| — Input resistance (-2.5 V to +2.5 V) | 10 MΩ | 10 MΩ | 100 kΩ | ||
| ● -25 mV to +25 mV | No | No | No | No | |
| ● -250 mV to +250 mV | Yes | Yes | No | No | |
| — Input resistance (-250 mV to +250 mV) | 10 MΩ | 10 MΩ | |||
| ● -5 V to +5 V | Yes | Yes | Yes | Yes | |
| — Input resistance (-5 V to +5 V) | 100 kΩ | 100 kΩ | 50 kΩ | 100 kΩ | |
| ● -50 mV to +50 mV | Yes | Yes | No | No | |
| — Input resistance (-50 mV to +50 mV) | 10 MΩ | 10 MΩ | |||
| ● -500 mV to +500 mV | Yes | Yes | No | No | |
| — Input resistance (-500 mV to +500 mV) | 10 MΩ | 10 MΩ | |||
| ● -80 mV to +80 mV | Yes | Yes | No | No | |
| — Input resistance (-80 mV to +80 mV) | 10 MΩ | 10 MΩ | |||
| Input ranges (rated values), currents | |||||
| ● 0 to 20 mA | Yes | Yes | Yes | Yes | |
| — Input resistance (0 to 20 mA) | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | |
| ● -20 mA to +20 mA | Yes | Yes | Yes | Yes | |
| — Input resistance (-20 mA to +20 mA) | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | |
| ● 4 mA to 20 mA | Yes | Yes | Yes | Yes | |
| — Input resistance (4 mA to 20 mA) | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC | |
| Input ranges (rated values), thermocouples | |||||
| ● Type B | Yes | Yes | No | No | |
| — Input resistance (Type B) | 10 MΩ | 10 MΩ | |||
| ● Type C | No | No | No | No | |
| ● Type E | Yes | Yes | No | No | |
| — Input resistance (Type E) | 10 MΩ | 10 MΩ | |||
| ● Type J | Yes | Yes | No | No | |
| — Input resistance (type J) | 10 MΩ | 10 MΩ | |||
| ● Type K | Yes | Yes | No | No | |
| — Input resistance (Type K) | 10 MΩ | 10 MΩ | |||
| ● Type L | No | No | No | No | |
| ● Type N | Yes | Yes | No | No | |
| — Input resistance (Type N) | 10 MΩ | 10 MΩ | |||
| ● Type R | Yes | Yes | No | No | |
| — Input resistance (Type R) | 10 MΩ | 10 MΩ | |||
| ● Type S | Yes | Yes | No | No | |
| — Input resistance (Type S) | 10 MΩ | 10 MΩ | |||
| ● Type T | Yes | Yes | No | No | |
| — Input resistance (Type T) | 10 MΩ | 10 MΩ | |||
| ● Type U | No | ||||
| ● Type TXK/TXK(L) to GOST | No | No | No | No | |
| Input ranges (rated values), resistance thermometer | |||||
| ● Cu 10 | No | No | No | No | |
| ● Cu 10 according to GOST | No | No | No | No | |
| ● Cu 50 | No | No | No | No | |
| ● Cu 50 according to GOST | No | No | No | No | |
| ● Cu 100 | No | No | No | No | |
| ● Cu 100 according to GOST | No | No | No | No | |
| ● Ni 10 | No | No | No | No | |
| ● Ni 10 according to GOST | No | No | No | No | |
| ● Ni 100 | Yes; Standard/climate | Yes; Standard/climate | No | No | |
| — Input resistance (Ni 100) | 10 MΩ | 10 MΩ | |||
| ● Ni 100 according to GOST | No | No | No | No | |
| ● Ni 1000 | Yes; Standard/climate | Yes; Standard/climate | No | No | |
| — Input resistance (Ni 1000) | 10 MΩ | 10 MΩ | |||
| ● Ni 1000 according to GOST | No | No | No | No | |
| ● LG-Ni 1000 | Yes; Standard/climate | Yes; Standard/climate | No | No | |
| — Input resistance (LG-Ni 1000) | 10 MΩ | 10 MΩ | |||
| ● Ni 120 | No | No | No | No | |
| ● Ni 120 according to GOST | No | No | No | No | |
| ● Ni 200 | No | No | No | ||
| ● Ni 200 according to GOST | No | No | No | No | |
| ● Ni 500 | No | No | No | No | |
| ● Ni 500 according to GOST | No | No | No | No | |
| ● Pt 10 | No | No | No | No | |
| ● Pt 10 according to GOST | No | No | No | No | |
| ● Pt 50 | No | No | No | No | |
| ● Pt 50 according to GOST | No | No | No | No | |
| ● Pt 100 | Yes; Standard/climate | Yes; Standard/climate | No | No | |
| — Input resistance (Pt 100) | 10 MΩ | 10 MΩ | |||
| ● Pt 100 according to GOST | No | No | No | No | |
| ● Pt 1000 | Yes; Standard/climate | Yes; Standard/climate | No | No | |
| — Input resistance (Pt 1000) | 10 MΩ | 10 MΩ | |||
| ● Pt 1000 according to GOST | No | No | No | No | |
| ● Pt 200 | Yes; Standard/climate | Yes; Standard/climate | No | No | |
| — Input resistance (Pt 200) | 10 MΩ | 10 MΩ | |||
| ● Pt 200 according to GOST | No | No | No | No | |
| ● Pt 500 | Yes; Standard/climate | Yes; Standard/climate | No | No | |
| — Input resistance (Pt 500) | 10 MΩ | 10 MΩ | |||
| ● Pt 500 according to GOST | No | No | No | No | |
| Input ranges (rated values), resistors | |||||
| ● 0 to 150 ohms | Yes | Yes | No | No | |
| — Input resistance (0 to 150 ohms) | 10 MΩ | 10 MΩ | |||
| ● 0 to 300 ohms | Yes | Yes | No | No | |
| — Input resistance (0 to 300 ohms) | 10 MΩ | 10 MΩ | |||
| ● 0 to 600 ohms | Yes | Yes | No | No | |
| — Input resistance (0 to 600 ohms) | 10 MΩ | 10 MΩ | |||
| ● 0 to 3000 ohms | No | No | No | No | |
| ● 0 to 6000 ohms | Yes | Yes | No | No | |
| — Input resistance (0 to 6000 ohms) | 10 MΩ | 10 MΩ | |||
| ● PTC | Yes | Yes | No | No | |
| — Input resistance (PTC) | 10 MΩ | 10 MΩ | |||
| Thermocouple (TC) | |||||
| Temperature compensation | |||||
| — parameterizable | Yes | Yes | |||
| — internal temperature compensation | Yes | Yes | |||
| — external temperature compensation via RTD | Yes | Yes | |||
| — Compensation for 0 °C reference point temperature | Yes; fixed value can be set | Yes; fixed value can be set | |||
| — Reference channel of the module | No | Yes | |||
| Cable length | |||||
| ● shielded, max. | 800 m; for U/I, 200 m for R/RTD, 50 m for TC | 800 m; for U/I, 200 m for R/RTD, 50 m for TC | 800 m | 800 m | |
| Analog value generation for the inputs | |||||
| Measurement principle | |||||
| Integration and conversion time/resolution per channel | |||||
| ● Resolution with overrange (bit including sign), max. | 16 bit | 16 bit | 16 bit | 24 bit; When using the function “Scaling of the measured values” or “Measuring range adaptation” (32 bit REAL format); 16 bit when using the S7 format (16 bit INTEGER) | |
| ● Integration time, parameterizable | Yes | Yes | Yes | ||
| ● Integration time (ms) | 2,5 / 16,67 / 20 / 100 ms | 2,5 / 16,67 / 20 / 100 ms | Fast mode: 2.5 / 16.67 / 20 / 100 ms, standard mode: 7.5 / 50 / 60 / 300 ms | ||
| ● Basic conversion time, including integration time (ms) | 9 / 23 / 27 / 107 ms | 9 / 23 / 27 / 107 ms | Fast mode: 4 / 18 / 22 / 102 ms; Standard mode: 9 / 52 / 62 / 302 ms | ||
| — additional conversion time for wire-break monitoring | 9 ms (to be considered in R/RTD/TC measurement) | 9 ms (to be considered in R/RTD/TC measurement) | |||
| — additional conversion time for resistance measurement | 150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms | 150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms | |||
| ● Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 | 400 / 60 / 50 / 10 Hz | 400 / 60 / 50 / 10 Hz | ||
| ● Basic execution time of the module (all channels released) | 62.5 µs; independent of number of activated channels | Corresponds to the channel with the highest basic conversion time | |||
| ● Time for offset calibration (per module) | Basic conversion time of the slowest channel | Basic conversion time of the slowest channel | |||
| Smoothing of measured values | |||||
| ● parameterizable | Yes | Yes | Yes | Yes | |
| ● Step: None | Yes | Yes | Yes | Yes | |
| ● Step: low | Yes | Yes | Yes | Yes | |
| ● Step: Medium | Yes | Yes | Yes | Yes | |
| ● Step: High | Yes | Yes | Yes | Yes | |
| Encoder | |||||
| Connection of signal encoders | |||||
| ● for voltage measurement | Yes | Yes | Yes | Yes | |
| ● for current measurement as 2-wire transducer | Yes | Yes | Yes | Yes; with external transmitter supply | |
| — Burden of 2-wire transmitter, max. | 820 Ω | 820 Ω | 820 Ω | ||
| ● for current measurement as 4-wire transducer | Yes | Yes | Yes | Yes | |
| ● for resistance measurement with two-wire connection | Yes; Only for PTC | Yes; Only for PTC | No | No | |
| ● for resistance measurement with three-wire connection | Yes; All measuring ranges except PTC; internal compensation of the cable resistances | Yes; All measuring ranges except PTC; internal compensation of the cable resistances | No | No | |
| ● for resistance measurement with four-wire connection | Yes; All measuring ranges except PTC | Yes; All measuring ranges except PTC | No | No | |
| Errors/accuracies | |||||
| Linearity error (relative to input range), (+/-) | 0.02 % | 0.02 % | 0.02 % | 0.02 % | |
| Temperature error (relative to input range), (+/-) | 0.005 %/K; With TC type T 0.02 ± % / K | 0.005 %/K; With TC type T 0.02 ± % / K | 0.005 %/K | 0.005 %/K | |
| Crosstalk between the inputs, max. | -80 dB | -80 dB | -60 dB | -80 dB | |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.02 % | 0.02 % | 0.02 % | 0.02 % | |
| Temperature error of internal compensation | ±6 °C | ±6 °C | |||
| note regarding accuracy | at temperatures below 0 °C, the figures for operating error and temperature error are doubled | at temperatures below 0 °C, the figures for operating error and temperature error are doubled | |||
| Operational error limit in overall temperature range | |||||
| ● Voltage, relative to input range, (+/-) | 0.3 % | 0.3 % | 0.3 % | 0.1 % | |
| ● Current, relative to input range, (+/-) | 0.3 % | 0.3 % | 0.3 % | 0.1 % | |
| ● Resistance, relative to input range, (+/-) | 0.3 % | 0.3 % | |||
| ● Resistance thermometer, relative to input range, (+/-) | 0.3 %; Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K | Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K | |||
| ● Thermocouple, relative to input range, (+/-) | 0.3 %; Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K | Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K | |||
| Basic error limit (operational limit at 25 °C) | |||||
| ● Voltage, relative to input range, (+/-) | 0.1 % | 0.1 % | 0.2 % | 0.05 % | |
| ● Current, relative to input range, (+/-) | 0.1 % | 0.1 % | 0.2 % | 0.05 % | |
| ● Resistance, relative to input range, (+/-) | 0.1 % | 0.1 % | |||
| ● Resistance thermometer, relative to input range, (+/-) | 0.1 %; Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K | Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K | |||
| ● Thermocouple, relative to input range, (+/-) | 0.1 %; Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K | Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K | |||
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |||||
| ● Series mode interference (peak value of interference < rated value of input range), min. | 40 dB | 40 dB | 80 dB; in the Standard operating mode, 40 dB in the Fast operating mode | ||
| ● Common mode voltage, max. | 10 V | 10 V | 10 V | 60 V DC/30 V AC | |
| ● Common mode interference, min. | 60 dB | 60 dB | 50 dB at 400 Hz; 60 dB at 60 / 50 / 10 Hz | 80 dB | |
| Isochronous mode | |||||
| Filtering and processing time (TCI), min. | 80 µs | ||||
| Bus cycle time (TDP), min. | 250 µs | ||||
| Interrupts/diagnostics/status information | |||||
| Diagnostics function | Yes | Yes | Yes | Yes | |
| Alarms | |||||
| ● Diagnostic alarm | Yes | Yes | Yes | Yes | |
| ● Limit value alarm | Yes; two upper and two lower limit values in each case | Yes; two upper and two lower limit values in each case | Yes; two upper and two lower limit values in each case | Yes; two upper and two lower limit values in each case | |
| Diagnoses | |||||
| ● Monitoring the supply voltage | Yes | Yes | Yes | Yes | |
| ● Wire-break | Yes; Only for 1 to 5 V, 4 to 20 mA, TC, R, and RTD | Yes; Only for 1 to 5 V, 4 to 20 mA, TC, R, and RTD | Yes; only for 1 … 5 V and 4 … 20 mA | Yes; only for 1 … 5 V and 4 … 20 mA | |
| ● Short-circuit | |||||
| ● Group error | |||||
| ● Overflow/underflow | Yes | Yes | Yes | Yes | |
| Diagnostics indication LED | |||||
| ● RUN LED | Yes; green LED | Yes; green LED | Yes; green LED | Yes; green LED | |
| ● ERROR LED | Yes; red LED | Yes; red LED | Yes; red LED | Yes; red LED | |
| ● MAINT LED | |||||
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green LED | Yes; green LED | Yes; green LED | Yes; green LED | |
| ● Channel status display | Yes; green LED | Yes; green LED | Yes; green LED | Yes; green LED | |
| ● for channel diagnostics | Yes; red LED | Yes; red LED | Yes; red LED | Yes; red LED | |
| ● for module diagnostics | Yes; red LED | Yes; red LED | Yes; red LED | Yes; red LED | |
| Potential separation | |||||
| Potential separation channels | |||||
| ● between the channels | No | No | No | Yes | |
| ● between the channels, in groups of | 4 | 8 | 8 | 1 | |
| ● between the channels and backplane bus | Yes | Yes | Yes | Yes | |
| ● between the channels and the power supply of the electronics | Yes | Yes | Yes | Yes | |
| Permissible potential difference | |||||
| between different circuits | 60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels | ||||
| between the inputs (UCM) | 20 V DC | 20 V DC | 20 V DC | ||
| Between the inputs and MANA (UCM) | 10 V DC | 10 V DC | 10 V DC | ||
| Isolation | |||||
| Isolation tested with | 707 V DC (type test) | 707 V DC (type test) | 707 V DC (type test) | 2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus | |
| Standards, approvals, certificates | |||||
| Suitable for applications according to AMS 2750 | Yes; Declaration of Conformity, see online support entry 109757262 | ||||
| Suitable for applications according to CQI-9 | Yes; Based on AMS 2750 E | ||||
| Ambient conditions | |||||
| Ambient temperature during operation | |||||
| ● horizontal installation, min. | -25 °C; From FS03 | 0 °C | -25 °C; From FS02 | -30 °C; From FS02 | |
| ● horizontal installation, max. | 60 °C | 60 °C | 60 °C | 60 °C | |
| ● vertical installation, min. | -25 °C; From FS03 | 0 °C | -25 °C; From FS02 | -30 °C; From FS02 | |
| ● vertical installation, max. | 40 °C | 40 °C | 40 °C | 40 °C | |
| Altitude during operation relating to sea level | |||||
| ● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | ||
| Dimensions | |||||
| Width | 25 mm | 35 mm | 35 mm | 35 mm | |
| Height | 147 mm | 147 mm | 147 mm | 147 mm | |
| Depth | 129 mm | 129 mm | 129 mm | 129 mm | |
| Weights | |||||
| Weight, approx. | 210 g | 310 g | 300 g | 280 g | |
| Other | |||||
| Note: | Supplied incl. 40-pole push-in front connectors. Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 Ohms (±0.02%); resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermoelement: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K | Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 ohms ±0.02%; resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermocouple: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K | |||
| Article number | 6ES7531-7PF00-0AB0 | |
| S7-1500, AI 8 X U/R/RTD/TC HF | ||
| General information | ||
| Product type designation | AI 8xU/R/RTD/TC HF | |
| HW functional status | FS01 | |
| Firmware version | V1.1.0 | |
| ● FW update possible | Yes | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | |
| ● Isochronous mode | No | |
| ● Prioritized startup | Yes | |
| ● Measuring range scalable | Yes | |
| ● Scalable measured values | No | |
| ● Adjustment of measuring range | No | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | V14 / – | |
| ● STEP 7 configurable/integrated from version | V5.5 SP3 / – | |
| ● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 | |
| ● PROFINET from GSD version/GSD revision | V2.3 / – | |
| Operating mode | ||
| ● Oversampling | No | |
| ● MSI | Yes | |
| CiR – Configuration in RUN | ||
| Reparameterization possible in RUN | Yes | |
| Calibration possible in RUN | Yes | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Input current | ||
| Current consumption, max. | 55 mA; with 24 V DC supply | |
| Power | ||
| Power available from the backplane bus | 0.85 W | |
| Power loss | ||
| Power loss, typ. | 1.9 W | |
| Analog inputs | ||
| Number of analog inputs | 8; Plus one additional RTD (reference) channel | |
| ● For voltage measurement | 8; Plus one additional RTD (reference) channel | |
| ● For resistance/resistance thermometer measurement | 8; Plus one additional RTD (reference) channel | |
| ● For thermocouple measurement | 8; Plus one additional RTD (reference) channel | |
| permissible input voltage for voltage input (destruction limit), max. | 20 V | |
| Constant measurement current for resistance-type transmitter, typ. | 150 Ohm, 300 Ohm, 600 Ohm, Cu10, Cu50, Cu100, Ni10, Ni100, Ni120, Ni200, Pt10, Pt50, Pt100, Pt200 climate: 1 mA; 6 kOhm, Ni500, Ni1000, LG-Ni1000, Pt200 standard, Pt500, Pt1000, PTC: 0.25 mA | |
| Technical unit for temperature measurement adjustable | Yes; °C/°F/K | |
| Input ranges (rated values), voltages | ||
| ● 0 to +5 V | No | |
| ● 0 to +10 V | No | |
| ● 1 V to 5 V | No | |
| ● -1 V to +1 V | Yes | |
| — Input resistance (-1 V to +1 V) | 10 MΩ | |
| ● -10 V to +10 V | No | |
| ● -2.5 V to +2.5 V | No | |
| ● -25 mV to +25 mV | Yes | |
| — Input resistance (-25 mV to +25 mV) | 10 MΩ | |
| ● -250 mV to +250 mV | Yes | |
| — Input resistance (-250 mV to +250 mV) | 10 MΩ | |
| ● -5 V to +5 V | No | |
| ● -50 mV to +50 mV | Yes | |
| — Input resistance (-50 mV to +50 mV) | 10 MΩ | |
| ● -500 mV to +500 mV | Yes | |
| — Input resistance (-500 mV to +500 mV) | 10 MΩ | |
| ● -80 mV to +80 mV | Yes | |
| — Input resistance (-80 mV to +80 mV) | 10 MΩ | |
| Input ranges (rated values), currents | ||
| ● 0 to 20 mA | No | |
| ● -20 mA to +20 mA | No | |
| ● 4 mA to 20 mA | No | |
| Input ranges (rated values), thermocouples | ||
| ● Type B | Yes | |
| — Input resistance (Type B) | 10 MΩ | |
| ● Type C | Yes | |
| — Input resistance (Type C) | 10 MΩ | |
| ● Type E | Yes | |
| — Input resistance (Type E) | 10 MΩ | |
| ● Type J | Yes | |
| — Input resistance (type J) | 10 MΩ | |
| ● Type K | Yes | |
| — Input resistance (Type K) | 10 MΩ | |
| ● Type L | No | |
| ● Type N | Yes | |
| — Input resistance (Type N) | 10 MΩ | |
| ● Type R | Yes | |
| — Input resistance (Type R) | 10 MΩ | |
| ● Type S | Yes | |
| — Input resistance (Type S) | 10 MΩ | |
| ● Type T | Yes | |
| — Input resistance (Type T) | 10 MΩ | |
| ● Type TXK/TXK(L) to GOST | Yes | |
| — Input resistance (Type TXK/TXK(L) to GOST) | 10 MΩ | |
| Input ranges (rated values), resistance thermometer | ||
| ● Cu 10 | Yes; Standard/climate | |
| — Input resistance (Cu 10) | 10 MΩ | |
| ● Cu 10 according to GOST | Yes; Standard/climate | |
| — Input resistance (Cu 10 according to GOST) | 10 MΩ | |
| ● Cu 50 | Yes; Standard/climate | |
| — Input resistance (Cu 50) | 10 MΩ | |
| ● Cu 50 according to GOST | Yes; Standard/climate | |
| — Input resistance (Cu 50 according to GOST) | 10 MΩ | |
| ● Cu 100 | Yes; Standard/climate | |
| — Input resistance (Cu 100) | 10 MΩ | |
| ● Cu 100 according to GOST | Yes; Standard/climate | |
| — Input resistance (Cu 100 according to GOST) | 10 MΩ | |
| ● Ni 10 | Yes; Standard/climate | |
| — Input resistance (Ni 10) | 10 MΩ | |
| ● Ni 10 according to GOST | Yes; Standard/climate | |
| — Input resistance (Ni 10 according to GOST) | 10 MΩ | |
| ● Ni 100 | Yes; Standard/climate | |
| — Input resistance (Ni 100) | 10 MΩ | |
| ● Ni 100 according to GOST | Yes; Standard/climate | |
| — Input resistance (Ni 100 according to GOST) | 10 MΩ | |
| ● Ni 1000 | Yes; Standard/climate | |
| — Input resistance (Ni 1000) | 10 MΩ | |
| ● Ni 1000 according to GOST | Yes; Standard/climate | |
| — Input resistance (Ni 1000 according to GOST) | 10 MΩ | |
| ● LG-Ni 1000 | Yes; Standard/climate | |
| — Input resistance (LG-Ni 1000) | 10 MΩ | |
| ● Ni 120 | Yes; Standard/climate | |
| — Input resistance (Ni 120) | 10 MΩ | |
| ● Ni 120 according to GOST | Yes; Standard/climate | |
| — Input resistance (Ni 120 according to GOST) | 10 MΩ | |
| ● Ni 200 | Yes; Standard/climate | |
| — Input resistance (Ni 200) | 10 MΩ | |
| ● Ni 200 according to GOST | Yes; Standard/climate | |
| — Input resistance (Ni 200 according to GOST) | 10 MΩ | |
| ● Ni 500 | Yes; Standard/climate | |
| — Input resistance (Ni 500) | 10 MΩ | |
| ● Ni 500 according to GOST | Yes; Standard/climate | |
| — Input resistance (Ni 500 according to GOST) | 10 MΩ | |
| ● Pt 10 | Yes; Standard/climate | |
| — Input resistance (Pt 10) | 10 MΩ | |
| ● Pt 10 according to GOST | Yes; Standard/climate | |
| — Input resistance (Pt 10 according to GOST) | 10 MΩ | |
| ● Pt 50 | Yes; Standard/climate | |
| — Input resistance (Pt 50) | 10 MΩ | |
| ● Pt 50 according to GOST | Yes; Standard/climate | |
| — Input resistance (Pt 50 according to GOST) | 10 MΩ | |
| ● Pt 100 | Yes; Standard/climate | |
| — Input resistance (Pt 100) | 10 MΩ | |
| ● Pt 100 according to GOST | Yes; Standard/climate | |
| — Input resistance (Pt 100 according to GOST) | 10 MΩ | |
| ● Pt 1000 | Yes; Standard/climate | |
| — Input resistance (Pt 1000) | 10 MΩ | |
| ● Pt 1000 according to GOST | Yes; Standard/climate | |
| — Input resistance (Pt 1000 according to GOST) | 10 MΩ | |
| ● Pt 200 | Yes; Standard/climate | |
| — Input resistance (Pt 200) | 10 MΩ | |
| ● Pt 200 according to GOST | Yes; Standard/climate | |
| — Input resistance (Pt 200 according to GOST) | 10 MΩ | |
| ● Pt 500 | Yes; Standard/climate | |
| — Input resistance (Pt 500) | 10 MΩ | |
| ● Pt 500 according to GOST | Yes; Standard/climate | |
| — Input resistance (Pt 500 according to GOST) | 10 MΩ | |
| Input ranges (rated values), resistors | ||
| ● 0 to 150 ohms | Yes | |
| — Input resistance (0 to 150 ohms) | 10 MΩ | |
| ● 0 to 300 ohms | Yes | |
| — Input resistance (0 to 300 ohms) | 10 MΩ | |
| ● 0 to 600 ohms | Yes | |
| — Input resistance (0 to 600 ohms) | 10 MΩ | |
| ● 0 to 3000 ohms | No | |
| ● 0 to 6000 ohms | Yes | |
| — Input resistance (0 to 6000 ohms) | 10 MΩ | |
| ● PTC | Yes | |
| — Input resistance (PTC) | 10 MΩ | |
| Thermocouple (TC) | ||
| Temperature compensation | ||
| — parameterizable | Yes | |
| — internal temperature compensation | Yes | |
| — external temperature compensation via RTD | Yes | |
| — Compensation for 0 °C reference point temperature | Yes; fixed value can be set | |
| — Reference channel of the module | Yes; 9th channel that can be used as a genuine 9th RTD channel regardless of the parameterization of the other channels, or that can be used for compensation in the case of TC measurement | |
| Cable length | ||
| ● shielded, max. | 800 m; at U; 200 m at R/RTD/TC | |
| Analog value generation for the inputs | ||
| Integration and conversion time/resolution per channel | ||
| ● Resolution with overrange (bit including sign), max. | 21 bit; For measuring mode RTC and TC when using the function “Scalable temperature measuring range” (32 bit REAL format); 16 bit for measuring mode R and U; 16 bit for all measuring modes when using the S7 format (16 bit INTEGER) | |
| ● Integration time, parameterizable | Yes | |
| ● Integration time (ms) | Fast mode: 2.5 / 16.67 / 20 / 100 ms, standard mode: 7.5 / 50 / 60 / 300 ms | |
| ● Basic conversion time, including integration time (ms) | Fast mode: 4 / 18 / 22 / 102 ms; Standard mode: 9 / 52 / 62 / 302 ms | |
| — additional conversion time for wire-break monitoring | Thermocouples, 150 Ohm, 300 Ohm, 600 Ohm, Cu10, Cu50, Cu100, Ni10, Ni100, Ni120, Ni200, Pt10, Pt50, Pt100: 4 ms; 6 kOhm, Ni500, Ni1000, LG-Ni1000, Pt200, Pt500, Pt1000: 13 ms | |
| ● Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 Hz | |
| ● Basic execution time of the module (all channels released) | Corresponds to the channel with the highest basic conversion time | |
| Smoothing of measured values | ||
| ● parameterizable | Yes | |
| ● Step: None | Yes | |
| ● Step: low | Yes | |
| ● Step: Medium | Yes | |
| ● Step: High | Yes | |
| Encoder | ||
| Connection of signal encoders | ||
| ● for voltage measurement | Yes | |
| ● for current measurement as 2-wire transducer | No | |
| ● for current measurement as 4-wire transducer | No | |
| ● for resistance measurement with two-wire connection | Yes | |
| ● for resistance measurement with three-wire connection | Yes; All measuring ranges except PTC; internal compensation of the cable resistances | |
| ● for resistance measurement with four-wire connection | Yes; All measuring ranges except PTC | |
| Errors/accuracies | ||
| Linearity error (relative to input range), (+/-) | 0.02 % | |
| Temperature error (relative to input range), (+/-) | 0.005 %/K | |
| Crosstalk between the inputs, max. | -80 dB | |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.02 % | |
| Temperature error of internal compensation | ±1,5 °C | |
| Operational error limit in overall temperature range | ||
| ● Voltage, relative to input range, (+/-) | 0.1 % | |
| ● Resistance, relative to input range, (+/-) | 0.1 % | |
| ● Resistance thermometer, relative to input range, (+/-) | Cuxxx Standard: ±0.5 K, Cuxxx Klima: ±0.5 K, Ptxxx Standard: ±1 K, Ptxxx Klima: ±0.5 K, Nixxx Standard: ±0.5 K, Nixxx Klima: ±0.3 K | |
| ● Thermocouple, relative to input range, (+/-) | Type B: > 600 °C ±2 K, Type E: > -200 °C ±1 K, Type J: > -210 °C ±1 K, Type K: > -200 °C ±2 K, Type N: > -200 °C ±2 K, Type R: > 0 °C ±2 K, Type S: > 0 °C ±2 K, Type T: > -200 °C ±1 K, Type C: ±4 K, Type TXK/TXK(L): ±1 K | |
| Basic error limit (operational limit at 25 °C) | ||
| ● Voltage, relative to input range, (+/-) | 0.05 % | |
| ● Resistance, relative to input range, (+/-) | 0.05 % | |
| ● Resistance thermometer, relative to input range, (+/-) | Cuxxx Standard: ±0.3 K, Cuxxx Klima: ±0.2 K, Ptxxx Standard: ±0.5 K, Ptxxx Klima: ±0.2 K, Nixxx Standard: ±0.3 K, Nixxx Klima: ±0.15 K | |
| ● Thermocouple, relative to input range, (+/-) | Type B: > 600 °C ±1 K, Type E: > -200 °C ±0.5 K, Type J: > -210 °C ±0.5 K, Type K: > -200 °C ±1 K, Type N: > -200 °C ±1 K, Type R: > 0 °C ±1 K, Type S: > 0 °C ±1 K, Type T: > -200 °C ±0.5 K, Type C: ±2 K, Type TXK/TXK(L): ±0.5 K | |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
| ● Series mode interference (peak value of interference < rated value of input range), min. | 80 dB; in the Standard operating mode, 40 dB in the Fast operating mode | |
| ● Common mode voltage, max. | 60 V DC/30 V AC | |
| ● Common mode interference, min. | 80 dB | |
| Interrupts/diagnostics/status information | ||
| Diagnostics function | Yes | |
| Alarms | ||
| ● Diagnostic alarm | Yes | |
| ● Limit value alarm | Yes; two upper and two lower limit values in each case | |
| Diagnoses | ||
| ● Monitoring the supply voltage | Yes | |
| ● Wire-break | Yes; Only with TC, R, RTD | |
| ● Overflow/underflow | Yes | |
| Diagnostics indication LED | ||
| ● RUN LED | Yes; green LED | |
| ● ERROR LED | Yes; red LED | |
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green LED | |
| ● Channel status display | Yes; green LED | |
| ● for channel diagnostics | Yes; red LED | |
| ● for module diagnostics | Yes; red LED | |
| Potential separation | ||
| Potential separation channels | ||
| ● between the channels | Yes | |
| ● between the channels, in groups of | 1 | |
| ● between the channels and backplane bus | Yes | |
| ● between the channels and the power supply of the electronics | Yes | |
| Permissible potential difference | ||
| between different circuits | 60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels | |
| Isolation | ||
| Isolation tested with | 2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus | |
| Standards, approvals, certificates | ||
| Suitable for applications according to AMS 2750 | Yes; Declaration of Conformity, see online support entry 109757262 | |
| Suitable for applications according to CQI-9 | Yes; Based on AMS 2750 E | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | 0 °C | |
| ● horizontal installation, max. | 60 °C | |
| ● vertical installation, min. | 0 °C | |
| ● vertical installation, max. | 40 °C | |
| Dimensions | ||
| Width | 35 mm | |
| Height | 147 mm | |
| Depth | 129 mm | |
| Weights | ||
| Weight, approx. | 290 g | |
| Other | ||
| Note: | for the R/RDT three-wire measurement, the conductor compensation is made alternating with the measurement; this then requires two module cycles for a measured value | |
| Weight | N/A | 
|---|---|