Article number |
6ES7553-1AA00-0AB0 |
|
S7-1500, TM PTO4 |
General information |
|
Product type designation |
TM PTO 4 |
HW functional status |
FS02 |
Number of channels |
4; Axes |
Product function |
|
● I&M data |
Yes; I&M0 to I&M3 |
● Isochronous mode |
Yes |
Engineering with |
|
● STEP 7 TIA Portal configurable/integrated from version |
STEP 7 V14 or higher |
● STEP 7 configurable/integrated from version |
V5.5 SP3 with GSD file / – |
● PROFINET from GSD version/GSD revision |
GSDML V2.32 |
Installation type/mounting |
|
Rail mounting |
Yes; S7-1500 mounting rail |
Supply voltage |
|
Load voltage L+ |
|
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
19.2 V |
● permissible range, upper limit (DC) |
28.8 V |
● Reverse polarity protection |
Yes |
Input current |
|
Current consumption, max. |
70 mA; without load |
Power |
|
Power available from the backplane bus |
1.3 W |
Power loss |
|
Power loss, typ. |
4 W |
Address area |
|
Address space per module |
|
● Inputs |
18 byte; Per channel |
● Outputs |
10 byte; Per channel |
Digital inputs |
|
Number of digital inputs |
12; 3 per channel, of which 1 DIQ |
Digital inputs, parameterizable |
Yes |
Input characteristic curve in accordance with IEC 61131, type 3 |
Yes |
Digital input functions, parameterizable |
|
● Synchronization |
Yes |
● Probe |
Yes |
● Drive ready |
Yes |
Input voltage |
|
● Type of input voltage |
DC |
● Rated value (DC) |
24 V |
● for signal “0” |
-5 … +5 V |
● for signal “1” |
+11 to +30V |
● permissible voltage at input, min. |
-5 V |
● permissible voltage at input, max. |
30 V |
Input current |
|
● for signal “1”, typ. |
2.5 mA |
Input delay (for rated value of input voltage) |
|
for standard inputs |
|
— parameterizable |
Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
— at “0” to “1”, min. |
4 µs; for parameterization “none” |
— at “1” to “0”, min. |
4 µs; for parameterization “none” |
for technological functions |
|
— parameterizable |
Yes |
Cable length |
|
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Digital outputs |
|
Number of digital outputs |
12; 3 per channel, of which 1 DIQ |
Current-sinking |
Yes; For DQn.0 and DQn.1 push-pull outputs |
Current-sourcing |
Yes |
Digital outputs, parameterizable |
Yes |
Short-circuit protection |
Yes; electronic/thermal |
● Response threshold, typ. |
0.2 A for DQn.0 and DQn.1, 0.9 A for DIQn.2 |
Controlling a digital input |
Yes |
Digital output functions, parameterizable |
|
● PTO (pulse train output) signal interface |
|
— 24 V asymmetrical |
Yes |
— RS 422 symmetrical |
Yes |
— TTL (5 V) asymmetrical |
Yes |
● PTO (pulse train output) signal type |
|
— Pulse and direction |
Yes |
— Count up, count down |
Yes |
— Incremental encoder (A, B phase shift) |
Yes |
— Incremental encoder (A, B phase shift, quadruple) |
Yes |
Switching capacity of the outputs |
|
● with resistive load, max. |
0.1 A; 0.5 A for DIQn.2 |
● on lamp load, max. |
1 W; 5 W for DIQn.2 |
Load resistance range |
|
● lower limit |
240 Ω; 48 ohms for DIQn.2 |
● upper limit |
12 kΩ |
Output voltage |
|
● Type of output voltage |
DC |
● for signal “1”, min. |
23.2 V; L+ (-0.8 V), L+ (-1.3 V) for DIQn.2 |
Output current |
|
● for signal “1” rated value |
0.1 A; 0.5 A for DIQn.2 |
● for signal “1” permissible range, max. |
0.12 A; 0.6 A for DIQn.2 |
● for signal “1” minimum load current |
2 mA |
● for signal “0” residual current, max. |
0.5 mA |
Output delay with resistive load |
|
● “0” to “1”, typ. |
1 µs; 28 µs for DIQn.2 |
● “1” to “0”, typ. |
1 µs; 25 µs for DIQn.2 |
Switching frequency |
|
● with resistive load, max. |
1 kHz; For DIQn.2 |
● with inductive load, max. |
0.5 Hz; According to IEC 60947-5-1, DC-13, for DIQn.2 |
● on lamp load, max. |
10 Hz; For DIQn.2 |
● For signal interface 24 V asymmetrical |
200 kHz; With DQn.0 and DQn.1 |
● For signal interface RS 422 symmetrical |
1 MHz |
● For signal interface TTL (5 V) asymmetrical |
200 kHz |
Cable length |
|
● shielded, max. |
600 m; Cable length, RS 422 / TTL Siemens Type 6FX2001-5: 125 kHz, 320 meters shielded, max.; 250 kHz, 160 meters shielded, max.; 500 kHz, 60 meters shielded, max.; 1 MHz, 32 meters shielded, max. 24 V (DQn.x / DIQn.2): 10 kHz, 600 meters, shielded, max. 200 kHz, 50 meters shielded, max. |
Isochronous mode |
|
Bus cycle time (TDP), min. |
250 µs; 375 µs if all 4 channels are used |
Jitter, max. |
1 µs |
Interrupts/diagnostics/status information |
|
Diagnostics function |
Yes |
Alarms |
|
● Diagnostic alarm |
Yes |
Diagnoses |
|
● Monitoring the supply voltage |
Yes |
● Short-circuit |
Yes; Thermal overload protection |
● Group error |
Yes |
Diagnostics indication LED |
|
● RUN LED |
Yes; green LED |
● ERROR LED |
Yes; red LED |
● MAINT LED |
Yes; Yellow LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; green LED |
● Channel status display |
Yes; green LED |
● for channel diagnostics |
Yes; red LED |
Potential separation |
|
Potential separation channels |
|
● between the channels |
No |
● between the channels and backplane bus |
Yes |
● Between the channels and load voltage L+ |
No |
Isolation |
|
Isolation tested with |
707 V DC (type test) |
Ambient conditions |
|
Ambient temperature during operation |
|
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C; Observe derating |
● vertical installation, min. |
0 °C |
● vertical installation, max. |
40 °C; Observe derating |
Altitude during operation relating to sea level |
|
● Installation altitude above sea level, max. |
5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200MP system manual |
Decentralized operation |
|
to SIMATIC S7-300 |
Yes; Via control and feedback interface |
to SIMATIC S7-400 |
Yes; Via control and feedback interface |
to SIMATIC S7-1200 |
Yes |
to SIMATIC S7-1500 |
Yes |
to standard PROFINET controller |
Yes; Via control and feedback interface |
Dimensions |
|
Width |
35 mm |
Height |
147 mm |
Depth |
129 mm |
Weights |
|
Weight, approx. |
300 g |