| General information |
| Part Number |
6ES7288-1CR20-0AA1 |
| Product type designation |
CPU CR20 AC/DC/relay |
| Engineering with |
| ● Programming package |
STEP 7 Micro/WIN SMART |
| Installation type/mounting |
| Rail mounting |
Yes; Standard – DIN rail |
| Supply voltage |
| Rated value (AC) |
230 V; 230 V AC (L1, N) |
| ● 120 V AC |
Yes; 85 to 132 V AC |
| ● 230 V AC |
Yes; 170 to 264 V AC |
| permissible range, lower limit (AC) |
85 V |
| permissible range, upper limit (AC) |
264 V |
| Reverse polarity protection |
No |
| Line frequency |
| ● permissible range, lower limit |
47 Hz |
| ● permissible range, upper limit |
63 Hz |
| Load voltage L+ |
| ● Rated value (DC) |
24 V |
| ● permissible range, lower limit (DC) |
5 V |
| ● permissible range, upper limit (DC) |
250 V |
| Input current |
| Current consumption (rated value) |
60 mA; At 220 V AC |
| Current consumption, max. |
80 mA; At 220 V AC |
| Inrush current, max. |
16.3 A; at 264 V |
| Power loss |
| Power loss, max. |
6 W |
| Memory |
|
| Type of memory |
DDR |
| Flash |
Yes |
| RAM |
Yes |
| Micro Memory Card |
No |
| CPU processing times |
| for bit operations, typ. |
150 ns; / instruction |
| for word operations, typ. |
1.2 µs; / instruction |
| for floating point arithmetic, typ. |
3.6 µs; / instruction |
| Hardware configuration |
| Integrated power supply |
No |
| Time of day |
| Clock |
| ● Type |
Software clock |
| ● Hardware clock (real-time) |
No |
| Digital inputs |
| Number of digital inputs |
12; Integrated |
| ● of which inputs usable for technological functions |
4; HSC: 4 @ 100 kHz single phase, 2 @ 50 kHz A/B phase |
| Source/sink input |
Yes |
| Input voltage |
| ● Type of input voltage |
DC |
| ● Rated value (DC) |
24 V; DC at 4 mA nominal |
| ● for signal “0” |
< 5 V DC |
| ● for signal “1” |
+15 to +30 V |
| Input current |
| ● for signal “0”, max. (permissible quiescent current) |
1 mA |
| ● for signal “1”, typ. |
4 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — parameterizable |
Yes; 0.2 µs, 0.4 µs, 0.8 µs, 1.6 µs, 3.2 µs, 6.4 µs and 12.8 µs,selectable in 4 groups |
| — at “0” to “1”, min. |
0.2 µs |
| — at “0” to “1”, max. |
12.8 µs |
| for interrupt inputs |
| — parameterizable Yes |
|
| Cable length |
| ● shielded, max. |
500 m; Standard input: 500 m, high-speed counters: 50 m |
| ● unshielded, max. |
300 m |
| Digital outputs |
| Number of digital outputs |
8; Relays |
| Switching capacity of the outputs |
| ● with resistive load, max. |
2 A |
| ● on lamp load, max. |
30 W; 30 W with DC, 200 W with AC |
| Output delay with resistive load |
| ● “0” to “1”, max. |
10 ms; max. |
| ● “1” to “0”, max. |
10 ms; max. |
| Switching frequency |
| ● of the pulse outputs, with resistive load, max. |
1 Hz |
| Relay outputs |
| ● Number of relay outputs |
8 |
| ● Number of operating cycles, max. |
10 000 000; mechanically 10 million, at rated load voltage 100 000 |
| Cable length |
| ● shielded, max. |
500 m |
| ● unshielded, max. |
300 m |
| Interfaces |
| Number of industrial Ethernet interfaces |
0 |
| Number of RS 485 interfaces |
1 |
| Optical interface |
No |
| 1. Interface |
| Interface type |
RS 485 (max. 187.5 kbps) |
| Isolated |
Yes; 500 V AC or 707 V DC |
| Interface types |
| ● RS 485 |
Yes |
| ● Design of the connection |
9-pin sub D socket |
| Protocols |
| Supports protocol for PROFINET IO |
No |
| PROFIBUS |
No |
| Protocols (Ethernet) |
| ● TCP/IP |
No |
| EMC |
| Interference immunity against discharge of static electricity |
| ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 |
Yes |
| — Test voltage at air discharge |
8 kV |
| — Test voltage at contact discharge |
4 kV |
| Interference immunity against high-frequency electromagnetic fields |
| ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 |
Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz,1.89 GHz, 50% ED (to IEC 61000-4-3) |
| — Frequency range of the RF radiation |
10 V/m for 80 MHz ~ 1 GHz, 3 V/m for 1.4 GHz ~ 2 GHz, 3 V/m for 87 MHz ~ 108 MHz, 174 MHz ~ 230 MHz, 470 MHz ~ 790 MHz, 1.4 GHz ~ 2 GHz, 1 V/m for 2 GHz ~ 2.7 GHz |
| Interference immunity to cable-borne interference |
| ● Interference immunity on supply lines acc. to IEC 61000-4-4 |
Yes; ±2 kV acc. to IEC 61000-4-4, burst; surge measurements with additional protective elements |
| ● Interference immunity on signal cables acc. to IEC 61000-4-4 |
Yes; ±2 kV acc. to IEC 61000-4-4, Burst |
| Interference immunity against voltage surge |
|
| ● Interference immunity on supply lines acc. to IEC 61000-4-5 |
Yes; ±1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), ±2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required |
| ● asymmetric interference |
|
| — Test voltage on supply cables |
2 kV |
| — Test voltage on signal cables >30m |
2 kV |
| Interference immunity against conducted variable disturbance induced by high-frequency fields |
| ● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 |
Yes; 10 V, 150 kHz to 80 MHz (to IEC 61000-4-6) |
| Emission of radio interference acc. to EN 55 011 |
| ● Limit class A, for use in industrial areas |
Yes; Emission of radio interference acc. to EN 61000-6-4 +A1 for use in industrial environments |
| Emission of conducted and non-conducted interference |
| ● Interference emission via line/AC current cables |
EN 61000-6-4, interference emission: Intended for use in industrial areas. |
| Degree and class of protection |
| IP degree of protection |
IP20 |
| Standards, approvals, certificates |
| CE mark |
Yes |
| Ambient conditions |
| Free fall |
| ● Fall height, max. |
0.5 m; five times, in product package |
| Ambient temperature during operation |
|
| ● min. |
0 °C |
| ● max. |
55 °C |
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
55 °C |
| ● vertical installation, min. |
0 °C |
| ● vertical installation, max. |
45 °C |
| Ambient temperature during storage/transportation |
| ● min. |
-40 °C |
| ● max. |
70 °C |
| Air pressure acc. to IEC 60068-2-13 |
| ● Storage/transport, min. |
660 hPa |
| ● Storage/transport, max. |
1 080 hPa |
| Altitude during operation relating to sea level |
| ● Installation altitude, min. |
-1 000 m |
| ● Installation altitude, max. |
2 000 m |
| Relative humidity |
| ● Operation at 25 ℃ without condensation, max. |
95% |
| configuration / header |
| configuration / programming / header |
| Programming language |
| — LAD |
Yes |
| — FBD |
Yes |
| — STL |
Yes |
| Dimensions |
| Width |
90 mm |
| Height |
100 mm |
| Depth |
81 mm |
| Weights |
| Weight, approx. |
365 g; approx. |