| Model | EM DI08 | 
| Order No. (MLFB) | 6ES7 288-2DE08-0AA0 | 
| Standard |  | 
| Dimension W x H x D (mm) | 45 x 100 x 81 | 
| Weight | 141.4 g | 
| Power consumption | 1.5 W | 
| Current consumption   (SM bus) | 105 mA | 
| Current consumption   (24 V DC) | 4 mA for each input point used | 
| Digital input |  | 
| Number of input points | 8 | 
| Type | The sinking / sourcing type (IEC type 1 sinking) | 
| Rated voltage | It is 24 V DC when the current is 4 mA, nominal value | 
| Allowable continuous voltage | Max 30 V DC | 
| Surge voltage | 35 V DC, lasting 0.5 s | 
| Logic 1 signal (min) | It is 15 V DC when the current is 2.5 mA | 
| Logic 0 signal (max) | It is 5 V DC when the current is 1 mA | 
| Isolation (field side and logic side) | 500 V AC, lasting 1 min | 
| Isolation group | 2 | 
| Filter time | 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, 12.8 ms | 
|  | (optional 4 inputs form one group) | 
| Number of inputs that connect at the same time | 8 | 
| Cable length (max) | 500m (Shielded), 300m (non shielded) |