| Article number |
6ES7323-1BH01-0AA0 |
6ES7323-1BL00-0AA0 |
|
SM323, 8DI/8DO, DC24V, 0,5A |
SM323, 16DI/DO, DC24V, 0,5A |
| Supply voltage |
|
|
| Load voltage L+ |
|
|
| ● Rated value (DC) |
24 V |
24 V |
| ● permissible range, lower limit (DC) |
20.4 V |
20.4 V |
| ● permissible range, upper limit (DC) |
28.8 V |
28.8 V |
| Input current |
|
|
| from load voltage L+ (without load), max. |
40 mA |
80 mA |
| from backplane bus 5 V DC, max. |
40 mA |
80 mA |
| Power loss |
|
|
| Power loss, typ. |
3.5 W |
6.5 W |
| Digital inputs |
|
|
| Number of digital inputs |
8 |
16 |
| Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Yes |
| Number of simultaneously controllable inputs |
|
|
| horizontal installation |
|
|
| — up to 40 °C, max. |
|
16 |
| — up to 60 °C, max. |
8 |
8 |
| vertical installation |
|
|
| — up to 40 °C, max. |
8 |
16 |
| Input voltage |
|
|
| ● Type of input voltage |
DC |
DC |
| ● Rated value (DC) |
24 V |
24 V |
| ● for signal “0” |
-30 to +5 V |
-30 to +5 V |
| ● for signal “1” |
13 to 30V |
13 to 30V |
| Input current |
|
|
| ● for signal “1”, typ. |
7 mA |
7 mA |
| Input delay (for rated value of input voltage) |
|
|
| for standard inputs |
|
|
| — at “0” to “1”, min. |
1.2 ms |
1.2 ms |
| — at “0” to “1”, max. |
4.8 ms |
4.8 ms |
| — at “1” to “0”, min. |
1.2 ms |
1.2 ms |
| — at “1” to “0”, max. |
4.8 ms |
4.8 ms |
| Cable length |
|
|
| ● shielded, max. |
1 000 m |
1 000 m |
| ● unshielded, max. |
600 m |
600 m |
| Digital outputs |
|
|
| Number of digital outputs |
8 |
16 |
| Short-circuit protection |
Yes |
Yes |
| ● Response threshold, typ. |
1 A |
1 A |
| Limitation of inductive shutdown voltage to |
L+ (-53 V) |
L+ (-48 V) |
| Controlling a digital input |
Yes |
Yes |
| Switching capacity of the outputs |
|
|
| ● on lamp load, max. |
5 W |
5 W |
| Load resistance range |
|
|
| ● lower limit |
48 Ω |
48 Ω |
| ● upper limit |
4 kΩ |
4 kΩ |
| Output voltage |
|
|
| ● for signal “1”, min. |
L+ (-0.8 V) |
L+ (-0.8 V) |
| Output current |
|
|
| ● for signal “1” rated value |
0.5 A |
0.5 A |
| ● for signal “1” permissible range, min. |
5 mA |
5 mA |
| ● for signal “1” permissible range, max. |
0.6 A |
0.6 A |
| ● for signal “1” minimum load current |
5 mA |
5 mA |
| ● for signal “0” residual current, max. |
0.5 mA |
0.5 mA |
| Output delay with resistive load |
|
|
| ● “0” to “1”, max. |
100 µs |
100 µs |
| ● “1” to “0”, max. |
500 µs |
500 µs |
| Parallel switching of two outputs |
|
|
| ● for uprating |
No |
No |
| ● for redundant control of a load |
Yes; only outputs of the same group |
Yes; only outputs of the same group |
| Switching frequency |
|
|
| ● with resistive load, max. |
100 Hz |
100 Hz |
| ● with inductive load, max. |
0.5 Hz |
0.5 Hz |
| ● with inductive load (acc. to IEC 60947-5-1, DC13), max. |
0.5 Hz |
|
| ● on lamp load, max. |
10 Hz |
100 Hz |
| Total current of the outputs (per group) |
|
|
| horizontal installation |
|
|
| — up to 40 °C, max. |
4 A |
4 A |
| — up to 60 °C, max. |
4 A |
3 A |
| vertical installation |
|
|
| — up to 40 °C, max. |
4 A |
2 A |
| Cable length |
|
|
| ● shielded, max. |
1 000 m |
1 000 m |
| ● unshielded, max. |
600 m |
600 m |
| Encoder |
|
|
| Connectable encoders |
|
|
| ● 2-wire sensor |
Yes |
Yes |
| — permissible quiescent current (2-wire sensor), max. |
2 mA |
1.5 mA |
| Interrupts/diagnostics/status information |
|
|
| Alarms |
No |
No |
| Diagnostics function |
No |
No |
| Diagnostics indication LED |
|
|
| ● Status indicator digital input (green) |
Yes |
Yes |
| ● Status indicator digital output (green) |
Yes |
Yes |
| Potential separation |
|
|
| Potential separation digital inputs |
|
|
| ● between the channels |
Yes |
Yes |
| ● between the channels, in groups of |
8 |
16 |
| ● between the channels and backplane bus |
Yes; Optocoupler |
Yes; Optocoupler |
| Potential separation digital outputs |
|
|
| ● between the channels |
Yes |
Yes |
| ● between the channels, in groups of |
8 |
8 |
| ● between the channels and backplane bus |
Yes; Optocoupler |
Yes; Optocoupler |
| Isolation |
|
|
| Isolation tested with |
500 V DC |
500 V DC |
| connection method / header |
|
|
| required front connector |
20-pin |
40-pin |
| Dimensions |
|
|
| Width |
40 mm |
40 mm |
| Height |
125 mm |
125 mm |
| Depth |
120 mm |
120 mm |
| Weights |
|
|
| Weight, approx. |
220 g |
260 g |