| Part Number | 6ES7326-2BF01-0AB0 | 
| Supply voltage |  | 
| Rated value (DC) | 24 V; 1L+ | 
| Reverse polarity protection | Yes | 
| Load voltage L+ |  | 
| ● Rated value (DC) | 24 V; 2L+, 3L+ | 
| ● Reverse polarity protection | No | 
| Input current |  | 
| from supply voltage 1L+, max. | 70 mA | 
| from load voltage 2L+ (without load), max. | 100 mA | 
| from load voltage 3L+ (without load), max. | 100 mA | 
| from backplane bus 5 V DC, max. | 100 mA | 
| Power loss |  | 
| Power loss, typ. | 12 W | 
| Digital outputs |  | 
| Number of digital outputs | 10 | 
| Short-circuit protection | Yes | 
| Limitation of inductive shutdown voltage to | L+ (-53 V) without series diode, L+ (-33 V) with series diode | 
| Switching capacity of the outputs |  | 
| ● on lamp load, max. | 5 W | 
| Output voltage |  | 
| ● for signal “1”, min. | L+ (-1 V) without series diode, L+ (-1.8 V) with series diode | 
| Output current |  | 
| ● for signal “1” rated value | 2 A 7 mA | 
| ● for signal “1” permissible range for 0 to 40 °C, min. | 
| ● for signal “1” permissible range for 0 to 40 °C, max. | 2 A; 2 A for horizontal installation, 1 A for vertical installation | 
| ● for signal “1” permissible range for 40 to 60 °C, min. | 7 mA | 
| ● for signal “1” permissible range for 40 to 60 °C, max. | 1 A; for horizontal installation | 
| ● for signal “0” residual current, max. | 0.5 mA | 
| Switching frequency |  | 
| ● with resistive load, max. | 10 Hz | 
| ● with inductive load, max. | 2 Hz | 
| ● on lamp load, max. | 10 Hz | 
| Total current of the outputs (per group) |  | 
| horizontal installation |  | 
| — up to 40 °C, max. | 7.5 A; without series diode, 5 A with series diode | 
| — up to 60 °C, max. | 5 A; without series diode, 4 A with series diode | 
| vertical installation |  | 
| — up to 40 °C, max. | 5 A; without series diode, 4 A with series diode | 
| Cable length |  | 
| ● shielded, max. | 1 000 m; 200 m for SIL 3, AK 6, Cat 4 | 
| ● unshielded, max. | 600 m | 
| Interrupts/diagnostics/status information | 
| Alarms |  | 
| ● Diagnostic alarm | Yes | 
| Diagnoses |  | 
| ● Diagnostic information readable | Yes | 
| Diagnostics indication LED |  | 
| ● Fail-safe operation | Yes | 
| ● Group error SF (red) | Yes | 
| Potential separation |  | 
| Potential separation digital outputs |  | 
| ● between the channels | Yes | 
| ● between the channels, in groups of | 5 | 
| ● between the channels and backplane bus | Yes | 
| ● between the channels and the power supply of the electronics | Yes | 
| Isolation |  | 
| Isolation tested with | 500 V DC/350 V AC | 
| Standards, approvals, certificates |  | 
| Highest safety class achievable in safety mode |  | 
| ● acc. to DIN VDE 0801 | AK 5 and 6 | 
| ● acc. to EN 954 | Cat. 4 | 
| ● Performance level according to ISO 13849-1 | e | 
| ● SIL acc. to IEC 61508 | SIL 3 | 
| connection method / header |  | 
| required front connector | 40-pin | 
| Dimensions |  | 
| Width | 80 mm | 
| Height | 125 mm | 
| Depth | 120 mm | 
| Weights |  | 
| Weight, approx. | 465 g |