| Standards, approvals, certificates |
|
| developed in accordance with IEC 61131 |
Yes |
| Operating systems |
|
| Runs under operating system |
|
| ● Windows 9x |
No |
| ● Windows ME |
No |
| ● Windows NT 4.0 |
No |
| ● Windows 2000 |
No |
| ● Windows XP |
Yes |
| ● Windows 7 |
Yes |
| Software |
|
| Software class |
A |
| Target system |
SIMATIC CP 341/CP 441-2 |
| Adjustable parameters |
|
| ● Response monitoring time |
100 ms to 25.5 s in 100-ms grid |
| ● Factor for the character delay time |
1 or 10 |
| ● Modem operation (ignore filler characters) |
with/without |
| ● RS 485 operation for 2-wire connection |
with/without |
● Preassignment of receive circuit on application of the
X.27 interface module |
Yes |
| Communication data |
|
| ● CRC polynomial |
X16 + x15 + x2 + 1 |
| ● Receive mailbox |
Specified on BRCV |
| ● Modbus protocol |
with RTU format |
| ● implemented function codes |
01, 02, 03, 04, 05, 06, 07, 08, 11, 12, 15, 16 |
| ● Broadcast Message |
possible |
| ● Transmission rate |
300 bit/s to 76 800 bit/s; (TTY to 19 200 bit/s) |
| ● V.24 control and signal cables |
none |
| ● Character delay time |
3.5 characters or multiples |
| Authorization/licenses |
|
| ● Single license (EL) |
Yes |
| Documentation |
|
| Languages |
|
| ● German |
Yes |
| ● English |
Yes |
| ● French |
Yes |